| 1 | Excavating in trenches, not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, cable, pipes etc. not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in Soft/ Loose soil complete all as specified and as directed by Engineer-in- charge. |
| 2 | Excavating in trenches, not exceeding 1.5 mtr wide and exceeding 1.5 mtr and not exceeding 3.00mtr in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, cable, pipes etc. not exceeding 10 sqm on plan and exceeding 1.5 mtr and not exceeding 3.00mtr in depth and getting out in Soft/ Loose soil complete all as specified and as directed by Engineer-in- charge. |
| 3 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25cm thick, in any type of soil complete all as spefied and as directed by Engineer-in-Charge. |
| 4 | Removing excavated material/soils to a distance not exceeding 50 mtr and depositing where directed at a level not exc.1.5 mtr above the starting point, complete all as spefied and as directed by Engineer-in-Charge. |
| 5 | Material and Labour sand cushioning, with dry and clean fine river sand for underground cable 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cable complete all as spefied and as directed by Engineer-in-Charge. (Note:- Punned thickness shall be considered for payment purpose) |
| 6 | Supply and laying Best quality, locally available, sub class ‘B’ burnt clay bricks (Old Size) for cable protection cover, laid flat and dry in trenches over the cable , perpendicular to the direction of cable complete all as specified and as directed by Engineer-in-Charge. |
| 7 | Taking out old unservicable steel tubular pole with and including embeded portion of PCC foundation with and including Material and Labour Steel tubular poles type 410 SP-31 (9.00mtr long) complete with cast iron base plate, finial, taper plug, bolts nuts & screws complete all as specified including internal surface of steel tubular pole through out and external surface up to planting depth shall be painted with bituminous paint and remaining external surface shall be treated with two coats of aluminium paint over a coat of red oxide zinc chromate primer complete and painting upto 1.5 mtr with alternate layer of yellow & black including marking Sr No of the poles , with and including excavation and earth work such as excavtion, returing filling ,removal and form work compete all as specified and as directed by Engineer-in-charge. Notes:- 1. The rate of Necessary earthwork , such as excavtion, returing filling ,removal and form work is included in this item . Nothing shall be paid extra on this account.2. Cement concrete work shall be measured and paid seperately in respective items of Schedule 'A' BoQ. |
| 8 | Material & Labour for PCC 1:4:8 , Type - D2, using 40mm graded stone aggregates as in foundations, filling and mass concrete complete all as specified and directed by Engineer-in-Charge. |
| 9 | Material & Labour for PCC 1:3:6 , Type C2 , using 40mm graded stone aggregates using 40mm graded stone aggregates as in foundations, filling and mass concrete complete all as specified and directed by Engineer-in-Charge. |
| 10 | Material & Labour for PCC 1:2:4 type B1 using 20 mm graded stone aggregates as in lintel upto 1.5m clear span, cills, steps; seismic and other similar bends, plinth courses, string courses, lacing courses, parapets and railing upto 60 cm in height, copings, kneelers, apex stones, bed plates, water troughs and thelikeincluding weathering, slightly rounded or chamfered angles and throating complete all as specified and as directed by Engineer-in-Charge. |
| 11 | Material & Labour Pin type insulator porcelain /polymer, vitreous, white / brown or green insulators with and including one galvanised MS spindle, two galvanized iron washer, GI nut of size 100 mm height and 65mm dia 1100 volts grade with and including dismantling of old existing unservicable insulators complete all as specified and directed by Engr-in- Charge. |
| 12 | Material & Labour Shackle type insulators, porcelain, vetreous white/ brown or green including galvanised MS strips, bolt,nuts and washer of size 75mm height and 90mm dia,size of strap section 31mm x 3mm and dia of 12 mm for working pressure 1100 volts grade with and including dismantling of old existing unservicable insulators complete all as specified and directed by Engr-in- Charge. |
