| Sl. No. | Item Description |
| 1 | Sub Head-I(Wiring) |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 Sq. mmFRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 Sq. mmFRLS PVC insulated copper conductor single core cable etc. as required. |
| 3 | Group B |
| 4 | Wiring for Light /Power Plug with 2 x 4 Sq. mmFRLS PVC Insulated Copper Conductor single core cable in surface/Recessed medium class PVC Conduit along with 1 No. 4 Sq. mmFRLS PVC Insulated copper conductor single core cable for loop earthing as required. |
| 5 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 6 | 1 x 1.5 sq. mm |
| 7 | Wiring for Circuit/Submain Wiring along with earth Wire with the following Sizes of FRLSPVC insulated copper conductor,single core Cable in surface/Recessed medium class PVC conduit as required. |
| 8 | 2 X 2.5 Sq. mm+ 1 X 2.5 Sq. mmEarth Wire |
| 9 | 4 X 16.0 Sq. mm+ 2 X 6.0 Sq. mmEarth Wire |
| 10 | Supplying and fixing modular blanking plate on the existing modular plate and switch box excluding modular plate as required |
| 11 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 12 | 25 mm |
| 13 | Supplying and Fixing suitable size G.I box with modular plate and cover in front on surface or in recess,including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps modular switch,connection,painting etc. as required. |
| 14 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 15 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 16 | Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required.(For Geyser and A.C ) |
| 17 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 18 | 8 way (4 + 24), Double door |
| 19 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 20 | Single Pole |
| 21 | Single pole and neutral |
| 22 | Supplying and fixing following rating, Four pole, 415 V, 10 Ka M.C.B in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 23 | 63 A F.P MCB 10 Ka \\"C\\" Curve |
| 24 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 25 | Supply installation testing and commissioning of Ceiling Fan 3 Star Rated with Voltage Range 90 V to 300 V,Min. Air Delivery 212 CMM,Service Value 5.3 Cu.m/min/watt,Aluminium Blades ,including wiring the down rods of standard length(Upto 45 cm)with 1.5 Sq. mmFR PVC insulated,copper conductor,single core cable including providing and fixing phenolic laminated sheet cover on the Fan Box etc as Required. |
| 26 | 1200 MM |
| 27 | Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminum body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP 66,IK-10, CRI >80, under voltage and over voltage protection, EMI EMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin),SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). |
| 28 | 150 watt |
| 29 | Supply,Installation,Testing and Commissioning 486 Cu.m/Hr. AC 220-240 Volts, 50 Hz exhaust fan made out of Metal Body with inbuilt thermo cutoff Protection and Noise Level not exceeding 37 dB of Following Sizes including connection etc. complete as required . |
| 30 | Supplying, installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K / 6000°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C)Powder coated die cast /Extruded aluminum Body including trim |
| 31 | 12 -15 watt |
| 32 | Supply installation testing and commissioning of IP:20 Decorative Aluminium Batten 10W-12 W +- 1 W LED Surface Mounted 2 ft. with system lumen efficacy of 100 lm/W and P.F >0.9 THD <20% CCT 6500K,CRI 80 .The LED should have life of 50000 Burning Hours at L70.The input voltage shall be 150 V to 270 V.The fixture should have inbuit surge protection of 2KV.Certification-LM 79 and LM 80.The test report should be from Govt. Approved Lab/inhouse NABL Lab. |
| 33 | LED Batten light (System lumen efficacy ≥120 <135 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV ,with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), DCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required , for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 34 | Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) |
| 35 | 40 watt |
| 36 | Supply installation testing and commissioning of IP65 led Bulk head 10 W +/- 1 W LED Surface Pressure Die Cast Aluminum system lumen efficacy of 100 lm/W with Polycarbonate Opal Diffuer and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80, IK rating IK08. The LED with Useful life of 50000 Hrs at L70. The Input voltage range shall be 150V to 265V. The Fixture should have In-built Surge Protection of 2.5kV Certification:- LM79 & LM80 test report should be from govt approved Inhouse NABL lab/ government of India authorised lab . |
