| 1 | Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, cable, pipes etc. not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in Soft/ Loose soil complete all as specified and as directed by Engineer-in- charge. |
| 2 | Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, cable, pipes etc. not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in hard/dense soil complete all as specified and as directed by Engineer-in- charge. |
| 3 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25cm thick, in any type of soil complete all as spefied and as directed by Engineer-in-Charge. |
| 4 | Removing excavated material/soils to a distance not exceeding 50 mtr and depositing where directed at a level not exc.1.5 mtr above the starting point, complete all as spefied and as directed by Engineer-in-Charge. |
| 5 | Material and Labour sand cushioning, with dry and clean fine river sand for underground cable 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cable complete all as spefied and as directed by Engineer-in-Charge. (Note:- Punned thickness shall be considered for payment purpose) |
| 6 | Supply and laying Best quality, locally available, sub class ‘B’ burnt clay bricks (Old Size) for cable protection cover, laid flat and dry in trenches over the cable , perpendicular to the direction of cable complete all as specified and as directed by Engineer-in-Charge. |
| 7 | Material & Labour for PCC 1:4:8 , Type - D2, using 40mm graded stone aggregates as in foundations, filling and mass concrete complete all as specified and directed by Engineer-in-Charge. |
| 8 | Material & Labour for PCC 1:3:6 , Type C2 , using 40mm graded stone aggregates using 40mm graded stone aggregates as in foundations, filling and mass concrete complete all as specified and directed by Engineer-in-Charge. |
| 9 | Material & Labour for PCC 1:2:4 type B1 using 20 mm graded stone aggregates as in lintel upto 1.5m clear span, cills, steps; seismic and other similar bends, plinth courses, string courses, lacing courses, parapets and railing upto 60 cm in height, copings, kneelers, apex stones, bed plates, water troughs and thelikeincluding weathering, slightly rounded or chamfered angles and throating complete all as specified and as directed by Engineer-in-Charge. |
| 10 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 35 Sqmm 3.50 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 11 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 50 Sqmm 3.50 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 12 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 25 Sqmm 3.50 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 13 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 70 Sqmm 3.50 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 14 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 95 Sqmm 3.50 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 15 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 150 Sqmm 3.50 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 16 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 16 Sqmm 4 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 17 | Supply and laying or fixing or laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing LT cable XLPE, PVC insulated screened, bedded, galvanised steel strip or wire armourd cable (heavy duty) 1100 volt grade with aluminium conductor having cross sectional area 10 Sqmm 2 core conforming to IS-7098 (Part-I -1988) complete all as specified and as directed by Engineer-in-Charge. (Excavation and earth work, sand cushioning & GI pipe shall be measured and paid for separately) |
| 18 | Material & Labour Aluminium conductors, steel reinforced (ACSR) conductor of any size for OH lines including stretching, with and including 2mm dia new aluminium binding wire ,jumpers,line taps etc. with and including taking down old unservicable ACSR conductor complete all as specified and directed by Engr-in- Charge. Notes: 1. The weight of 2mm aluminium binding wire shall not be considered while considering the weight of aluminium conductors, steel reinforced (ACSR).But the rate for providing 2mm aluminium binding wire is included in this item and nothing shall be paid extra on this account. |
| 19 | Material & Labour Pin type insulator porcelain /polymer, vitreous, white / brown or green insulators with and including one galvanised MS spindle, two galvanized iron washer, GI nut of size 100 mm height and 65mm dia 1100 volts grade with and including dismantling of old existing unservicable insulators complete all as specified and directed by Engr-in- Charge. |