| 13 | Material & Labour for Cross arms, bracings, supports, clamps and back plate fabricated from structural steel section including nuts, bolts, washers, welding bending cold or hot, drilling holes for bolts in any shapes size as directed and inclusive of one coat of zinc chromate primer , with and including one under coat and one finished coat of aluminium paint complete including dismantling of existing unservicable cross arms of MS channel complete all as specified and directed by Engr-in- Charge. Notes: 1. The measurment and payment shall be made on the actual weight of mild steel material. The weight of premier and paint shall not be considered while weighing of mild steel material.But the rate of one coat of zinc chromate primer , with and including one under coat and one finished coat of aluminium paint is included in this item and nothing shall be paid extra on this account. |
| 14 | Material & Labour Aluminium conductors, steel reinforced (ACSR) conductor of any size for OH lines including stretching, with and including 2mm dia new aluminium binding wire ,jumpers,line taps etc. with and including taking down old unservicable ACSR conductor complete all as specified and directed by Engr-in- Charge. Notes: 1.The measurment and payment shall be made as per the actual weight of ACSR conductor. The weight of 2mm aluminium binding wire shall not be considered while considering the weight of aluminium conductors, steel reinforced (ACSR).But the rate for providing 2mm aluminium binding wire is included in this item and nothing shall be paid extra on this account. |
| 15 | Restretching only the ACSR conductor fixed on over head line / poles and tightening the ACSR conductor complete with authorised sag and binding with insulators in proper position after tighting with and including new aluminium binding wire of dia 2mm all as specified and directed by Engineer-in -Charge.Notes: 1. The rate of 2mm aluminium binding wire shall is included in this item and nothing shall be paid extra on this account. 2. Insulators if required for replacing , shall be measured and paid seperately under relavant items of Schedule'A' BoQ. |
| 16 | Taking down old unserviceable ACSR conductor of assorted sizes from existing overhead lines, including disconnection and removal from poles, complete all as specified and as directed by the Engineer-in-Charge.Notes:(a) The dismantled material shall become the property of the contractor and shall be removed from site accordingly. No credit shall be passed, and no payment shall be admissible towards the value of dismantled material or for any labour involved in its handling, stacking or transportation.(b) Underground cable and allied works shall be measured and paid for separately under relevant items.” |
| 17 | Material and Labour for Stay assembly complete with 20mm dia 1800 mm long stay rod with threaded ends and GI Nuts two number thimbles MS clamps made out of 40mmx6mm flat iron including nuts ,bolts and washer 300 mm x 300 mm x 6mm stay, plate, stay bow, including painting of exposed MS work with two coats of aluminium paint over a coat of red oxide primer with and including (Loop type insulators, stay wire clamp complete all as shown in electrical plate No. 1 with and including earth work such as excavation, returning fillng and removal complete all as specified and as directed by Engineer-in-charge. Note : The rate of earth work such as excavation, returning filling and removal is included in this item and nothng shall be paid extra on lthis account. PCC work shall be measured and paid separetly under appropriate items of Schedule'A' BoQ. |
| 18 | Material & Labour in replacement MCCB 4 pole, 63 Amps , 415 volts adjustable type, with breaking capacity 16 KA complete all as specified and directed by Engineer-in-Charge. |
| 19 | Material & Labour in replacement MCCB 4 pole, 100 Amps , 415 volts adjustable type, with breaking capacity 25 KA complete all as specified and directed by Engineer-in-Charge. |
| 20 | Material & Labour in replacement MCCB 4 pole, 160 Amps , 415 volts adjustable type, with breaking capacity 35/36 KA complete all as specified and directed by Engineer-in-Charge. |
| 21 | Material & Labour in replacement MCCB 4 pole, 200 Amps , 415 volts adjustable type, with breaking capacity 35/36 KA complete all as specified and directed by Engineer-in-Charge. |
| 22 | Material & Labour in replacement MCCB 4 pole, 250 Amps , 415 volts adjustable type, with breaking capacity 35/36 KA complete all as specified and directed by Engineer-in-Charge. |