| 37 | Supplying and installing following size of perforated HotDipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 38 | 300mm (W) x 50 mm (H) wide cable tray perforated type |
| 39 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 40 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 41 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 42 | Supply installation testing and commissioning of 2.2 KVA Sine Wave Inverter , Input 1 Phase 3 wire and output 1 phase 3 wire with 2 Nos of 12 V 200 aH Battery. |
| 43 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
| 44 | Fixing of lightning conductor finial (single prong) with base plate including holes etc. complete as required. |
| 45 | Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. |
| 46 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) |
| 47 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) |
| 48 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket,bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sandcushioning and protective covering etc., complete as required. |
| 49 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 50 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 51 | Supplying and Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in groundin Existing DWC Pipe including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 52 | 3.5 C X25 Sq.mm A2XFY |
| 53 | 3.5 C X 50 Sq.mm A2XFY |
| 54 | 3.5 C X 185 Sq.mm A2XFY |
| 55 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 56 | 3½ X 25 sq. mm (28mm) |
| 57 | 3½ X 50 sq. mm (38mm) |
| 58 | 3½ X 185 sq. mm (57mm) |
| 59 | Supplying,Installation,Testing and Commissioning of Cubical Type Indoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars etc. as required as per the Following Description.(IP:42)( Building Distribution Panel -1 ) .The successful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel.Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating.The Panel Builder Shall be CPRI /ERDA/ANY NABL ACCREDITED LAB approved.Refer SLD |
| 60 | INCOMER |
| 61 | Adj. TMR Based MCCB 200 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH |
| 62 | 300 A,415 Volts 50Hz Aluminium Busbar set of 4 strips |
| 63 | Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch, Indicating Lamp, CT Set and other necessary relays Required to make it Functional as mentioned in the SLD |
| 64 | OUTGOINGS |
| 65 | MCB 63 A F.P \\"C\\" Curve 10 Ka |
| 66 | Adj. TMR Based MCCB 63 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH |
| 67 | Load Bearing Members to be made out of 2.0 mm CRCA Sheet. |
| 68 | Partitions to be made out of 1.6 mm CRCA Sheet |
| 69 | Gland Plates to be 3.0 mm Thick. |
| 70 | Supplying,Installation,Testing and Commissioning of Cubical Type Indoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars etc. as required as per the Following Description.(IP:42)( Building Distribution Panel -2 ) .The successful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel.Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating.The Panel Builder Shall be CPRI /ERDA/ANY NABL ACCREDITED LAB approved.Refer SLD |
| 71 | INCOMER |
| 72 | Adj. TMR Based MCCB 200 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH |
| 73 | 300 A,415 Volts 50Hz Aluminium Busbar set of 4 strips |
| 74 | Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch, Indicating Lamp, CT Set and other necessary relays Required to make it Functional as mentioned in the SLD |
| 75 | OUTGOINGS |
| 76 | MCB 63 A F.P \\"C\\" Curve 10 Ka |
| 77 | Load Bearing Members to be made out of 2.0 mm CRCA Sheet. |
| 78 | Partitions to be made out of 1.6 mm CRCA Sheet |
| 79 | Gland Plates to be 3.0 mm Thick. |
| 80 | Supplying,Installation,Testing and Commissioning of Cubical Type Indoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars etc. as required as per the Following Description.(IP:42)( Building Distribution Panel -3) .The successful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel.Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating.The Panel Builder Shall be CPRI /ERDA/ANY NABL ACCREDITED LAB approved.Refer SLD |
| 81 | INCOMER |
| 82 | Adj. TMR Based MCCB 100 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH |
| 83 | 200 A,415 Volts 50Hz Aluminium Busbar set of 4 strips |
| 84 | Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch, Indicating Lamp, CT Set and other necessary relays Required to make it Functional as mentioned in the SLD |
