| 1 | Supply, Installation, Testing & commissioning of (500) KVA Silent DG set with STD Panel- 3 Phase comprising of CUMMINS make Engine Model No. QSM 15-G1 coupled to 415 Volt 3 phases Stamford make alternator mounted on a common base frame along with other accessories i.e. Fuel tank, Battery with leads. (Make - Cummins, Kirlosker, Greaves cotton) |
| 2 | Charges of annual Operation contract of Internal Electrical, airconditioning, fire fighting and fire alarm, CCTV, Travellator skywalk between sector-51 and sector-52 Metro Station, Noida. Details of Manpower deputed in only one shift for all services as follow:-1) Internal electrical system :- a)- 1 No. Highly Skill @ 41444-00 pm, b)- 1 No. Skill @ 34241.00 c)- 1 No. Un Skill manpower. @ 25270.002) CCTV system :- a) 1 No. Skill manpower.@ 34241.003) Travellator - a) 1 No. Skill @ 34241.00, b) 1 No. Un Skill manpower.@ 25270.004) Fire fighting system & Fire alarm system :- a) 1 No. Skill @ 34241.00, b) 1 No. Un Skill manpower @ 25270.005 HVAC system :- a) 1No. Skill @ 34241.00, b) 1 No. Un skill manpower@ 25270.006) for Care Taker Staff:- a) 2 No. Skill @ 34241.00 (total cost of 1b+2+3+4+5) = 272285.00 for A & B shiftTotal cost of 1a = 41444.00 for General ShiftTotal Cost of 6 = 34241x2 = 68482.00Grand total = 382211.00 per months |
| 3 | Earth work in excavation by mechanical means(Hydraulic excavator) over areas( exceeding 30cm in depth 1.5m in width as well as 10sqm on plan) including getting out ADN disposal exacavated earth . Lead upto 50M and lift upto 1.5 m, as directed by E/I. The contractor has detected different utilities like sewer line, Water Pipe line, Electric cable, Telephone cable, gas pipe lne etc. using utiity detecting machine before start of excavation only after getting permision of E/I All kinds of soil. (AOR) |
| 4 | Centering and shuttering including strutting, propping etc. and removal of form for : -a)-Foundations, footings, Bases of columns, etc. for mass concrete (DSR Civil-18/I.No.-5.9.1/P-96) |
| 5 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete up to plinth level. -a)-Cold twisted bars. (AOR) |
| 6 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level-a)- 1:4:8 (1 Cement : 4 coarse sand(zone-III) : 8 graded stone aggregate 40 mm nominal size). (DSR Civil-18/I.No.-4.1.8/P-86) |
| 7 | b)- 1:2:4 (1 Cement : 2 coarse sand(zone-III) : 4 graded stone aggregate 20 mm nominal size). (DSR Civil-18/I.No.-4.1.3/P-86 ) |
| 8 | Supplying and laying of aluminium conductor PVC insulated armoured, served, sheathed cable 1100 Volts grade at a depth of 750 mm. below ground level over a cushion of 75 mm. thick sand alround and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. Clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respects. the armouring of the cable shall be properly connected with the earth conductor by clamps etc. (KEI/Polycab, Havell's make) |
| 9 | 1) 240 Sq.mm. 3.5 Core |
| 10 | S/F of Palm or Pin type copper tin plated cable socket (lugs) to the cable lead insulation with tape and making connections complete as per direction of E/I. P.S. No. 504 |
| 11 | 1- 240 sq. mm |
| 12 | 2- 120 sq. mm |
| 13 | Supply and burying earth for lighting conductor of 900mm x 900mm x 3mm copper plate vertically with its top at least 3 metres below ground level complete with 20mm dia G.I. pipe for watering funnel, 30cm square C.I. frame with hinged cover masonry housing alternate layers of charcoal/coke and salt at least 150mm thick alround etc. as per directions of Engineer-in-charge complete in all respect. .(P.S. No 709 |
| 14 | Supply and burying of 600mm x 600mm x 3mm copper plate vertically for earthing with its top at least 3 metres below ground level complete with 20mm dia G.I. pipe and funnel for watering and two earthing lead of two no. 8 SWG copper wire in 15mm dia G.I. pipe up to switch board (from appron to switch board the cost of G.I. pipe and copper wire will be extra) 30cm square C.I. frame with hinged cover masonry housing alternate layers of charcoal/coke and salt at least 150mm thick alround etc. complete in all respect.. .(P.S. No 704 |
| 15 | Supply and laying of 32mm x 6mm copper strip from earth electrode directly in the ground as required complete in all respect.. .(P.S. No 718 |
