| 1 | Hybrid Power Factor Correction Panel |
| 2 | Design, Supply, Installation, Testing & commissioning of cubicle type Semi compartmentalized floor mounted free-standing type with separation system Hybrid APFC panel. Hybrid panel should have, 433V, 50HZ, 3 phase 4 wire/3 Wire supply. Active part should be modular and have modules of 50/100 A or mentioned in specs, AHF must be intrinsic design of voltage sourced IGBT based intelligent 3-Level topology with 12 IGBT's with Programmable Microprocessor Controller to maintain Power Factor, Harmonics & Unbalancing. The passive part must be as per IS: 16636:2017 or IEC 61921 & 61439 Part -I & II (OEM Factory made) with valid temperature rise test from CPRI/ASTA-ERDA. The passive part must be as per the duly housed in epoxy powder coated 2mm thick CRCA steel sheet semi compartmentalized enclosure free standing type with all supports, accessories, switch gears, capacitors, control gears, protections, wiring, interconnections, control MCBs, controllers, reactors, etc. |
| 3 | All Major components like Capacitor, Reactors, Controller, Capacitor Duty Contactor and AHF module should be of single manufacturer for better operation and maintenance practice. All capacitors should be ISI/BIS Marked with valid CML Number on each name plate. All detuned reactors shall be with CE marking and ROHS compatible, IEC-60529, Electromagnetic standard FCC 15J,Class-A IEC61000-4, ANSI IEEE Standard 519-2014 (Harmonics LIMITS) items like capacitors should have valid CPRI type tested as per the relevant IS. Hybrid Panel should be IP-42 and duly housed in epoxy powder coated 2mm thick CRCA sheet steel semi compartmentalized enclosure free standing type with all supports, accessories, switch gears, control gears, protections, wiring, interconnections, control MCBs and maintain PF,I-THD,V-THD as per IEEE 519-92 etc. as required. Also complete in all respects & having its main components as bellow along with all other standard components ,circuitry & specifications as required: |
| 4 | NOTE:1) CT,VT for power factor measurement source side also consider in all panels. |
| 5 | Hybrid Power Factor Correction Panel AHF(300 Amp) + (APFC) 450 KVAR |
| 6 | INCOMMER |
| 7 | S.I.T.C of 1 No.of 1250 A 4P Electrically Operated Drawout (EDO) type ACB with Ics=Icu=Icw=50 KA having Microprocessor based releases for overload, S/C, O/C and earth fault protection. |
| 8 | 1 No. of Display meter with compatible RS 485 ports. |
| 9 | 3 No.of Phase Indicating & ON-OFF LED Lights 230 V. |
| 10 | 1 Set. of Ammeter - digital 3 Phase. |
| 11 | 6 No. of MCB 6A-SP-10kA-C-Curve. |
| 12 | BUS BARS |
| 13 | 1600-Amps (neutral equal size) 3 phase 4 wire 415 volts 50 HZ AL bus bars with colour coded PVC heat shrinkable sleeves. |
| 14 | OUTGOING |
| 15 | Active Part: |
| 16 | AHF 300 Amp - 1 Nos. Three Lavel Topology 12-IGBT based active technology with gate driver,interfacing,voltage sencing & control cards,heat sinks,cooling fan,current tranducers,SMPS,SSR etc.) each have following. |
| 17 | 9 Nos. of High-speed Semiconductor fuse |
| 18 | 3 No of 100 Amp 3P4W AHF module (3 -Level Topology ,12 IGBT Circuit) |
| 19 | 1 No. of Programmable HMI With 7inches LED Display. |
| 20 | Passive Part: |
| 21 | APFC 450Kvar-1Nos. The Solution should comprise of 450kVAr including Capacitor Duty Contactor, APFC relay & Detuned filter reactors 14% with 143% linearity. The capacitor bank should have the following step ratings:100X2+50X 3+25X2+15X1+10X2+5X3 Capacitor shall be Gas impregnated Heavy Duty MPP type low loss with overcurrent capability of 1.8xIr and Inrush current capability of 400xIr.Each stage of the capacitor bank should have suitable overload and short circuit protection as defined below. |
| 22 | 1 No APFC Relay with 3 CT sencing facilities. |
| 23 | Cap Bank -100KVAR - 2 Nos. (Each Consist) |