| 20 | Material & Labour Shackle type insulators, porcelain, vetreous white/ brown or green including galvanised MS strips, bolt,nuts and washer of size 75mm height and 90mm dia,size of strap section 31mm x 3mm and dia of 12 mm for working pressure 1100 volts grade with and including dismantling of old existing unservicable insulators complete all as specified and directed by Engr-in- Charge. |
| 21 | Supply & Fixing Rolling type insulators, porcelain, vetreous white/ brown including galvanised MS strips, bolt,nuts and washer and dia of 12 mm for working pressure 1100 volts grade with and including dismantling of old existing unservicable insulators complete all as specified and directed by Engr-in- Charge. |
| 22 | Material & Labour for Cross arms, bracings, supports, clamps and back plate fabricated from structural steel section including nuts, bolts, washers, welding bending cold or hot, drilling holes for bolts in any shapes size as directed and inclusive of one coat of zinc chromate primer , with and including one under coat and one finished coat of aluminium paint complete including dismantling of existing unservicable cross arms of MS channel complete all as specified and directed by Engr-in- Charge. Notes: 1. The measurment and payment shall be made on the actual weight of mild steel material. The weight of premier and paint shall not be considered while weighing of mild steel material.But the rate of one coat of zinc chromate primer , with and including one under coat and one finished coat of aluminium paint is included in this item and nothing shall be paid extra on this account. |
| 23 | Taking out old unservicable steel tubular pole with and including embeded portion of PCC foundation with and including Material and Labour Steel tubular poles type 410 SP-31 (9.00mtr long) complete with cast iron base plate, finial, taper plug, bolts nuts & screws complete all as specified including internal surface of steel tubular pole through out and external surface up to planting depth shall be painted with bituminous paint and remaining external surface shall be treated with two coats of aluminium paint over a coat of red oxide zinc chromate primer complete and painting upto 1.5 mtr with alternate layer of yellow & black including marking Sr No of the poles , with and including excavation and earth work such as excavtion, returing filling ,removal and form work compete all as specified and as directed by Engineer-in-charge. Notes:- 1. The rate of Necessary earthwork , such as excavtion, returing filling ,removal and form work is included in this item . Nothing shall be paid extra on this account.2. Cement concrete work shall be measured and paid seperately in respective items of Schedule 'A' BoQ. |
| 24 | Restretching only the ACSR conductor fixed on over head line / poles and tightening the ACSR conductor complete with authorised sag and binding with insulators in proper position after tighting with and including new aluminium binding wire of dia 2mm all as specified and directed by Engineer-in -Charge.Notes: 1. The rate of 2mm aluminium binding wire shall is included in this item and nothing shall be paid extra on this account. 2. Insulators if required for replacing , shall be measured and paid seperately under relavant items of Schedule'A' BoQ. |
| 25 | Supplying and fixing in replacement flat twin core cable of size 10 sqmm , PVC insulated aluminium conductor, provided with inner sheathing of PVC tape and overall PVC sheathed, 1100 volts grade, heavy duty , suspended from insulating hangers at intervals not exceeding 1.00 metre , with and including 4mm suspension wire, complete all as specified and directed by Engr-in- Charge. |
| 26 | Supplying and fixing in replacement flat twin core cable of size 16 sqmm , PVC insulated aluminium conductor, provided with inner sheathing of PVC tape and overall PVC sheathed, 1100 volts grade, heavy duty , suspended from insulating hangers at intervals not exceeding 1.00 metre , with and including 4mm suspension wire, complete all as specified and directed by Engr-in- Charge. |
| 27 | Material & Labour in replacement Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts ofapproved size, for LT, 20cm x15cm size complete all as specified and directed by Engineer-in-Charge. |
| 28 | Material & Labour in replacement MCCB 4 pole, 160 Amps , 415 volts adjustable type, with breaking capacity 35/36 KA complete all as specified and directed by Engineer-in-Charge. |