| 23 | Material & Labour in replacement MCCB 4 pole, 400 Amps , 415 volts adjustable type, with breaking capacity 36 KA complete all as specified and directed by Engineer-in-Charge. |
| 24 | Supply & Fixing in replacement off load Changeover switch , 415 volts , 50Hz ,TPN , 4 Pole , 63 Amps capacity, enclosed in sheet metal enclosure , floor/ wall mounter complete with handle mechanism, interlocking arrangements, connections , and all accesories compete all as per manufacturer's instructions , compete all as specified and directed by Engineer-in-Charge. |
| 25 | Supply & Fixing in replacement off load Changeover switch , 415 volts , 50Hz ,TPN , 4 Pole , 100 Amps capacity, enclosed in sheet metal enclosure , floor/ wall mounter complete with handle mechanism, interlocking arrangements, connections , and all accesories compete all as per manufacturer's instructions , compete all as specified and directed by Engineer-in-Charge. |
| 26 | Supply & Fixing in replacement off load Changeover switch , 415 volts , 50Hz ,TPN , 4 Pole , 200 Amps capacity, enclosed in sheet metal enclosure , floor/ wall mounter complete with handle mechanism, interlocking arrangements, connections , and all accesories compete all as per manufacturer's instructions , compete all as specified and directed by Engineer-in-Charge. |
| 27 | Supply & Fixing in replacement off load Changeover switch , 415 volts , 50Hz ,TPN , 4 Pole , 320 Amps capacity, enclosed in sheet metal enclosure , floor/ wall mounter complete with handle mechanism, interlocking arrangements, connections , and all accesories compete all as per manufacturer's instructions , compete all as specified and directed by Engineer-in-Charge. |
| 28 | Supply & Fixing in replacement off load Changeover switch , 415 volts , 50Hz ,TPN , 4 Pole , 400 Amps capacity, enclosed in sheet metal enclosure , floor/ wall mounter complete with handle mechanism, interlocking arrangements, connections , and all accesories compete all as per manufacturer's instructions , compete all as specified and directed by Engineer-in-Charge. |
| 29 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 16 Sqmm 4 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 30 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 25 Sqmm 4 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 31 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 35 Sqmm 3.50 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 32 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 50 Sqmm 3.50 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 33 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 70 Sqmm 3.50 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 34 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 95 Sqmm 3.50 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 35 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 120 Sqmm 3.50 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 36 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 150 Sqmm 3.50 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 37 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 185 Sqmm 3.50 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 38 | Supply and Fabrication, installation , testing and commissioning factory made , CPRI Approved , , double door , floor mounted LT panel board of size 1.5 Mtr x 1.2 Mtr x 0.50Mtr suitable for 415 volts, 3 phase, 4 wire, 50HZ, AC supply system having bus bar chamber with insulated aluminiumr bus bars of rating 600 Apms and 400 A for neutral, mounted on suitable fibre insulators.The panel shall be dust and vermin proof IP-54 class protection and made of 3.15 mm thick MS sheet on 40x40x6mm thick MS angle iron frame work, and having seprate chamer for each MCCBs powder coated finish front & back opening, including internal wiring with PVC insulated solid copper conductor cable 1100 volts grade of appropriate size (but not less than 4.0sq mm),PCC work and mounting MS Stand 40x40 x 6 mm angle iron of size having 50 cm height and comprising of the following :- Incomming :- (a) MCCB , 4 pole, 415 volts grade, 400 Amps rating and 50 KA rupturning capacity adjustable thermal setting :01 No. Outgoing :- (b) MCCB 4 pole, 415 volts grade,250 Amps rating and 35KA rupturning capacity, adjustable thermal setting :02 Nos. (c) MCCB, 4 pole, 415 volts grade,160 Amps rating and 25 KA rupturning capacity, adjustable thermal setting :01 No. (d) MCCB 4 pole, 415 volts grade,125 Amps