| 24 | 1 No. 250A 3P MCCB 25 KA with built in protection |
| 25 | 1 No. Capacitor Duty Contactor for 100 kvar Capacitor Unit. |
| 26 | 4 No. of 33.1KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 27 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 28 | Cap Bank -50KVAR - 3 Nos. (Each Consist) |
| 29 | 1 No. 125A 3P MCCB 25 KA with built in protection |
| 30 | 1 No. Capacitor Duty Contactor for 50 kvar Capacitor Unit. |
| 31 | 2 No. of 33.1KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 32 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 33 | Cap Bank -25KVAR - 2 Nos. (Each Consist) |
| 34 | 1 No. 63A 3P MCCB 25 KA with built in protection |
| 35 | 1 No. Capacitor Duty Contactor for 25 kvar Capacitor Unit. |
| 36 | 1 No. of 33.1KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 37 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 38 | Cap Bank -15KVAR - 1 Nos. (Each Consist) |
| 39 | 1 No. 32A 3P MCCB 25 KA with built in protection |
| 40 | 1 No. Capacitor Duty Contactor for 15 kvar Capacitor Unit. |
| 41 | 1 No. of 20KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 42 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 43 | Cap Bank -10KVAR - 2 Nos. (Each Consist) |
| 44 | 1 No. 25A 3P MCCB 25 KA with built in protection |
| 45 | 1 No. Capacitor Duty Contactor for 10 kvar Capacitor Unit. |
| 46 | 1 No. of 12.5KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 47 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 48 | Cap Bank -5KVAR - 3 Nos. (Each Consist) |
| 49 | 1 No. 16A 3P MCCB 25 KA with built in protection |
| 50 | 1 No. Capacitor Duty Contactor for 7 kvar Capacitor Unit. |
| 51 | 1 No. of 6.3KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 52 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 53 | As Above |
| 54 | Hybrid Power Factor Correction Panel AHF (250 Amp) + APFC (400 KVAR ) |
| 55 | INCOMMER |
| 56 | S.I.T.C of 1 No. of 1250 A 4P Electrically Operated Drawout (EDO) type ACB with Ics=Icu=Icw=50 KA having Microprocessor based releases for overload, S/C, O/C and earth fault protection. |
| 57 | 1 No. of Display meter with compatible RS 485 ports(MODBUS). |
| 58 | 3 No. of Phase Indicating & ON-OFF LED Lights 230 V. |
| 59 | 1 Set. of Ammeter - digital 3 Phase. |
| 60 | 6 No. of MCB 6A-SP-10kA-C-Curve. |
| 61 | BUS BARS |
| 62 | 1600-Amps (neutral equal size) 3 phase 4 wire 415 volts 50 HZ AL bus bars with colour coded PVC heat shrinkable sleeves. |
| 63 | OUTGOING |
| 64 | Active Part: |
| 65 | AHF 250 Amp - 1 Nos. Three Level Topology 12-IGBT based active technology with gate driver, interfacing, voltage sensing & control cards, heat sinks, cooling fan, current tranducers, SMPS,SSR etc.) each have following. |
| 66 | 9 Nos. of High speed Semiconductor fuse |
| 67 | 2 Nos. of 100 Amp 3P4W AHF module (3 -Level Topology ,12 IGBT Circuit) |
| 68 | 1 No. of 50 Amp 3P4W AHF module (3 -Level Topology ,12 IGBT Circuit) |
| 69 | 1 No. of Programmable HMI With 7inches LED Display. |
| 70 | Passive Part: |
| 71 | APFC 400Kvar-1Nos. The Solution should comprise of 450kVAr including Capacitor Duty Contactor,APFC relay & Detuned filter reactors 14% with 143% linearity.The capacitor bank should have the following step ratings:100X2+50X2+25X2+15X1+10X2+5X3 Capacitor shall be Gas impregnated Heavy Duty MPP type low loss as per standards with overcurrent capablity of 1.8xIr and Inrush current capability of 400xIr .Each stage of the capacitor bank should have suitable overload and short circuit protection as defined below. |
| 72 | 1 No APFC Relay with 3 CT sencing facilities. |
| 73 | Cap Bank -100KVAR - 2 Nos. (Each Consist) |
| 74 | 1 No. 250A 3P MCCB 25 KA with built in protection |
| 75 | 1 No. Capacitor Duty Contactor for 100 kvar Capacitor Unit. |
| 76 | 4 No. of 33.1KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 77 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 78 | Cap Bank -50KVAR - 2 Nos. (Each Consist) |