| 29 | Material & Labour in replacement MCCB 4 pole, 200 Amps , 415 volts adjustable type, with breaking capacity 35/36 KA complete all as specified and directed by Engineer-in-Charge. |
| 30 | Material & Labour in replacement MCCB 4 pole, 250 Amps , 415 volts adjustable type, with breaking capacity 35/36 KA complete all as specified and directed by Engineer-in-Charge. |
| 31 | Material & Labour in replacement MCCB 4 pole,350 Amps , 415 volts adjustable type, with breaking capacity 35/36 KA complete all as specified and directed by Engineer-in-Charge. |
| 32 | Material & Labour in replacement MCCB 4 pole, 400 Amps , 415 volts adjustable type, with breaking capacity 36 KA complete all as specified and directed by Engineer-in-Charge. |
| 33 | Material & Labour in replacement MCCB 4 pole, 100 Amps , 415 volts adjustable type, with breaking capacity 25 KA complete all as specified and directed by Engineer-in-Charge. |
| 34 | Material & Labour in replacement MCCB 4 pole, 63 Amps , 415 volts adjustable type, with breaking capacity 16 KA complete all as specified and directed by Engineer-in-Charge. |
| 35 | Supply & Fixing in replacement off load Changeover switch , 415 volts , 50Hz ,TPN , 4 Pole , 400 Amps capacity, enclosed in sheet metal enclosure , floor/ wall mounter complete with handle mechanism, interlocking arrangements, connections , and all accesories compete all as per manufacturer's instructions , compete all as specified and directed by Engineer-in-Charge. |
| 36 | Supply & Fixing in replacement off load Changeover switch , 415 volts , 50Hz ,TPN , 4 Pole , 100 Amps capacity, enclosed in sheet metal enclosure , floor/ wall mounter complete with handle mechanism, interlocking arrangements, connections , and all accesories compete all as per manufacturer's instructions , compete all as specified and directed by Engineer-in-Charge. |
| 37 | Supply & Fixing in replacement off load Changeover switch , 415 volts , 50Hz ,TPN , 4 Pole , 200 Amps capacity, enclosed in sheet metal enclosure , floor/ wall mounter complete with handle mechanism, interlocking arrangements, connections , and all accesories compete all as per manufacturer's instructions , compete all as specified and directed by Engineer-in-Charge. |
| 38 | Material and labour for in replacement Earthing complete with galvanised iron earth plate electrode of size 600mm x 600mm x 6mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including earth continuity GI strip 32mm x 6mm (upto test point from earth plate i.e. 7.5m min) by means of GI bolts/nuts/washersand including protected by 15mm dia GI light grade protection pipe from earth plate to test point, including making of test point. Earth plate shall be surrounded by packed layer of char coal/coke & salt all around bottom and top with alternative layer. 20mm GI mediumt grade pipe for watering (should be 10cm above GL) and including socket, plug, funnel, wire mesh, RCC cover and (including steel for cover) PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) including necessary form work, excavation and earth work in any type of soil , returning filling and disposal of surplus soil to a distance not exceeding 50m, complete all as specified & shown in electrical plate No. 3 of SSR 2009 (Part-I) complete all as specified and and as directed by Engineer-in-charge. Note:- (i) Earth continuity of GI strip 32mm x 6mm including protection pipe up to 7.5 mtrs from earth electrode will be included in unit rate, complete all as specified and directed. (ii) The rate of earth work in soft/loose soil i.e. excavation, returing filling and removal, form work is included in this item and nothing shall be paid extra on this account. (iii) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (iv) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge. |
| 39 | Material and Labour in replacement for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required GI strip 32mm x 6mm compete all as specified and as directed by Engineer-in-Charge |
| 40 | Supply and Laying in replacement GI tubing 50mm bore Light grade with all fittings such as clamps laid in trenchs or fixed on wall along pole including fixing arrangement , nut bolts, clamps etc.complete for protection of electic cable / strip complete all as specified and as directed by Engineer - in charge. Note : Excavation and earth work shall be measured and paid seperately under appropriate items of Schedule'A'BoQ. |