| 85 | OUTGOINGS |
| 86 | MCB 63 A F.P \\"C\\" Curve 10 Ka |
| 87 | Load Bearing Members to be made out of 2.0 mm CRCA Sheet. |
| 88 | Partitions to be made out of 1.6 mm CRCA Sheet |
| 89 | Gland Plates to be 3.0 mm Thick. |
| 90 | Supplying,Installation,Testing and Commissioning of Cubical Type Outdoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars etc. as required as per the Following Description.(IP:65)( Transformer Distribution Panel) .The successful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel.Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating.The Panel Builder Shall be CPRI /ERDA/ANY NABL ACCREDITED LAB approved.Refer SLD |
| 91 | INCOMER |
| 92 | Adj. TMR Based MCCB 630 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH |
| 93 | 800 A,415 Volts 50Hz Aluminium Busbar set of 4 strips |
| 94 | Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch, Indicating Lamp, CT Set and other necessary relays Required to make it Functional as mentioned in the SLD |
| 95 | OUTGOINGS |
| 96 | Adj. TMR Based MCCB 200 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH |
| 97 | Adj. TMR Based MCCB 100 Amps FP Icu=Ics=100% Breaking Capacity 36 KA with Extendable ROH |
| 98 | Load Bearing Members to be made out of 2.0 mm CRCA Sheet. |
| 99 | Partitions to be made out of 1.6 mm CRCA Sheet |
| 100 | Gland Plates to be 3.0 mm Thick. |
| 101 | Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 23AWG Twisted Pair Cable in existing conduit/ on surface, Category 6 Unshielded Twisted Pair, 4 pair should be complied as per UL/ETL verification program for compliance with ANSI/TIA-568.2-D standard. Outer diameter should be in the range of 6.1mm nominal with Operating Temperature Range : -5° to +60°C, Bending Radius : < 4 X Cable Diameter at –5°C ± 1°C and Pulling Force : 11.5Kg etc. complete as required. |
| 102 | 1 run of cable |
| 103 | Supplying and fixing of following size Wall Mount Rack having Fixed Structure with 0.8mm CRCA Sheet, completely knocked-down condition (CKD) Shape, Vertical Mounting Rail 1.6 mm with 'U'Marking,Minimum 2 cable entry/exit provision at Top and bottom with rubber protection, Front 5mm Toughened Glass with lock, wall mounting kit, Powder coated Color- RAL- 7035, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbersclosed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required. |
| 104 | 9U Rack |
| 105 | 15U Rack |
| 106 | Supplying Installation Testing and Commissioning of 4MP IP IR Dome Camera having following specifications and features etc :-1) Signal System: PAL/NTSC, Signal to Noise Ratio: >50 dB,Camera should display Camera title, Date & Time in live & recorded video2)Image Sensor: 1/2.8\\" or better progressive Scan CMOS to get color image even at night condition(Minimum Illumination: 0.006 Lux@ F1.4,AGC ON, 0 lux with IR or better) True Day & Night High Performance Mechanical IR cut filter with auto switch, Integrated IR Source (Auto, Manual)- Inbuilt IR LED's with effective distance upto 50 meter or better and 30 meter for colour view in night, Imaging: 1/3s to 1/30000s electronic shutter support, Auto Gain Control , White Balance- Auto, Back Light Compensation,Multi zone Privacy Masking, HLC, Digital Watermarking.3) Compression (Minimum): Video:- H.265 or better,Audio:- G.711U/A, G.711Mu, G.726, AAC, G.7234) Wide Dynamic Range:- WDR (120dB or more)5) Digital Noise Reduction:- DNR (3D) On/Off6) Video Streaming & Frame Rates :- Triple streaming , configurable Main stream: 4MP (2560×1440)25/30fps , Sub streams minimum: 720P@25/30 fps7) Image Setting: Rotate Mode, saturation, brightness, contrast, sharpness adjustable through client software or web browser, Edge Analytics: Tripwire, Intrusion, Motion Detection |
| 107 | 8) Cyber Security: AES 256-bit Encryption,Configuration encryption, trusted execution, Digest,security logs, account lockout, video encryption,IP/MAC filtering, HTTPS, trusted upgrade9) Onboard Storage: Camera should support built-in Micro SD/ SDHC/ SDXC Card slot upto 512 GB. It should be supplied with minimum 128GB memory Card.10) Recording Management: Format SD, overwrite,storage management, video to NAS device,11) Alarm Trigger : Motion/tampering detection;network disconnection detection; IP conflict detection;memory card state detection; memory space detection12)Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP, NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE,NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS,unicast,13) System Capability: ONVIF, Camera shall support open source VMS14) Ethernet: 1 RJ 45 10/100 Ethernet port15) Audio : It should support 1 x Built-In Mic and 1/1 Alarm In/ Out for External Mic. and Speakers as per site requirement.16) Power Input: The camera should support simultaneous dual power input—12 VDC (via power adapter) and PoE (802.3af)—to ensure continuous operation in the event of a failure in one power source. |