| 79 | 1 No. 125A 3P MCCB 25 KA with built in protection |
| 80 | 1 No. Capacitor Duty Contactor for 50 kvar Capacitor Unit. |
| 81 | 2 No. of 33.1KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 82 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 83 | Cap Bank -25KVAR - 2 Nos. (Each Consist) |
| 84 | 1 No. 63A 3P MCCB 25 KA with built in protection |
| 85 | 1 No. Capacitor Duty Contactor for 25 kvar Capacitor Unit. |
| 86 | 1 No. of 33.1KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 87 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 88 | Cap Bank -15KVAR - 1 Nos. (Each Consist) |
| 89 | 1 No. 32A 3P MCCB 25 KA with built in protection |
| 90 | 1 No. Capacitor Duty Contactor for 15 kvar Capacitor Unit. |
| 91 | 1 No. of 20KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 92 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 93 | Cap Bank -10KVAR - 2 Nos. (Each Consist) |
| 94 | 1 No. 25A 3P MCCB 25 KA with built in protection |
| 95 | 1 No. Capacitor Duty Contactor for 10 kvar Capacitor Unit. |
| 96 | 1 No. of 12.5KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 97 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 98 | Cap Bank -5KVAR - 3 Nos. (Each Consist) |
| 99 | 1 No. 16A 3P MCCB 25 KA with built in protection |
| 100 | 1 No. Capacitor Duty Contactor for 7 kvar Capacitor Unit. |
| 101 | 1 No. of 6.3KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 102 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 103 | As Above |
| 104 | Hybrid Power Factor Correction Panel AHF (150 Amp) + APFC (250 KVAR) |
| 105 | INCOMMER |
| 106 | 1No. 800A Amps. 415 Volts 4P Ics=Icu=Icw=50 KA Microprocessor Based Type ACB with overload, S/C, O/C and earth fault protection. |
| 107 | 1 No. of Display meter with compatible RS 485 ports(MODBUS). |
| 108 | 3 No. of Phase Indicating & ON-OFF LED Lights 230 V. |
| 109 | 1 Set. of Ammeter - digital 3 Phase. |
| 110 | 6 No. of MCB 6A-SP-10kA-C-Curve. |
| 111 | BUS BARS |
| 112 | 1000-Amps (neutral equal size) 3 phase 4 wire 415 volts 50 HZ AL bus bars with colour coded PVC heat shrinkable sleeves. |
| 113 | OUTGOING |
| 114 | Active Part: |
| 115 | AHF 150 Amp - 1 Nos. Three Level Topology 12-IGBT based active technology with gate driver, interfacing, voltage sensing & control cards, heat sinks, cooling fan, current tranducers, SMPS,SSR etc.) each have following. |
| 116 | 9 Nos. of High speed Semiconductor fuse built in protection. |
| 117 | 1 No of 100 Amp 3P4W AHF module (3 -Level Topology ,12 IGBT Circuit) |
| 118 | 1 No of 50 Amp 3P4W AHF module (3 -Level Topology ,12 IGBT Circuit) |
| 119 | 1 No. of Programmable HMI With 7inches LED Display. |
| 120 | Passive Part: |
| 121 | APFC 250Kvar-1Nos. The Solution should comprise of 450kVAr including Capacitor Duty Contactor,APFC relay & Detuned filter reactors 14% with 143% linearity.The capacitor bank should have the following step ratings:50X3+25X2+15X1+10X2+5X3 Capacitor shall be Gas impregnated Heavy Duty MPP type low loss as per standards with overcurrent capablity of 1.8xIr and Inrush current capability of 400xIr .Each stage of the capacitor bank should have suitable overload and short circuit protection as defined below. |
| 122 | 1 No APFC Relay with 3 CT sencing facilities. |
| 123 | Cap Bank -50KVAR - 3 Nos. (Each Consist) |
| 124 | 1 No. 125A 3P MCCB 25 KA with built in protection |
| 125 | 1 No. Capacitor Duty Contactor for 50 kvar Capacitor Unit. |
| 126 | 2 No. of 33.1KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 127 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 128 | Cap Bank -25KVAR - 2 Nos. (Each Consist) |
| 129 | 1 No. 63A 3P MCCB 25 KA with built in protection |
| 130 | 1 No. Capacitor Duty Contactor for 25 kvar Capacitor Unit. |
