| 1 | Supply installation, testing and commissioning of Silent Type -Floor Mounted Diesel Generator set CPCB IV+ Compliance model of 250KVA ,1500 RPM,0.8 Lagging power factor,3 phase Alternator at 415 volt suitable for 50Hz, 3 phase system & for 0.85 load factor and consisting of the following i/c DG Change over panel / AMF panel & supply with minimum 300 litres of fuel during the time of installation along with : DEF Tank Capable of 10-12 Hrs of Operation. a) Diesel Engine:-4 stroke, liquid cooled, Six cylinder in Line, electric start, exhaust mainfold with SS exhaust flexible, flywheel and flywheel housing, fule and lube oil filters, HDAC/Dry type air cleaner, starter motor, battery charger, capable of taking 10% over loading for one hour in 12 hours of continuos operation.Fuel consumption at 75% load should not be more than 40 litres(Considering 0.845 specific gravity of diesel,+1% tolerance),change of lubricrant oil should be at minimum 500 hrs or 1 year & lube oil consumption at 100% load should be <0.1% of FC. The engine to be fitted complete with all the required accessories. (With 5 years warranty from the date of installation or 5000 hours of running whichever is earlier). |
| 2 | b) Engine mounted Instrumental panel fitted with and having digital display for following:-Start-stop switch with key,Engine Temperature indication,Lubrication oil temperature indication,Battery Charging indication,starting Battery Voltage indication,Over speed indication,Low lub Oil trip Indication,Engine running hours Indication.Oil pressure indication. c) Alternator:- synchronous alternator rated at minimum 250 KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor, temperature rise at 125 Degree C.Brushless Single Bearing, (4 pole), rotating field, solid state voltage regulator, voltage regulation +- 1%, insulation class H, sealed type 1 bearing, flex disc coupling, 100% rating of one step load accaptance, 25% of rated amps of unbalanced load capability. The alternator shall be having silent acoustic enclosure of IP23.(minimum 2 years warranty from the date of installation) d) Fuel Tank:-Daily service fuel Tank suitable for minimum 6 hrs of operation on full load capacity fabricated out of 3 mm thick M.S sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ' c' pipes of suitable dia complete with valves, level indicators and accessories as required as per specifications.e) Exhaust System :-Residential silence type with minimum 05 mtr Exhaust Pipe, max allowable back pressure 10.0 kPa ,exhaust temperature 515 °C. |
| 3 | f) Starting System:-12 V/ 24 V DC starting system comprising of starter motors voltage regulator and arrangement for initial excitation complete with suitable nos. of batteries (25 plates, 180 Ah capacity lead acid type) as required as per specifications.g) Enclosure:-Powder coated weather proof (IP23) canopy Engine and alternator mounted on AV mounts with, with silence-acoustic type and SS exhaust below optimised to meet stringent MOEF / CPCB norms for sound and emission-Baserail with drawout type fuel tank, drain plug, inlet and outlet connections, airvent, level gauge. h)AMF CONTROLLER:- The system shall operate on 24V DC power and include Automatic Mains Failure (AMF) and Automatic Transfer Switch (ATS) functions. It shall have CAN bus and serial communication facilities. The device shall provide protection as per ANSI codes: 27P (under voltage), 59 (over voltage), 81U (under frequency), 81O (over frequency), 50TD (time delay overcurrent), 32F (forward power), 32R (reverse power), 14 (under speed), 12 (over speed), and 51 (inverse time overcurrent) . BREAKER DETAILS:- Three (03) numbers of MCCB( one for incomer, one for DG and one for outgoing ) shall be provided, each rated at 400A, 4-pole, with a breaking capacity of 36kA (Icu = Ics = Icw for 1 second with adjustable settings). |