| 16 | Supply and laying of 32 mm x 6 mm G.I. strip from earth electrode directly in the ground as required complete in all respect. .. .(P.S. No 717 |
| 17 | Supply, Installation, Testing & commissioning of Sheet Moulded Compound and Thermoplatic LT Distribution box of size 1800x4100x1200mm, for 3 Phase Out door connection to LT Line consumers through incl. 1000A TPN ALUMINIUM BUSBAR having these accessores & equipments :-1. INCOMER FOR TRF 1 &2a) 02 Nos. 630A FP 50KA ACB EDO TYPE - MPR O/L, S/C E/F (L&T/LEGRAND make)2-METERING :-a) 02 Nos. MULTIFUNCTION METER (Make- AE/LK)b) 06 Nos. 630/5A CT CLASS-1 (Make- AE/KAPPA )c) 06 Nos. INDICATION LED LAMP RYB (Make- L&T / Siemens/VISHNO )d) 06 Nos. ON/OFF / TRIP INDICATING LIGHT (Make- L&T / Siemens/VISHNO )d) 14 Nos. 2A SP MCB (Make- L&T / Legrand)3) BUSCOUPLER :-a) 1 No. 800A FP 50KA ACB EDO TYPE - MPR O/L, S/C E/F (Make- L&T / Legrand)b) 02 Nos. INDICATION LED LAMP RYB (Make- L&T / Siemens/VISHNO )c) 02 Nos. 2A SP MCB (Make- L&T / Legrand) |
| 18 | 4) INCOMER FOR DG SET :-a) 1 No. 800A FP 50KA ACB EDO TYPE - MPR O/L, S/C E/F(Make- L&T / Legrand) |
| 19 | 5) INCOMER FOR DG SET :-a) 1 No/ Multifunction meter (AE/LK make)b) 03 Nos. 630/5A CT CLASS-1 (AE/KAPPA make)c) 03 Nos. INDICATION LED LAMP RYB (L&T / Siemens/VISHNO make)d) 03 Nos. ON/OFF/ TRIP INDICATING LIGHT(L&T / Siemens/VISHNO make)e) 07 Nos. 2A SP MCB (Make- L&T / Legrand) |
| 20 | 6) AMF SYSTEM :-a) 01 No. DC AMMETER 0-30Ar (AE/RISHABH make)b) 01 No. DC VOLT METER 0-50A (AE/RISHABH make)c) 01 No. AMF LOGIC RELAY (PROCOM/AE make)d) 02 Nos. 32A DP MCB (L&T / Siemens/VISHNO make)e) 04 Nos. PUSH BUTOON WITH ELEMENT (Make- L&T/LK / Legrand)f) 05 Nos. AUXILIARY RELAY 230V AC WITH 2NO+2NC (OMRON make)g) 01 No. BATTERY CHARGER (NHP Make)h) 10 Nos. NORMAL TERMINALS 2.5MM (SALZER make)i) 01 No. AUTO MANUAL SEL SWITCH (SALZER make)j) 02 Nos. ON/OFF LIGHT (L&K/LK/LEGRAND) |
| 21 | Outgoinga) 03 Nos. 630A FP MCCB WITH ROTARY HANDLE ANDSPEADER LINK- TMR (L&T/LEGRAND MAKE) |
| 22 | including Nuts, Bolts, Washers, Ferul Numbers, Cable Ties, TieBase, Copper PVC Control Wire, Power Wire, CopperThimbles, Panel Locks, I-Hooks, PVC Tape, InsulatorsE-type, L-Type , Round Type, MCB Chanel, Pvc Chanel,Connector Chanel, Connectors, Foam Gaskit Etc |
| 23 | TECHNICAL SPECIFICATIONS / CONSTRUCTIONAL FEATURES |
| 24 | ConstructionPanel shall be free standing floor /wall mounted, dust and vermin proof constructionLoad Bearing - 2.0 mm. CRCA sheetNon load Bearing - 1.6 mm. CRCA sheetGland Plate -2.0 mm. undrilled detachable |
| 25 | Paint- Surface of enclosure shall be pre treated by seven tank process.- Powder Coated, inside and outside Siemens Grey,(RAL7032)- Base frame shall be painted with Black |
| 26 | Bus bars- Electrolytic grade Copper bus bars of required ratings shall be provided- Busbar shall be supported on SMC supports.- Busbar shall be insulated with heat shrinkable PVC sleeves color coded |
| 27 | Name Plates- Each feeder shall have engraved anodized Al nameplates with each feeder details & rating offeeder.- Feeder name plates, Panel name plate and manufacturers name plate shall be secured by screws- MV Danger notice plate shall be provided |
| 28 | Earth bus- A continuous earth bus of Al shall run at bottom. |
| 29 | Panel shall have removable gland plates at Top/Bottom as required |
| 30 | Bus bars & Cable entry shall be from Top/Bottom as required |
| 31 | Wiring- All internal wiring with PVC insulated Copper wires.- Current Transformers secondary circuit shall be wired by 2.5sq.mm PVC insulated copper wires.- Control wiring shall be with 1.5sq.mm PVC insulated copper wires.- Identification ferrules shall be used at both ends of wires |
| 32 | Necessary control fuses &terminals provided as required |
| 33 | Important Notes- Any change in specifications, rating and feeder quantity will attract price revision (if any)- Cable Glands are not considered in our scope.- Equipment will offered for following routine test only.Check of Bill of Materials as per approved drawingVisual and dimnl. Check.Functional check.HV/Megger test as per relevant IS. |
| 34 | The panel supply and installation with all above accessories complete in all respects as per direction of E/I (Make - Tricolite, Advance, L & K, R P Control, Legrand) Please Enable Macros to View BoQ information |