| 131 | 1 No. of 33.1KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 132 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 133 | Cap Bank -15KVAR - 1 Nos. (Each Consist) |
| 134 | 1 No. 32A 3P MCCB 25 KA with built in protection |
| 135 | 1 No. Capacitor Duty Contactor for 15 kvar Capacitor Unit. |
| 136 | 1 No. of 20KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 137 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 138 | Cap Bank -10KVAR - 2 Nos. (Each Consist) |
| 139 | 1 No. 25A 3P MCCB 25 KA with built in protection |
| 140 | 1 No. Capacitor Duty Contactor for 10 kvar Capacitor Unit. |
| 141 | 1 No. of 12.5KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 142 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 143 | Cap Bank -5KVAR - 3 Nos. (Each Consist) |
| 144 | 1 No. 16A 3P MCCB 25 KA with built in protection |
| 145 | 1 No. Capacitor Duty Contactor for 7 kvar Capacitor Unit. |
| 146 | 1 No. of 6.3KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 147 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 148 | As Above |
| 149 | Hybrid Power Factor Correction Panel AHF (150 Amp) + APFC (200 KVAR ) |
| 150 | INCOMMER |
| 151 | 1 No. of 630A Amps. 415 Volts 4P Microprocessor Based Type ACB of 50KA with overload, S/C, O/C and earth fault protection. |
| 152 | 1 No. of Display meter with compatible RS 485 ports. |
| 153 | 3 No. of Phase Indicating & ON-OFF LED Lights 230 V. |
| 154 | 1 Set. of Ammeter - digital 3 Phase. |
| 155 | 6 No. of MCB 6A-SP-10kA-C-Curve. |
| 156 | BUS BARS |
| 157 | 800-Amps (neutral equal size) 3 phase 4 wire 415 volts 50 HZ AL bus bars with colour coded PVC heat shrinkable sleeves. |
| 158 | OUTGOING |
| 159 | Active Part: |
| 160 | AHF 150 Amp - 1 Nos. Three Level Topology 12-IGBT based active technology with gate driver, interfacing, voltage sensing & control cards, heat sinks, cooling fan, current tranducers, SMPS, SSR etc.) each have following. |
| 161 | 9 Nos. of High speed Semiconductor fuse built in protection. |
| 162 | 1 No of 100 Amp 3P4W AHF module (3 -Level Topology ,12 IGBT Circuit) |
| 163 | 1 No of 50 Amp 3P4W AHF module (3 -Level Topology ,12 IGBT Circuit) |
| 164 | 1 No. of Programmable HMI With 7inches LED Display. |
| 165 | Passive Part: |
| 166 | APFC 200Kvar-1Nos. The Solution should comprise of 450kVAr including Capacitor Duty Contactor,APFC relay & Detuned filter reactors 14% with 143% linearity.The capacitor bank should have the following step ratings:50X2+25X2+15X1+10X2+5X3 Capacitor shall be Gas impregnated Heavy Duty MPP type low loss as per standards with overcurrent capablity of 1.8xIr and Inrush current capability of 400xIr .Each stage of the capacitor bank should have suitable overload and short circuit protection as defined below. |
| 167 | 1 No APFC Relay with 3 CT sencing facilities. |
| 168 | Cap Bank -50KVAR - 2 Nos. (Each Consist) |
| 169 | 1 No. 125A 3P MCCB 25 KA with built in protection |
| 170 | 1 No. Capacitor Duty Contactor for 50 kvar Capacitor Unit. |
| 171 | 2 No. of 33.1KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 172 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 173 | Cap Bank -25KVAR - 2 Nos. (Each Consist) |
| 174 | 1 No. 63A 3P MCCB 25 KA with built in protection |
| 175 | 1 No. Capacitor Duty Contactor for 25 kvar Capacitor Unit. |
| 176 | 1 No. of 33.1KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 177 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 178 | Cap Bank -15KVAR - 1 Nos. (Each Consist) |
| 179 | 1 No. 32A 3P MCCB 25 KA with built in protection |
| 180 | 1 No. Capacitor Duty Contactor for 15 kvar Capacitor Unit. |
| 181 | 1 No. of 20KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 182 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 183 | Cap Bank -10KVAR - 2 Nos. (Each Consist) |
| 184 | 1 No. 25A 3P MCCB 25 KA with built in protection |
| 185 | 1 No. Capacitor Duty Contactor for 10 kvar Capacitor Unit. |