rating and 25 KA rupturning capacity, adjustable thermal setting :02 Nos. (e) MCB SPN 63 Amps 240 Volt and 10 KA rupturning capacity \\"C \\" Curve -06 Nos. (f) Voltmeter electronic, digital type, with selector switch 0 - 500 volts, AC, 50 Hz - 1 No. (g) Ammeter electronic, digital type, 0 - 400 amps, AC, 50 Hz - 1 No. (h) Current transformer 200 / 5 amps rating, AC, 50 Hz - 3 Nos. (j) Phase indication LED lamps - 3 Nos. Note: Make and complete detailed drawings of the LT Panel shall be submitted to and approved by the GE prior to procurement / manufacture . The panel shall be executed strictly as per approved drawings and specifications complete all as specified and as directed by Engineer-in-charge. |
| 39 | Supply and Fabrication, installation , testing and commissioning factory made , CPRI Approved , outdoor type , double door , floor mounted LT pannel board of 1.2 Mtr x 1.0 Mtr x 0.40Mtr suitable for 415 volts, 3 phase, 4 wire, 50HZ, AC supply system having bus bar chamber with insulated aluminiumr bus bars of rating 600 Apms and 400 A for neutral, mounted on suitable fibre insulators.The panel shall be dust and vermin proof IP-54 class protection and made of 3.15 mm thick MS sheet on 40mm x 40mm x 6mm thick MS angle iron frame work, and having seprate chamer for each MCCBs powder coated finish front & back opening, including internal wiring with PVC insulated solid copper conductor cable 1100 volts grade of appropriate size (but not less than 4.0sq mm),PCC work and mounting on MS Stand 40mm x 40mm x 6 mm angle iron of size having 50 cm height and comprising of the following :- Incoming (a) MCCB 4 pole, 415 volts grade, 400 Amps rating and 50 KA rupturning capacity adjustable thermal setting :02 Nos. Outt going (a) On Load Change over Switch 4 pole 415 Volts 400A - 01 No. (b) MCCB 4 pole, 415 volts grade,125 Amps rating and 25 KA rupturning capacity, adjustable thermal setting :01 No. (c) MCB SPN 63 Amps 240 Volt and 10 KA rupturning capacity \\"C \\" Curve -04 Nos (f) Voltmeter electronic, digital type, with selector switch 0 - 500 volts, AC, 50 Hz - 1 No. (g) Ammeter electronic, digital type, 0 - 400 amps, AC, 50 Hz - 1 No. (h) Current transformer 200 / 5 amps rating, AC, 50 Hz - 3 Nos. (j) Phase indication LED lamps - 3 Nos. (k) Fitting Charges for internal electric wiring and accessories including testing and commissioning Note: Make and complete detailed drawings of the LT Panel shall be submitted to and approved by the GE prior to procurement / manufacture . The panel shall be executed strictly as per approved drawings and specifications complete all as specified and as directed by Engineer-in-charge. |
| 40 | Taking out from trenches / poles / wall etc LT UG Cable PVC insulated sheathed with multistranded aluminium conductor armoured and relaying after fault rectification duly tested in trenches / Poles / Wall of LT Under Ground Cable of any sizes icomplete all as specified and directed by Engr-in-Charge. Notes: 1.Earth work such as excavation, returning filling and removal shall be measured and paid seperately as material and labour under appropriate items of Schedule 'A' BoQ.2. if cable required extra for rectification fault shall be measured and paid seperately under appropriate items of Schedule'A' BoQ. |
| 41 | Material & Labour for cable end heat shrink type jointing kit 1100 Volts for indoor/outdoor termination with jointing material and accessories suitable for 16 Sqmm to 70 Sqmm 3.5/4 core XLPE/PVC armoured aluminium conductor cable complete all as specified and directed by Engineer in Charge |
| 42 | Material & Labour cable end heat shrink type jointing kit 1100 Volts for indoor/outdoor termination with jointing material and accessories suitable for 95 Sqmm to 120 Sqmm 3.5 core XLPE/PVC armoured aluminium conductor cable complete all as specified and directed by Engineer in Charge |
| 43 | Material and labour for preparation and painting of steel tubular electrical poles, including cross arms, channels, clamps, etc., by scraping and cleaning of old, loose, patchy and cracked paint, and applying one coat of aluminium paint over the entire surface. Painting shall also include providing a block strip of 30 cm to 1.50 m height from ground level with alternate bands of black and white synthetic enamel paint, with and including writing pole number with black synthetic enamel paint complete all as specified and as directed by the Engineer-in-Charge.Note: Necessary shutdown of the feeder shall be arranged/obtained by the contractor before commencement of the work, and painting shall be carried out with due safety precautions. |