| 41 | Supply and Laying in replacement GI tubing 80mm bore Light grade with all fittings such as clamps laid in trenchs or fixed on wall along pole including fixing arrangement , nut bolts, clamps etc.complete for protection of electic cable / strip complete all as specified and as directed by Engineer - in charge. Note : Excavation and earth work shall be measured and paid seperately under appropriate items of Schedule'A'BoQ. |
| 42 | Supply and Fabrication, installation , testing and commissioning in replacement factory made IP-54 , CPRI Approved , Out door type , LT electrical panel board, AC, 3 phase, 4 wire, 415 / 500 V, 50 Hz, outdoor type, fabricated with 3.15 mm thick made of CRCA, powder coated , , Cable gland, bottom with detachable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit, chamber for aluminium bus bars including aluminium bus bars 4 Nos, 800 amps capacity insulated with colored PVC sleeves mounted on suitable insulators and seperators, holes drilled for connections, complete suitable for mounting following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated, complete mounted on PCC pillars complete all as specified and comprising of the followings:-INCOMING :-(a) MCCB 4 Pole, 415 V, adjustable thermal setting ,400 Amps with breaking capacity 36 KA - 01 No. OUTGOING :- (a) MCCB 4 Pole, 415 V, adjustable thermal setting 250 Amps with breaking capacity 25 KA - 02 Nos. (b) MCCB 4 Pole, 415 V, adjustable thermal setting 100 Amps with breaking capacity 16 KA - 02 Nos. (c) MCCB 4 pole 63 Amps, 415V, 16 KA-01 No. (d) Voltmeter, electronic, digital type, with selector switch 0 - 500 volts, AC, 50 Hz - 1 No. (e) Ammeter electronic, digital type, 0 - 800 amps, AC, 50 Hz - 1 No. (f) Current transformer 200 / 5 amps rating, AC, 50 Hz - 3 Nos. (g) Phase indication LED lamps - 3 Nos(RYB). Note: Make and complete detailed drawings of the LT Panel shall be submitted to and approved by the GE prior to procurement / manufacture . The panel shall be executed strictly as per approved drawings and specifications complete all as specified and as directed by Engineer-in-charge. |
| 43 | Supply and Fabrication, installation , testing and commissioning in replacement factory made IP-54 , CPRI Approved , Out door type , LT electrical panel board, AC, 3 phase, 4 wire, 415 / 500 V, 50 Hz, outdoor type, fabricated with 3.15 mm thick made of CRCA, powder coated , Cable gland, bottom with detatchable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit, chamber for aluminium bus bars including aluminium bus bars 4 Nos, 800 amps capacity insulated with colored PVC sleeves mounted on suitable insulators and seperators, holes drilled for connections, complete suitable for mounting following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated, complete mounted on PCC pillars complete all as specified and comprising of the followings:-INCOMING :-(a) MCCB 4 Pole, 415 V, adjustable thermal setting ,400 Amps with breaking capacity 36 KA - 01 No. OUTGOING :- (a) MCCB 4 Pole, 415 V, adjustable thermal setting 250 Amps with breaking capacity 25 KA - 02 Nos. (b) MCCB 4 Pole, 415 V, adjustable thermal setting 200 Amps with breaking capacity 25 KA - 01 No. (c) Voltmeter, electronic, digital type, with selector switch 0 - 500 volts, AC, 50 Hz - 1 No. (d) Ammeter electronic, digital type, 0 - 800 amps, AC, 50 Hz - 1 No. (e) Current transformer 200 / 5 amps rating, AC, 50 Hz - 3 Nos. (g) Phase indication LED lamps - 3 Nos(RYB). Note: Make and complete detailed drawings of the LT Panel shall be submitted to and approved by the GE prior to procurement / manufacture . The panel shall be executed strictly as per approved drawings and specifications complete all as specified and as directed by Engineer-in-charge. |
| 44 | Supply and Fabrication, installation , testing and commissioning in replacement factory made IP-54 , CPRI Approved , out door type LT electrical panel board, AC, 3 phase, 4 wire, 415 / 500 V, 50 Hz, outdoor type, fabricated with 3.15 mm thick made of CRCA, powder coated , Cable gland, bottom with detatchable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit, chamber for aluminium bus bars including aluminium bus bars 4 Nos, 500 amps capacity insulated with colored PVC sleeves mounted on suitable insulators and seperators, holes drilled for connections, complete suitable for mounting following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated, complete mounted on PCC pillars complete all as specified and comprising of the followings:-INCOMING :-(a) MCCB 4 Pole, 415 V, adjustable thermal setting ,250 Amps with breaking capacity 25KA - 01 No. OUTGOING :- (a) MCCB 4 