| 1 | Taking out unserviceable DG Set 200 KVA from Waldevi Pump House and shifting it to MES Yard at Arty Center complete all as directed by the Engineer - in - Charge.Note :- Quotated rates includes all T & P required for for the shifting of DG Set |
| 2 | Taking out unserviceable DG Set 320 KVA from Waldevi Pump House and shifting it to MES Yard at Arty Center complete all as directed by the Engineer - in - Charge.Note :-Quotated rates includes all T & P required for for the shifting of DG Set |
| 3 | Supply, installation, testing and commissioning Diesel Engine driven generating set of capacity not less than 200 KVA/ 160 KW, 3 phase, 4 wire, 415 V, 50 Hz,1500 RPM, AC power supply with power factor 0.8 (lagging), coupled directly to alternator, mounted on a common base plate complete with integral acoustic enclosures (shall have salient features) modular bolted construction & pure polyester based coating to ensure long life in all weather conditions & for outdoor application / installation, integrated design thereby facilitating / easy handling. The design of integral acoustic enclosure shall be approved by National Physical laboratory as per central pollution control board (CPCB-IV +) latest regulation / norms (NOx+HC < 4.0, CO < 3.5, PM < 0.2 & smoke limit < 0.7 ) with fuel tank, battery & standard accessories, tools & spares as provided by manufacturer complete with necessary PCC foundations PCC foundation as per OEM/ manufacturer recommendation to bear the load of DG set having suitable size including excavation and earth work with block masonry work and plastering all as specified and as directed:- |
| 4 | (I) ENGINE- Efficient CRDI System, designed & tested for 50 degree ambient temperature, Water cooled diesel engine at 1500 RPM, engine capacity suitable for 200 KVA output ,415 V,50 Hz, No of cylinder- 06 Nos consists of direct injection, turbo-charged, four stroke liquid cooled technology confirming to BS : 5514 and IS :10000 suitable for prime duty generating set. Alternator under NTP conditions with provision of 10 % over load for 1 hour confirming to latest CPCB norms .The Engine shall consist of the following:-(a) Dry type air cleaner(b) Exhaust silencer(c) Expansion bellows(d) Lube oil cooler(e) Lube oil filter(f) Radiator, radiator fan and mounting(g) Fuel pump, with governor(h) Fly wheel with starter ring(j) Battery charging alternator with suitable capacity(k) electric starter motor of suitable Volts as per OEM |
| 5 | Engine Monitoring system :- The genset monitoring and safety system, having following features :-(a) Controller Microprocessor based ,Graphical LED display,integrated with AMF,Synchorinisation & Communication compatable , Control panel consisting of built in ON/OFF/start key (b) Battery charging voltmeter.(c) Electronic hour meter. (d) Indication & Monitoring of oil pressure & safety trip in case of Low oil pressure. (e) Indication & Monitoring of coolant temperature & safety trip in case of high coolant temperature. (f) In-built engine shut down system in case of engine over speed. (g) Indication & Monitoring of fuel level and alarm. |
| 6 | (II) BRUSH LESS ALTERNATOR:- Alternator suitable rated for 200 KVA DG at 0.8 PF, 415V, 3 phase, 4 wire, 50 cycles/sec, 1500 RPM, self excited and self regulated, with Brushless Excitation Band of voltage regulation + 1% of rated voltage, from NO load to full load, Insulation class \\"H\\". The alternator generally conforms to BS : 2613/ IS : 4722(III) BATTERY:- Heavy duty battery of suitable AH and Nos connected to the system fully charged including lead and battery terminals complete of Make as provided by OEM |
| 7 | (IV) STANDARD CONTROL PANEL The control panel with aluminium bas bar, bottom entry and exit of cable made of sheet steel duly painted with stove enamel paint consists of followings :-(a) 01 No MCCB of suitable rating.(b) 01 No, EMS(c) 03 Nos Current Transformer(d) 02 Nos indicating lamps(e) 01 set control fuses(f) 01 No KWh meter |
| 8 | (V) DEF Tank:-(a) DEF/ Aqueous urea to sets off the chemical reaction with Exhaust gas(b) Tank size is optimized in accordance to DEF consumption(VI) Exhaust Gas Treatment System(a) DOC & SCR system sets off the reaction to meet the latest CPCB norms(b) Reduction in NOx & HC ,Reduction in PM(VII) Supply Module & DCU:- Control & monitor the DEF |
| 9 | (VIII) AUTOMATIC MAINS FAILURE (AMF) CONTROL PANEL (DOUBLE CONTACTOR)The control panel will be free standing, , cubical type, outdoor type, front operated dust and vermin proof, fabricated out 3 mm thick CRCA sheet duly power coated after necessary pre-treatment process & consisting of following :-Power Circuit Mains DG Set1 No 4P contactor suitable rated 1 No 4P contactor suitable rated1 No 3P MCCB suitably rated 1 No 3P MCCB suitably ratedControl & Metering Circuit1 No Microprocessor based AMF logic controller1 No KWh meter1 No Line Voltage Monitor L&T Make.1 set of control fuses1 No static battery charger circuit with ON/OFF switch. Battery charger \\"ON\\" indication. Reserves Polarity indication. 1 No DC battery charging ammeter. |
| 10 | (IX) ONE SET OF ACCESSORIES COMPRISING OF:-(a) Fuel tank - Capacity of tank shall be to hold diesel sufficient for 08 hours running at full load, with following features:(i) Level indicator.(ii) drain plug .(iii) MS class 'C' piping for inlet from pump to tank to engine.(iv) Fuel strainer.(v) Air vent.(b) Base plate :- Fabricated out of MS channel's ISMC of suitable size suitable for fixing of DG set all specified by the manufacturer.(X) Necessary civil foundation works including excavation , PCC , and other requirements as required and as recommended by OEM. The Foundation shall be minimum of 400mm above the FFL. Please Enable Macros to View BoQ information |
| 11 | (IX) ONE SET OF ACCESSORIES COMPRISING OF:-(a) Fuel tank - Capacity of tank shall be to hold diesel sufficient for 08 hours running at full load, with following features:(i) Level indicator.(ii) drain plug .(iii) MS class 'C' piping for inlet from pump to tank to engine.(iv) Fuel strainer.(v) Air vent.(b) Base plate :- Fabricated out of MS channel's ISMC of suitable size suitable for fixing of DG set all specified by the manufacturer.(X) Necessary civil foundation works including excavation , PCC , and other requirements as required and as recommended by OEM. The Foundation shall be minimum of 400mm above the FFL. Please Enable Macros to View BoQ information |