| 44 | Material and labour for preparation and painting of PCC poles, including brackets, fittings, etc., by scrubbing and cleaning of old, deteriorated paint and preparing the surfaces, and applying two coats of cement-based paint over the entire surface. Painting shall also include providing a colour strip up to 1.50 m height from ground level with two coats of synthetic enamel paint with black and white strip, and writing pole numbers with black synthtic enamel paint, complete all as specified and as directed by the Engineer-in-Charge. |
| 45 | Cutting and Trimming of trees branches from electric over head lines and clearing of 2 meter distance horizontal and vertical from outer edge of conductor including removing cut branches 50 Mtr (minimum) away from the place all as directed by Engr-in- Charge. Notes: 1. Contractor will ensure shut down on the feeder in writing before commencement of work on electrical lines2 Length of Each span shall be considered for measurment 40.00mtr. if the length of span less than 40.00mtr payment shall be made on the proportional rates as quoted by contractor for 40.00 mtr each span. |
| 46 | Supply and Laying GI tubing 80mm bore Light grade with all fittings such as clamps laid in trenchs or fixed on wall along pole including fixing arrangement , nut bolts, clamps etc.complete for protection of electic cable / strip complete all as specified and as directed by Engineer - in charge. Note : Excavation and earth work shall be measured and paid seperately under appropriate items of Schedule'A'BoQ. |
| 47 | Supply and Laying GI tubing 50mm bore Light grade with all fittings such as clamps laid in trenchs or fixed on wall along pole including fixing arrangement , nut bolts, clamps etc.complete for protection of electic cable / strip complete all as specified and as directed by Engineer - in charge. Note : Excavation and earth work shall be measured and paid seperately under appropriate items of Schedule'A'BoQ. |
| 48 | Supply and Laying GI tubing 40mm bore Light grade with all fittings such as clamps laid in trenchs or fixed on wall along pole including fixing arrangement , nut bolts, clamps etc.complete for protection of electic cable / strip complete all as specified and as directed by Engineer - in charge. Note : Excavation and earth work shall be measured and paid seperately under appropriate items of Schedule'A'BoQ. |
| 49 | Material and Labour for Boring of holes under road, pavement, hard standing by using ultra sounding technique suitable for 0.4 mpa working pressure trenchless technology , for size of bore 40mm to 80mm complete all as specified and directed by Engr-in-Charge. Note: Galvanised Iron light grade pipe of respective dias shall be measured and paid separetly under appropriate items of Schedule'A' BoQ. |
| 50 | Supply and Fixing in replacement of voltmeter 0-500 volts digital type complete all as specified and as directed by Engr-in-charge. |
| 51 | Supply and Fixing in replacement of Ammeter 0-400Amps digital type complete all as specified and as directed by Engr-in-charge. |
| 52 | Supply & Fixing in replacement CTs for ampermeter complete all as specified and as directed by Engr-in-charge. . |
| 53 | Material and labour for Factory made Bus Bar Chamber of size 60cm x 60cm x 45 cm suitable of 3 phase 433 Volts, outdoor type, made out of 3.15 mm thick M S Sheet with 200 Amps rated aluminium busbar (4 Nos ) PVC sleeves and coloured (Red,Yellow,Blue and Black) with locking arrangments and angle iron stand of size 40mm x 40mm x 6mm frame grouted in ground with PCC foundatiuon 1:2:4 type B1 with 20mm graded stone aggregate alongwith all necesary cable connections,lugs and cable gland with and including two coats of synthetic enamel paint over with and including one coat of red oxide zinc chrome primer complete all as specified and as directed by Engineer - in - charge. |
| 54 | Disconnecting, dismantling & taking out old existing unserviceable burnt inter connection wire from the control panel of any description & in any postion and supply, fixing, testing new PVC insulated multistranded FRLSH copper wire 16 Sqmm single core suitable upto 1100 Volts with all fixing materials required at site complete all as specified and as directed by Engineer-in-charge. |