Pole, 415 V, adjustable thermal setting 100 Amps with breaking capacity 25 KA - 02 Nos . (b) MCCB 4 Pole, 415 V, adjustable thermal setting 63 Amps with breaking capacity 16 KA - 02 Nos. (c) Voltmeter, electronic, digital type, with selector switch 0 - 500 volts, AC, 50 Hz - 1 No. (d) Ammeter electronic, digital type, 0 - 400 amps, AC, 50 Hz - 1 No. (e) Current transformer 200 / 5 amps rating, AC, 50 Hz - 3 Nos. (f) Phase indication LED lamps - 3 Nos(RYB). Note: Make and complete detailed drawings of the LT Panel shall be submitted to and approved by the GE prior to procurement / manufacture . The panel shall be executed strictly as per approved drawings and specifications complete all as specified and as directed by Engineer-in-charge. |
| 45 | Supply and Fabrication, installation , testing and commissioning in replacement factory made IP-54 , CPRI Approved , out door type LT electrical panel board, AC, 3 phase, 4 wire, 415 / 500 V, 50 Hz, outdoor type, fabricated with 3.15 mm thick made of CRCA, powder coated , Cable gland, bottom with detatchable plates, front and rear with hinged type door and locking arrangements, chamber for cable entry and exit, chamber for aluminium bus bars including aluminium bus bars 4 Nos, 500 amps capacity insulated with colored PVC sleeves mounted on suitable insulators and seperators, holes drilled for connections, complete suitable for mounting following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated, complete mounted on PCC pillars complete all as specified and comprising of the followings:-INCOMING :-(a) MCCB 4 Pole, 415 V, adjustable thermal setting ,200 Amps with breaking capacity 25KA - 01 No. OUTGOING :- (a) MCCB 4 Pole, 415 V, adjustable thermal setting 100 Amps with breaking capacity 25 KA - 01 No . (b) MCCB 4 Pole, 415 V, adjustable thermal setting 63 Amps with breaking capacity 16 KA - 02 Nos. (c) Voltmeter, electronic, digital type, with selector switch 0 - 500 volts, AC, 50 Hz - 1 No. (d) Ammeter electronic, digital type, 0 - 400 amps, AC, 50 Hz - 1 No. (e) Current transformer 200 / 5 amps rating, AC, 50 Hz - 3 Nos. (f) Phase indication LED lamps - 3 Nos (RYB).Note: Make and complete detailed drawings of the LT Panel shall be submitted to and approved by the GE prior to procurement / manufacture . The panel shall be executed strictly as per approved drawings and specifications complete all as specified and as directed by Engineer-in-charge. |
| 46 | Cutting and Trimming of trees branches from electric over head lines and clearing of 2 meter distance horizontal and vertical from outer edge of conductor including removing cut branches 50 Mtr (minimum) away from the place all as directed by Engr-in- Charge. Notes: 1. Contractor will ensure shut down on the feeder in writing before commencement of work on electrical lines2 Length of Each span shall be considered for measurment 40.00mtr. if the length of span less than 40.00mtr payment shall be made on the proportional rates as quoted by contractor for 40.00 mtr each span. |
| 47 | Surface excavation,grass cutting not exceeding 15cm in depth with and including cleaning the bushes and vegetation / root of small trees, and leveling with around the poles / feeder piller boxes / sub stations with and including removal compete all as specified and as directed by Engineer-in-Charge |
| 48 | Material and Labour for Boring of holes under road, pavement, hard standing by using ultra sounding technique suitable for 0.4 mpa working pressure trenchless technology , for size of bore 50mm to 80mm complete all as specified and directed by Engr-in-Charge. Note: Galvanised Iron light grade pipe of respective dias shall be measured and paid separetly under appropriate items of Schedule'A' BoQ. |
| 49 | Taking down old unserviceable service cable/underground (UG) cable of any size, including removal of unserviceable bricks/PCC cable covers, complete all as specified and as directed by the Engineer-in-Charge.Notes:(a) Earth work such as excavation, returning filling and removal shall be measured and paid for separately under relevant items of Schedule 'A' BoQ..(b) Where new/old cable is laid along the same alignment/location, earth work such as excavation, returning filling and removal shall be measured and paid only once. No duplicate measurement shall be admissible in this regard. |
| 50 | Note:- The contract sum shall be calculated by deducting the amount shown in Credit Schedule attached to this tender from total amount of Schedule 'A'/BOQ Please Enable Macros to View BoQ information |