| 4 | METERING & INDICATIONS:- The metering and indication system shall include four multifunction meters capable of measuring voltage, current, frequency, power factor, kilowatt, kilovolt-ampere, energy in KWh (old), on and run hours, with site-selectable kWh/kVAh display, accuracy class 0.5, auxiliary supply of 80–300V AC/DC, LED display, One (01) DC analog voltmeter of range 0–30V DC (MI type) and one (01) DC analog ammeter of range 0–30A DC (MI type) shall be provided. Indication lamps shall be provided as follows: red, yellow, and blue lamps operating at 230V AC; white lamp operating at 24V DC. All indication lamps shall be of cluster LED type of 22.5mm dia. CT DETAILS:-Three (03 sets. of Current Transformers (CTs) shall be provided, each having a rating of 400A/5A. BATTERY CHARGER:- One(01) no. of battery charger shall be provided of CCCV type. CONTROL CIRCUIT ACCESSORIES:- The control circuit accessories shall consist of push button actuators (green, red, and emergency type), TNC switches, contact block modules (NO and NC), control relays with relay bases, selector switches,MCB as suitable for above installation |
| 5 | Supply and fixing of extra exhaust pipe beyond the exhaust pipe provided with DG set. (i)150 mm dia MS pipe including fabrication, painting etc as required:- |
| 6 | Earthing with 40 mm dia G.I. Earth pipe (medium gauge) 4.5 m. long complete with masonry enclosure on top CI cover plate size 12\\"x 12\\" having locking arrangement including CC work, holes on earth pipe etc. as required. |
| 7 | Extra for using salt (5 kg) and charcoal (46kg) for pipe earth electrode as required. |
| 8 | Proving and fixing / drawing of 4.06 mm dia (8 SWG) G.I. wire on surface or in existing G.I/ PVC/ Polythene pipe for loop earthing as required. |
| 9 | Providng and laying 15mm dia (medium gauge) G.I. pipe for drawing of 4.06mm (8SWG) dia G.I./ Copper wire for earth connection from earth electrodes etc as required. |
| 10 | Earthing with Copper earth plate 600 mm x 600 mm x 3 mm thick i/c accessories and providing masonry enclosure with CI cover plate Size 12\\"x 12\\" having locking arrangement, along with 20 mm dia (medium gauge) watering pipe including CC work etc as required:- |
| 11 | Supply and fixing of 25mm x 3mm Copper on walls/ floor of the building for horizontal/ vertical network including necessary spacers and porcelain insulators at regular intervals. |
| 12 | Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick i/c accessories and providing masonry enclosure with CI cover plate Size 12\\"x 12\\" having locking arrangement, along with 20 mm dia (medium gauge) watering pipe including CC work etc as required:- |
| 13 | Extra for using salt (12 kg) and charcoal (96kg) for plate earth electrode as required. |
| 14 | Supply and fixing of 25mm x 5mm GI strip on wall/ floor of the building for horizontal/ vertical run including necessary spacers and porcelain insulators at regular intervals. |
| 15 | SITC of floor mounted (outdoor type) Feeder panel having Dimension of[1200(H) X 1400 (W) X 400 (D) mm] & degree of protection IP55 fabricated with 16 SWG (1.6 mm) CRCA sheet and 1.6mm thick passivated gland plate(dust and vermin proof) with 400A TPN Aluminium Busbarbusbar shall be provided as per made of EC-grade aluminium, designed considering a current density of 1.0A/sq.mm,25x6 mm GI Earth bus throughout the length of the panel board having provisions for cable entry through bottom side only along with following necessary switchgears:- INCOMERS:- 1) 400A FP,36kA thermal magnetic MCCB:- 01 no, 2) 400A FP Spreader terminal:- 02 set, 3) 3phase digital LED type Display Multifunction Meter- 01 no, 4) LED type Phase Indicator Lamp(Red-Yellow-Blue):- 03 nos, 5) 6 A,single pole-10kA, C-curve MCB for Control unit:- 03 nos, 6) 320/5A Class-15 VA Tape wound CT coil-03 nos {Make:- C & S/ L & T/Mediatech/Snheider/Rishabh} OUTGOING:-1) 160A,FP-25kA Thermal Magnetic MCCB:- 02 nos, 2) 160A ,FP,Spreader Terminal:- 04 set, 3)125A,FP,25kA Thermal Magnetic MCCB:- 01 nos, 4) 125A,FP Spreader Terminal:- 02 set, 5)100A,FP-25kA Thermal Magnetic MCCB:- 01 nos,6) 100A ,FP Spreader Tereminal:- 02 set, 7) 80A,FP-25kA Thermal Magnetic MCCB:- 01 nos, 8) 80A,FP Spreader Terminal:- 02 set {Make:- C & S/ L & T/Mediatech/Snheider/Rishabh} (all the MCCB should be adjustable type) |
