| 1 | Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth for poles, laying under ground HT cable, GI tubing (where provided for protection of cables), stay and getting out in any type of soil complete all as specified and directed. |
| 2 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm. complete all as specified and directed. |
| 3 | Removing excavated material soil n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed. |
| 4 | M&L for sand cushioning with dry and clean fine river sand for underground cable 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cable complete all as specified and directed. Note:- Punned thickness shall be considered for payment purpose. |
| 5 | M & L for cutting of road /hard standing as required at site, not exceeding 20 cm width and not exceeding 60 cm in depth for laying of cable protection pipe including insert the cable inside pipe making good the disturbed road/hard standing by providing PCC (1:2:4) Type B-1 using 20 mm graded stone aggregate up to the existing surface level and make good complete all as specified and directed. |
| 6 | Taking up or down steel tubing and connections,including cleaning for refixing or removal to store of any bore complete as specified and directed. |
| 7 | S&F GI tubing light grade 80 mm dia with all fittings laid in trenches or fixed on pole for protection of cable while fix on pole or HT pole structures pipe tightend with D type steel clamp, washers, nut, bolt etc. complete as specified and directed. |
| 8 | Supply and laying un-reinforced precast concrete cable cover of class HV, type-1 flat of size 300mm x 180mm x 40mm (ISI marked) for protection of UG cable over sand cushioning perpendicular across the cable length wise in trenches complete all as specified and directed. |
| 9 | S&F/Laying, connecting and testing of HT cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) 11KV (Earthed) as per IS 7098 (Part-II) with stranded aluminium conductor of following size complete all as specified and directed:-Note:- 1. The earth work, GI pipe shall be measured and paid sepretely.2. Cable may fixing/ passing through pipe laid in trenches or fixed to pole/ wall or fixed to LT panel etc.3. ACSR Conductor and cross arms,UG cable replaced with UG cable |
| 10 | 120 Sqmm, 3 core. |
| 11 | M & L for cable jointing kit suitable for 11 KV (E) grade cable outdoor end termination, cold shrinkable type joint complete with joining material and accessories suitable for 95 sqmm XLPE 3 Core HT cable armoured aluminium conductor cable join on existing outdoor termination on HT pole,Transformer after completion of cable joint positioing the HT cable complete all as specified and directed. |
| 12 | Dismantling cross-arms of M.S. channel or angle sections etc. including mild steel nuts,bolts,washers etc and removing from site of work complete all as specified and directed. |
| 13 | Dismantling of ACSR conductor of any type complete all as specified and directed. |
| 14 | Supply, installation, testing of 11 KV outdoor type gang operated triple pole air break switch suitable for vertical mounting fixed type complete with 12 insulators 400 amps rating before installation merge the insulators in water and meggaring the insulators, for testing 11000 volt meggar provided by contractor and steel frame mechanically operated mechanism consisting of operating rod 25 mm bore medium grade GI pipe of suitable length worked form ground level and with locking arrangement flat iron clamp 50 mm x 6 mm size including MS channel of suitable size and length for fixing GOD including bolts, nuts and washers as in repair complete all as specifed and directed. Please Enable Macros to View BoQ information |