| 108 | 17) Power Requirement: 12VDC/24 VDC/PoE (802.3af)/ePoE18) Housing/ Enclosure:- IP67 weather proof, IK10,Metallic body19) Operating Condition:- Ambient Temperature:- (- )05°C to 50°C, humidity 95% (max) (non-condensing)20) IR life: 40000 hours or higher21) Video Bit rate: 32 KBPS - 8 MBPS or better 22) Standards: BIS with ER, STQC Certified, CE, FCC and RoHS |
| 109 | 4MP @ 25/30fps@1440P (2560 x 1440) Dome Camera with 2.8/ 3.6/ 6/8/12 mm fixed lens (as per site requirement). |
| 110 | Supplying Installation Testing and Commissioning of following Channel Network Video Recorder (NVR)with camera licenses to record for all channels having specifications and features etc as mentioned below :1) Network Video Recorder Embedded/ Installed OS (Linux) along with Camera Licenses to record per NVR and to provide a live view, storage and simultaneously Multi-channel playback of all IP camera or more and must be ONVIF with minimum support of 384 Mbps incoming Bandwidth.2) NVR should support video compressions : H.265 or better, H.264, MJPEG.3) Must support 1 channel RCA Input, 2 channel RCA Output for Two-way Talk with G.711U/A, G.711u,PCM, G726 audio compressions.4) Intelligent auto power on when power resumes after power outage.5) Storage: It should support minimum 8 SATA Slots with 20TB capacity/ Slot and RAID support of RAID 0/1/5/6/10.6) Connectivity Interface : 2 Nos. x 10/100/1000 Mbps Ethernet Ports, 1x RS485, 1x RS232, 1x eSATA Port7) Backup Interface : Its should have 4 Nosx USB port (2x USB3.0, 2xUSB2.0)8) Video Output Ports: 2x8) Video Output Ports: 2x HDMI and 2 VGA9) Alarm Ports: It should have 16/8 Ch In/ Out ports to connect various type of external sensors and output devices like hooter/ Siren etc. |
| 111 | 10) Email & SMS Altert options: Option for SMS/Email Alerts to minimum 5 designated mobile number for power failure, HDD failure, vandalism, tempring, network disconnection and panic11) Web & Mobile Application: Web, Mobile app ( For iPhone, iPad, Android Phone) for alerts and viewing.12) Protocols: HTTP, HTTPS, TCP/IP, IPv4/IPv6,UDP, DHCP, DNS, SMTP, UPnP, IP Filter, PPPoE,FTP, DDNS, Alarm Server, IP Search, Multicast, AutoRegistration, ONVIF (Profile T, Profile S, Profile G),CGI, SDK and OEM Cloud for remote monitoring without any public IP need.13) Standards: CE, FCC, RoHS, BIS Certified14) Power Supply : Should support AC100-240V, 50/60Hz Power supply. 15) Operating Condition : -5°C to 50°C, humidity 90% (max) (non-condensing)16) The VMS application shall support all the features & functionalities of the offered cameras.17) VMS should consist Licenses for all channels to record Cameras with General, motion detection,intelligent, alarm and POS recording modes. VMSshould be provided with Camera Licenses , with no dependency of VMS licenses by binding with the MAC address of the cameras to achieve the functionality.18) The NVR OEM shall be responsible for providing a mobile application compatible with both Android and iOS devices, enabling remote monitoring and playback of cameras/NVR footage. |
| 112 | 19) The OEM must provide its own DDNS server hosted in India, eliminating the need for a public IP address for remote monitoring over the Internet.20) Must support Continuous, Alarm, Motion, Instant,Panic Recording Mode21) It should support Resolution: 32MP; 24MP; 16MP;12MP; 8MP; 5MP; 4MP; 1080p; 720p; D1; CIF; QCIF22) When alarm recording is enabled and an event occurs, you can click the alarm icon on monitoring page to view the alert details. The snapshot function issupported on monitoring and playback page23) The Network Video Recorder (NVR) shall be configured to send email whenever a system message is created or an alarm event occurs. The email server shall be a valid SMTP server. Each recipient email address shall be configured to receive any combination of critical, warning, or informational messages or alarm notifications. When an alarm occurs, the email message includes the NVR name,time of alarm and a list of camera that is configured to record upon alarm24) It should have Web and GUI interface.25) Built-In Artificial Intelligence: NVR should have built-in AI :-- 2 Channel face detection and recognition, - Minimum 4 Channel perimeter protection, - Minimum 8 Channel Smart Motion Detection26) Face Recognition Database Capacity: It should support total Blacklist and Whitelist capacity of Minimum 20,000 Faces or more with Face Detection speed of 12 face images/sec and facility to add Name,gender, birthday, address, credential type, credential No., countries & regions and state to each face image. |