| 16 | Supplying, installation, testing & commissioning of powder coated prewired panel board suitable for 415 volts TP MCCB as incomer & outgoing including busbar & connection as required of the following ratings & sizes:- |
| 17 | 4 way TP MCCB outgoing & TP MCCB incomer upto 400 amps:- |
| 18 | Supplying, installation, testing & commissioning of powder coated prewired digital meter module complete with ammeter, voltmeter, phase indicator lamp, control fuses, CTs, in the existing panel board including connection etc. as required:- |
| 19 | Supplying, installation, testing & commissioning of powder coated side cable module (1 pair) in the existing panel board including connection etc. as required suitable for the following sizes and ratings:- |
| 20 | 4/6 way outgoing and incomer upto 400 amps :- |
| 21 | Supplying and installation of powder coated steel sheet enclosure for 415 volts MCCB (TP/FP) complete with necessary connection etc as required:- |
| 22 | Enclosure suitable for MCCB upto 100 amps:- |
| 23 | Supplying & installation of TP/FP MCCB of following ratings in the existing MCCB enclosure/ panel board including connection etc as required (Ics=100% of Icu with adjustable settings):- |
| 24 | 16 to 100 amps TP MCCB, Breaking capacity 16/18KA (Thermal Magnetic):- |
| 25 | 250 amps TP MCCB, Breaking capacity 36KA (Thermal Magnetic) :- |
| 26 | 16 to 100 amps FP MCCB, Breaking capacity 16/18KA (Thermal Magnetic):- |
| 27 | Supplying and fixing of the following PVC conduit (medium gauge) with all accessories on slab/recessed on wall etc as required. |
| 28 | 32 mm dia |
| 29 | providing & fixing of GI pipes of Heavy class as per IS:1239 with latest amendment complete with G.I fittings i/c trenching and refilling ,cutting and making good the walls etc. complete as per CPWD specification & direction of the Engineer-in-charge |
| 30 | 50 mm dia nominal bore |
| 31 | 80 mm dia nominal bore |
| 32 | Wiring for Circuit/Sub-main with the following sizes of PVC insulated Copper conductor cable (FR) in existing PVC casing capping/ conduit in recess/surface including connection etc. as required:- |
| 33 | 4 X 16 sq mm |
| 34 | 4 X 35 sq mm |
| 35 | 4 X 70 sq mm |
| 36 | Supplying and laying of the following sizes XLPE insulated PVC sheathed aluminium conductor armoured cable with necessary connection etc as required |
| 37 | 3.5 core 70 Sq mm |
| 38 | 3.5 core 120 Sq mm |
| 39 | 3.5 core 300 Sq mm |
| 40 | Supplying and fixing of aluminium terminal ends (LUGS) - long barrel of following sizes : - |
| 41 | 70 sq mm |
| 42 | 120 Sq mm |
| 43 | 300 Sq mm |
| 44 | Supplying and fixing of aluminium terminal ends (LUGS) - long barrel of following sizes : - |
| 45 | 3.5 core or 4 core 240/300 sqmm size:- |
| 46 | 3.5 core or 4 core 70/95/120/150 sqmm size:- |
| 47 | Drawing of armoured/un-armoured cable with proper saddling etc as required:- |
| 48 | Excavation of earth for cable trench of 800mm depth & 300mm width in all kinds of soil including back filling of cable trench with the excavated soil with 20cm layer of sand, 3.5 nos bricks per metre for protection including ramming, consolidating to the original shape as per direction of Site Engineer :- |
| 49 | Making road crossing by horizontal boring for smooth laying of UPVC / CI / DI / GI pipes etc. of required dia complete as per specification and the direction of the Engineer-in-charge. |
| 50 | by manual means |
| 51 | Relocation of Existing 125 KVA DG set including necessary dismantling,transportation,reinstallation by mechanical carriage along with testing , commissioning of the same by authorised service provider of the OEM including necessary connection etc as required at the new working site as per the direction of site-Engineer. Please Enable Macros to View BoQ information |