| 55 | Disconnecting, dismantling & taking out old existing unserviceable/burnt inter connection wire from the control panel of any description & in any postion and supply, fixing, testing new PVC insulated multistranded FRLSH copper wire 25 Sqmm single core suitable upto 1100 Volts with all fixing materials required at site complete all as specified and as directed by Engineer-in-charge. |
| 56 | Supply and laying, fixing or passing through pipe, in replacement, PVC insulated, aluminium conductor, armoured cable of 1100 volts grade, with inner PVC sheathing, galvanised steel wire/tape armouring and overall PVC sheathing, nominal cross-sectional area 16 sq.mm x 2 core , for service connections, complete all as specified and as directed by the Engineer-in-Charge. |
| 57 | Supply and laying, fixing or passing through pipe, in replacement, PVC insulated, aluminium conductor, armoured cable of 1100 volts grade, with inner PVC sheathing, galvanised steel wire/tape armouring and overall PVC sheathing, nominal cross-sectional area 10 sq.mm x 2 core , for service connections, complete all as specified and as directed by the Engineer-in-Charge. |
| 58 | Supply only aluminium thimbles 1100 volts suitable for 70 Sqmm to 150 Sqmm cable complete all as specified and as directed by the Engineer-in-Charge. |
| 59 | Supply only aluminium thimbles 1100 volts suitable for 25 Sqmm to 50 Sqmm cable complete all as specified and as directed by the Engineer-in-Charge. |
| 60 | Supply only aluminium thimbles 1100 volts suitable for 6 Sqmm to 16 Sqmm cable complete all as specified and as directed by the Engineer-in-Charge. |
| 61 | Supply only smooth finish highly durable ruggedness copper Copper thimbles 1100 volts suitable for 70 Sqmm to 150 Sqmm cable complete all as specified and directed by Engineer-in-Charge. |
| 62 | Supply only smooth finish highly durable ruggedness copper thimbles 1100 volts suitable for 25 Sqmm to 50 Sqmm cable complete all as specified and directed by Engineer-in-Charge. |
| 63 | Supply only smooth finish highly durable ruggedness copper Copper thimbles 1100 volts suitable for 6 Sqmm to 16 Sqmm cable complete all as specified and as directed by the Engineer-in-Charge. |
| 64 | Material and labour in replacement Earthing complete with galvanised iron earth plate electrode of size 600mm x 600mm x 6mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including earth continuity GI strip 32mm x 6mm (upto test point from earth plate i.e. 7.5m min) by means of GI bolts/nuts/washersand including protected by 15mm dia GI light grade protection pipe from earth plate to test point, including making of test point. Earth plate shall be surrounded by packed layer of char coal/coke & salt all around bottom and top with alternative layer. 20mm GI mediumt grade pipe for watering (should be 10cm above GL) and including socket, plug, funnel, wire mesh, RCC cover and (including steel for cover) PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) including necessary form work, excavation and earth work in any type of soil , returning filling and disposal of surplus soil to a distance not exceeding 50m, complete all as specified & shown in electrical plate No. 3 of SSR 2009 (Part-I) complete all as specified and and as directed by Engineer-in-charge. Note:- (i) Earth continuity of GI wire 4 mm including protection pipe up to 7.5 mtrs from earth electrode will be included in unit rate, complete all as specified and directed. (ii) The rate of earth work in soft/loose soil i.e. excavation, returing filling and removal, form work is included in this item and nothing shall be paid extra on this account. (iii) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (iv) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge. |
| 65 | Taking down old unserviceable service cable/underground (UG) cable of any size, including removal of unserviceable bricks/PCC cable covers, complete all as specified and as directed by the Engineer-in-Charge.Notes:(a) Excavation and earthwork shall be measured and paid for separately under relevant items.(b) Where new/old cable is laid along the same alignment/location, excavation and earthwork shall be measured and paid only once. No duplicate measurement shall be admissible in this regard. |
| 66 | Note:- The contract sum shall be calculated by deducting the amount shown in Credit Schedule attached to this tender from total amount of Schedule 'A'/BOQ Please Enable Macros to View BoQ information |