| 1 | PART (A) |
| 2 | Operation, keeping the equipment and minor maintenance in premises of RO plant neat & tidy from 9.00 AM to 5.00 PM as per the instruction of EIC. (1 nos. semiskilled labour per RO per day*11 nos. RO = Total 11 semiskilled labour per day) |
| 3 | Labour charges for cleaning with blowering/servicing of electrical items of 11RO = 01job (01 skilled and 02 unskilled = 01×805+2×541=1887 In every month minimum two times work will be done). |
| 4 | Providing cartridge filter of 4”×20”×5 micron for RO plant as per instruction EIC. |
| 5 | RO membrane cleaning chemical |
| 6 | RO antiscalant |
| 7 | Labour charges for taking out the submersible pumping set for tubewell after completion of yield test or development of tubewell (submersible pumping set upto 2.2kwh). |
| 8 | Labour charges for lowering single phase 11.00 submersible pump. |
| 9 | Providing and fixing PTMT bib cock of approved quality and colour, 15mm nominal bore, 86 mm long, weighing not less than 88 gms. |
| 10 | Providing and fixing gun metal non-return valve of approved quality (screwed end): 25 mm nominal bore Vertical. |
| 11 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. INTERNAL WORK EXPOSED ON WALL: 25 mm nominal outer dia Pipes. |
| 12 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. INTERNAL WORK EXPOSED ON WALL: 20 mm nominal outer dia Pipes. |
| 13 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. INTERNAL WORK EXPOSED ON WALL: 15 mm nominal outer dia Pipes. |
| 14 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade Old work (one or more coats applied @ 0.83 ltr/10 sqm). |
| 15 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : One or more coats on old work |
| 16 | Distempering with 1st quality acrylic distember (Ready mix) having VOC content less than 50 grams/ litre of approved brand and manufacture to give an even shade: Old work (one or more coats). |
| 17 | Lettering with black Japan paint of approved brand and manufacture. |
| 18 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering. All work up to plinth level 1:2:4 (1 cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size). |
| 19 | 12 mm cement plaster of mix: 1:6 (1 cement : 6 fine sand). |
| 20 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 21 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS: 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement: 4 Coarse sand), jointing with grey cement slurry @ 3.3kg/sqm including pointing the joints with white cement and matching pigment etc., complete. |
| 22 | Brick work with FALG bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 23 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS: 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. Circular tank. |
| 24 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External work: 50 mm dia nominal bore. |
| 25 | Wiring for circuit/submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/recessed steel conduit as required (2 X 10 sq. mm + 1 X 6 sq. mm earth wire). |
| 26 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required (1 x 1.5 sq. mm). |
| 27 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required (5/6 amps switch). |
| 28 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required (2 way 5/6 A switch). |
| 29 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required (15/16 A switch). |
| 30 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required (6 pin 15/16 A socket outlet). |
| 31 | Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required (63 A TP&N). |
| 32 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required (63 A). |
| 33 | Providing with fitting DOL 3Hp Single Phase Dol Starter with complete safety accessories (Provided with protection degree IP 54, FRLS (fire retardant low smoke) internal wiring, overload, short circuit device). |
| 34 | Providing with fitting DOL 3Hp three Phase Dol Starter with complete safety accessories (Provided with protection degree IP 54, FRLS (fire retardant low smoke) internal wiring, overload, short circuit device, single phase preventor). |
| 35 | Wiring for circuit/submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required (2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire). |
| 36 | Supply of 1.5HP 3 Phase Submersible Pump (head above 65Meter, High Operating Efficiency Designed for Wide Voltage Operation, Motor Portion Covered with Corrosive Resistance Stainless Steel). |
| 37 | Supply of 1.5HP one Phase Submersible Pump (head above 65Meter, High Operating Efficiency Designed for Wide Voltage Operation, Motor Portion Covered with Corrosive Resistance Stainless Steel). |
| 38 | Repairing of 1HP/3HP submersible pump with complete copper winding and other accessories etc. |
| 39 | Total impact of GST for the purpose of CTC Please Enable Macros to View BoQ information |