| 186 | 1 No. of 12.5KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 187 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 188 | Cap Bank -5KVAR - 3 Nos. (Each Consist) |
| 189 | 1 No. 16A 3P MCCB 25 KA with built in protection |
| 190 | 1 No. Capacitor Duty Contactor for 7 kvar Capacitor Unit. |
| 191 | 1 No. of 6.3KVAR MPP-H capacitor at 525 V AC with 14% AL wound Detuned Reactor. |
| 192 | 1 Set of start/stop PB & On/OFF LED, A/M S.S |
| 193 | As Above |
| 194 | Supplying of following size of XLPE insulated , PVC sheathed cable of 1.1 kV grade , aluminium conductor, flat steel strip armoured,comforming to IS: 7098 (Part 2) with upto date ammendment complete as required. |
| 195 | 3.5C X 400 sq. mm |
| 196 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. |
| 197 | Above 185 sq. mm and upto 400 sq. mm |
| 198 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 199 | Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
| 200 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/ XLPE aluminium conductor cable of 1.1 kV grade as required. |
| 201 | 3.5C X 400 sq. mm |
| 202 | LT 1.1 kV CONTROL CABLES |
| 203 | Supplying of following sizes of 1.1 kV grade PVC insulated copper conductor armoured stranded Control Cable conforming to IS :1554 complete as required and as per specifications. |
| 204 | 6 core, 2.5 Sq.mm. Cu. Conductor cable |
| 205 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 206 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 207 | Supplying and making end termination with double brass compression gland and Copper lugs for following size of PVC sheathed copper conducter armoured control cable of 1.1 kV grand as required. |
| 208 | 6 C x 2.5 Sq.mm. |
| 209 | Supply , Installation, Testing and commissioning of following rating Acb's in the spare compartment of existing LT Panels at various locations including fabrication, connection with solid bus bar, etc. as required |
| 210 | 2 -Nos. ACB, EDO Type 1250 Amps, 50 kA, 4 Pole, Microprocessor Based . SITC of Indicator RYB, On,Off,trip, current transformer, CT shorting Terminals, MCB , Neutral Link, Auxiliary Contractor, Terminal Blocks, Wiring for feeder, Busbar Link for ,etc as required at site. |
| 211 | 4-Nos. of 800A 4P ACB with Ics=Icu=Icw 50 KA having Mircroprocessor based releases for O/L, S/C & E/F. SITC of Indicator RYB, On,Off,trip, current transformer, CT shorting Terminals, MCB , Neutral Link, Auxiliary Contractor, Terminal Blocks, Wiring for feeder, Busbar Link for ,etc as required at site. |
| 212 | Each ACB shall have one set of the following items: |
| 213 | Intelligent multi function digital meter Datalog (8 MB),Analog I/O, digital I/O variants available, Meter with Ethernet port available Parameters: V, A, F, kW, KVA, kVAr, kWh, kVAh, kVArh, PF, Runhr, Onhr, Interupts,Phase angle, THD, Neutral current, Max Demand (with RTC), Events (high-low) with time stamp,Individual Harmonics upto 31st. |
| 214 | All ACBs shall have Icu=Ics=Icw for 1.0 secs for all ACBs |
| 215 | 1 Set Indication Lamps, LED type, for RYB with2 Amp control MCB.& breaker 'ON', 'OFF', 'TRIP' & spring charged lamps with 2 Amp MCB for controlling alonwith SITC of TNC switch. |
| 216 | As Above upto the entire satisfaction of Engineer-in -Charge |
| 217 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 218 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection / terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 219 | Add GST @6.33% |
| 220 | Less Rebate on following materials after de-termination and dismantling from existing panel including transportation from PGI. |
| 221 | 500KVAR APFC Panel at ACC SS & ATC SS |
| 222 | 480KVAR APFC Panel at NHE SS |
| 223 | 250 KVAR APFC Panel at APC SS & AEC SS |
| 224 | 175 KVAR APFC Panel at Emergency SS |
| 225 | 150 KVAR APFC Panel at MDH SS Please Enable Macros to View BoQ information |