| 113 | 27) Face & Human Attributes Search: Search Pictures/ Video by Gender, age group, glasses,expressions, face mask, beard, Top color, top type,hat, bag, age, gender and umbrella.28) ANPR Capability: It should support ANPR Camera with License plate, plate color, vehicle body,vehicle model, vehicle logo, calling, seatbelt, vehicleregistration location etc vehicle attributes.29) Alarm Notifications based on: Motion detection, video tampering, video loss, scene changing, PIR alarm, Camera external alarm, Face detection, face recognition, perimeter protection (intrusion and tripwire), ANPR, people counting, stereo analysis, crowd distribution, heat map, Disk Full, Storage Error,IP Conflict and abnormal behavior of fan, cybersecurity exception30) Alarm Notification should be linked with Recording, snapshots, Camera external alarm output, buzzer, logs, presets and email.31) General AI Based Search: Search Pictures by channel, time, event type, target classification (Fall Detection, People Approach Detection, People No. Exception Detection, People Staying Detection, Violence Detection.32) Smart playback function: Should support smart search for the selected area in the video and smart playback to improve the playback efficiency33) VCA (Video Content Analytic): Should support multiple video contented analytics based on camera analytics34) Analytics by NVR: Perimeter protection and face recognation |
| 114 | 32 Channel Network Video Recorder (NVR) having display split :- Main screen: 1/4/8/9/16/25/32(36), 2nd screen: 1/4/8/9/16 |
| 115 | Supplying, Installation, Testing and Commissioning following capacity Serveillance grade Hard Disk with upto 256MB/s Transfer Rate, 256 MB Cache, 7200 RPM Disk Speed, 3.5 inch form factor, SATA Interface, BSMI, ICES-003/NNB-003, CE, FCC, KC,Maghreb, RCM, UKCA, VCCI, CB-Scheme, TUV, UL Certifications. |
| 116 | 10TB (Terabytes) |
| 117 | Supply and fixing following port Rack Mount loaded LIU with pigtail, Front-mounted cable saddles for jumper management, suitable to manage both splicesand terminations, Pre-assembled shelves in multiple configurations, Rubber fiber slotted bracket built-in,metal splice shelf to protect the fibers, 2 fiber spoolsbuilt-in for 900μm tight buffered fiber storing, Capable of storing up to 3 meters of 900μm tight buffered fiber per adapter, Removable front and rear covers forbetter access to interior of LIU, Should be Single /Multi mode LC Type fully loaded. Accessory kit consists of cable ties, mounting ear screws, and spiralwrap tube etc complete as required. |
| 118 | 24 Port LIU |
| 119 | Supplying, Installation, Testing and commissioning of following CAT6 Patch Cord should have ETL/UL verification program certificate for compliance withANSI/TIA-568.2-D etc. complete as required. |
| 120 | Copper Patch Cords of length 1m (3ft) |
| 121 | Copper Patch Cords of length 3m (10ft) |
| 122 | Supplying, Installation, Testing and commissioning of RJ45 Connector for CAT 6/6A Cables. RJ45 modular plug supports 4 twisted pairs, 8 positions, 8connectors. Housing: PC, UL94V-2, transparent color,Use for 24- 26 AWG stranded wires etc. complete as required. |
| 123 | Supplying, Installation, Testing and commissioning of CAT6 Copper Information Outlet (IO) with face plate of color as per site requirement, should have ETL/ULverification program certificate for compliance with ANSI/TIA-568.2-D. All copper Cable and Components should be from same OEM to maintain compatibility and interoperability etc. complete as required. |
