| 1 | Dismantling of U/s DG set 500 KVA capacity and disconnecting all coomections, LT panel board and cables and loading and transporting the the DG set and handing over to the MES storeyard and as directed by the Engineer-in-charge. |
| 2 | Supply, installation, testing and commissioning of silent Diesel Engine Generating set of 500 KVA capacity all as per CPCB-IV + norms, 415 Volts 3 Phase, 0.8 Power Factor, 50 Hz, 1500 RPM, self excited, self regulated, brushless AC generator with AMF panel of suitable rating including accoustic enclosure suitable for ambient condition at sea area and conforming to Engine as per IS : 10002, ISO-3046, BS-5514 and Alternator as per IS: 4774, BS EN 60034-1 with all necessary accessories for proper functioning of DG set including PCC Foundation, GI Pipe for laying of cable etc all as per manufacturers instructions complete all as specified in Particular specifications and as directed by Engineer-in-charge. |
| 3 | Note :1. The capacity of Generator set shall be net after all due de-rating factors as per relevant IS desing and site conditions.2. Rate quoted shall be deemed to be inclusive of cable and terminations fro DG et to AMF panel, with necessary fixing arrangments all as specified and directed.3. The rate quoted shall be deemed to include for first fill of oil and final successful acceptance test. |
| 4 | Supply, laying & testing, replacement LT UG XLPE cable, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) earth system with stranded aluminium conductor, 1100 volts grade of size 3.5 core 630 sqmm and conforming to IS all as specified and directed. |
| 5 | Supply, laying & testing, replacement LT UG XLPE cable, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) earth system with stranded aluminium conductor, 1100 volts grade of size 3.5 core 400 sqmm and conforming to IS all as specified and directed. |
| 6 | Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for laying pipe lines, cables etc and nexc 1.5 m in depth and getting out hard / dense soil complete including taking out cables, cable cover all as specified and directed. |
| 7 | Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for laying pipe lines, cables etc and nexc 1.5 m in depth and getting out soft / loose soil complete including taking out cables, cable cover all as specified and directed. |
| 8 | Returning, filling-in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm using excavated soil all as specified and directed. |
| 9 | Removing excavated materials to a distance not exceedcing 50 meters and depositing where directed at a level not exceeding 1.5 m above the starting point all as specified and directed. |
| 10 | M&L for Unreinforced Precast Cement Concrete Cable Covers, Class LV Type - 1, Flat, size 250mm X 150mm X 40mm in trenches for cable protection, embossed with \\"ELECTRIC\\" on the top surface complete all as specified and directed. |
| 11 | Supply and spread clean dry river sand as cable cushioning for protection of underground cable to be laid in trenches / transformer yard / two pole structure etc complete all as specified and directed. (Note: Punned down thickness will only measured for the purpose of payment.) |
| 12 | M&L for 110 mm dia DWC medium grade pipe for cable protection and sealing both ends incluidn gtaking down old pipe |
| 13 | Supply, fabricate, install, test and commissioning LT outdoor control panel, weather proof , dust /vermin proof, IP 55 made out of 3.15mm thick CRCA sheet both sides openable door with angle iron frame and locking arrangement,including bus bar suitable for 3 phase 4 wire AC supply of drwing 415 V, 50 Hz AC, , the panel comprising 1400 Amp aluminium bus bar including PC sleeves / taps RYB colurs for phase identification, conforming to IP 54 and fixed on raised PCC platform as per OEM requirments and drawings with PCC 1:2:4, type B1 ( using 20 mm graded stone aggregate) raised base with control wiring , cable gland brass lugs etc complete including taking down old panel, all as specified and as dircted. The panel shall be certified by CPRI and include the following in the panel.(a) ACB (Manual drawout type) 4 Pole, 800 Amps, 50 KA-01 No ( Incoming)(b) ACB ( Manual drawout type) 4 Pole, 630 Amps, 50 KA-02 Nos ( for outgoing for hangers) (c) MCCB 4 pole 32 Amps, 16 KA -01 Nos ( Spare)(d) LED type phase indicator with controlling fuses for RYB - 03 sets (incoming and outgoing)(e) 3 phase multifunction energy meter ( Voltage 0-500 V, Ampere 1-125 amps , energy consumption in KWH or units consumption including CTs and PTs.(f) Electrolyte type copper busbars, PVC colour sleeved 800 Amps capacity TP(g) Danger notice plate of approved size for LT 20 x 15 cm - 01 no. |
| 14 | M&L in repairs Earthing complete with Galvanised Steel Earth Plate Electrode 600 X 600 X 6 mm thick burried directly in ground [earth pit not less than 2.25 m deep below ground level] with top edge of Plate not less than 1.50 m below normal ground level connected to 32x6mm thick GI strip [Earth Lead] and GI pipe 50 mm, Medium Grade for earthing lead protection to the extent of maximum 7.5m, Earth Plate Electrode surrounded by 150mm thick packed layers of Charcoal and Common Salt filled in alternate layers, connected to the Plate by means of GI Bolts & Nuts complete all as per Electrical Plate No. 3 of SSR Part – I, connected to panel / DB including testing on completion including main earthing, Charcoal, Common Salt, PCC [1:2:4, Type B1] Pit with RCC 1:2:4, Type B1 Cover, 50 mm thick with 6 Nos, 8 mm dia TMT bars in both ways, MS frame made with 40 X 40 X 6 mm Angle Iron, MS Funnel with 20 mm bore, medium grade GI Watering pipe, wire mesh, earth work excavation, return filling, removal of surplus soil etc. including taking down old earthing complete allas specified and as directed. |
| 15 | Supply and replace GI strip of size 32x 6 mm complete with porcelain insulator saddles at 1.5 m spacing fixed with screws for fixing on wall , floor or roof all as specified and as dircted. |