| 124 | Supplying, installation, Testing and commissioning of following capacity 24 port Layer 2 indoor Network Switch having features and specifications etc. asmentioned here under: At least 24 X RJ-45 Gigabit Ethernet Ports and additional 2 X 10G Base -T with 4 X SFP Ports with non-blocking architecture by havingSwitching capacity of min. 168Gbps and packet forwarding rate of 125Mpps or higher, 16K MAC table.Console Port, USB port, Stacking support of min. 8units per stack. Internal dual AC Power supply, STP,RSTP, MSTP, BPDU Filter, BPDU Restriction, Min. 9K Jumbo Frame, LBD, IGMP Snooping V1/V2/V3, MLDSnopping V1/V2. IGMP /MLD Groups 1K or more, IPv4/IPv6 Loopback Interface, 16 L3 IP Interface, Ipv6 ND, VRRPv3, UDP Helper, ECMP. VLAN: 802.1Ǫ,Port based, Ǫ-in-Ǫ, Multicast VLAN, Protocol VLAN,VLAN Trunking, DHCP Snopping, Server, server Screening. RADIUS , TACACS+ Authentication, ǪoS: 802.1P, 8 queues per port, ǪoS : WRR, Strict+WRR,WRED, 802.1p. ACL: MAC based, IPv4C IPv6,TCP/UDP Port number, time based ACL, TFTP Client,SNMP V1, v2c, v3, SNMP traps, RMON, DHCP server, relay, client, LLDP, LLDP-MED, OAM, Dying Gasp, 802.3ah, sflow, RIP, OSPF v2/v3, policy basedroute, SSL, SSH. 6 kV surge protection on all Gigabit Ethernet ports and on all GE RJ-45 access ports.Certifications: UL, CE, FCC, RoHS, MTCTE,OEM/Product must be on Trusted Telecom Portal of Department of Telecommunication, Government of India etc. complete as required. |
| 125 | 24 port PoE Layer 2 Network Switch with PoE Support of 370W or higher with each copper port supporting 802.3at PoE+ min. |
| 126 | Supply, installation, testing and commissioning of Junction Boxes/DB-10 Pairs with Original Krone module and Back Mount Frame and have Lock -n- key, complete in all respect as per specification and desired by EIC |
| 127 | Supply,Installation,Testing and Commissioning of Media Converter. |
| 128 | Supply & Erection of Termination Box complete as per specification and as desired by EIC. |
| 129 | Supplying,Installation,Testing and Commissioning of 55 Inches Ultra H.D LED Display Monitor as per the Specifications attached. |
| 130 | Suplying and fixing following modular switch/ socket on the existing modular plate & switch box inculding connection but excluding modular plate etc. as required. |
| 131 | Telephone socket outlet |
| 132 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. |
| 133 | 1 or 2 Module (75mm x 75mm) |
| 134 | Fire Detection |
| 135 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices(including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card,minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. |
| 136 | Two Loop Panel. |
| 137 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 138 | Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required. |
| 139 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 140 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 141 | Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required. |
| 142 | Supplying,Installation,Testing and Commissioning of CO2 Type Fire Extinguisher 4.5 Kg. Capacity ISI Mark(IS:15683)suitable for 'B' and 'C' class fires - inflammable liquids, gaseous fires like L.P.G. and acetylene, and electrical fires |
| 143 | Supplying,Installation,Testing and Commissioning of MAP 90 ABC Type Fire Extinguisher 4.0 Kg. Capacity ISI Mark(IS:15683)suitable for Class A/B/C Type Fires . |
| 144 | Diversion Line 33 KV |
| 145 | Supply of Steel tabular poles as per 410 SP 33 with base plate of size 1.5’x1.5’ x 8 mm with GI rod for earthing , painting , Earthing rod and spirla earthing etc . |
| 146 | Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. |
| 147 | Above 8.0 metre and upto 10.0 metre |
| 148 | Above 6.5 metre and upto metre 8 Mtr |
| 149 | Supply and laying of ACSR Rabbit conductor 0.05 with jumpering and termination works. |
| 150 | Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg permetre) V shape cross arm for two 11 KV over head line conductors complete with 50 mm X 6mm M.S. flat iron clamps,bolts and nuts including drilling holes for insulator pins, bolts, F-top,nuts and washers etc (as per drawing) and painting with primer and finish paint as required. |
| 151 | Supplying and erection of 33 KV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required. |
| 152 | Dismantling of over head lines comprising of copper/ aluminium over head conductor, G.I. wire, cross arms, insulators etc. asrequired. |
| 153 | Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required. |
| 154 | GI Ch iron 10x50x6mm x 8 ft |
| 155 | S/l of Guy with turn buckler and Guy insulator etc, 8 SWg twisted GI wire laid in cement concrete . Complete job in all respects. |
| 156 | Note:-The rates quoted are inclusive of all carriages of materials (Mechanical/Manual) from source to site work and all extra charges including dewatering if any during the execution of work till complete in all respects. Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail