| 1 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 2 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia includingaccessories, and providing masonry enclosure with cover platehaving locking arrangement and watering pipe etc. with charcoal/coke and salt as required. |
| 3 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 4 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 5 | Painting on G.S. sheet with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : |
| 6 | Old work (one or more coats) |
| 7 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel,making connections, etc. as required. |
| 8 | 100 A,30KA,FPMCCB |
| 9 | 125 A,36KA,FPMCCB |
| 10 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required |
| 11 | 6 Moudle (200mmX75mm) |
| 12 | 12 Module (200mmX150mm) |
| 13 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 14 | 5/6 A switch |
| 15 | 3 pin 5/6 A socket outlet |
| 16 | 15/16 A switch |
| 17 | 6 pin 15/16 A socket outlet |
| 18 | Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 19 | Supplying and fixing brass batten/ angle holder (PVC) including connection etc. as required. |
| 20 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 21 | Supplying and fixing of following sizes of heavy class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 22 | 25 mm |
| 23 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 24 | 3x 2.5 sq.mm |
| 25 | 3x 4sq.mm |
| 26 | 3x 6 sq.mm |
| 27 | Supply and fixing of suitable size G.I. box with modular plate and cover on front or surface in recess including providing and fixing 6 pin 5/6 & 15/16A modular socket outlet and 15/16A modular switch, connection etc.as required. |
| 28 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. |
| 29 | Group A |
| 30 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 31 | Group A |
| 32 | Supplying and fixing suitable size G.I. box with modular plate and cover in front on surface or in recess including providing and fixing 25A modular socket outlet and 25A modular SP MCB \\"C\\" curve including connections, painting etc. as required. |
| 33 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessoriesincluding safety pin, nut bolts,washers,temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase ACsupply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR,PVC insulated copper conductor single core cableand earthing etc. as required. |
| 34 | 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 35 | Servicing of power distribution cubical panel/Feeder pillar having MCCB at incoming and MCCB/MCB at outgoing which includes, checking of control circuit , power circuit, replacement of burnt/broken thimble upto size 2.5 sqmm, busbar tightening, internal connection/termination tightening, removing of rust from inner and outer surface, removing the carbon deposit from conductor, cleaning with the help of blower/cloths, packing of holes with suitable sealent etc. complete as required. This item exclude replacement of any spare part/accessories/switchgear, painting of panel and same shall be paid seperately.Panel size upto 2000(W) X 2400(H) but not below the 1500(W) X 1500(H). Dimensions are in mm. |
| 36 | Servicing of power distribution cubical panel/Feeder pillar having MCCB at incoming and MCCB/MCB at outgoing which includes, checking of control circuit , power circuit, replacement of burnt/broken thimble upto size 2.5 sqmm, busbar tightening, internal connection/termination tightening, removing of rust from inner and outer surface, removing the carbon deposit from conductor, cleaning with the help of blower/cloths, packing of holes with suitable sealent etc. complete as required. This item exclude replacement of any spare part/accessories/switchgear, painting of panel and same shall be paid seperately.Panel size upto 1000(W) X 1000(H) but not below the 500(W) X 500(H). Dimensions are in mm. |
| 37 | Servicing of power distribution cubical panel/Feeder pillar having MCCB at incoming and MCCB/MCB at outgoing which includes, checking of control circuit , power circuit, replacement of burnt/broken thimble upto size 2.5 sqmm, busbar tightening, internal connection/termination tightening, removing of rust from inner and outer surface, removing the carbon deposit from conductor, cleaning with the help of blower/cloths, packing of holes with suitable sealent etc. complete as required. This item exclude replacement of any spare part/accessories/switchgear, painting of panel and same shall be paid seperately.Panel size upto 1500(W) X 1500(H) but not below the 1000(W) X 1000(H). Dimensions are in mm. |
| 38 | Supplying and Fixing of LT panel door lock made of anti-Corrosion material, having PVC knob for opening/closing, in existing LT panel etc. complete as required. |
| 39 | Supplying and Fixing of 3 phase digital voltmeter in existing LT panel incluiding connection and all mounting accessories complete as required. Make Laurtz knudsen Model no CI 1,Cat.No.WL132010OOOO or equivalent model of ABB, Siemens |
| 40 | Supplying and Fixing of 3 phase digital ammeter in existing LT panel incluiding connection and all mounting accessories complete as required. Make Laurtz knudsen Model no CI 1,Cat.No.WL131010OOOO or equivalent model of ABB, Siemens |
| 41 | Supplying and Fixing of flush head type push start/stop button of colour red/ green /black/ yellow/ white/ blue/ amber/ gray, size 22.5 mm, suitable for DC/AC voltage in existing LT panel/ starter panel etc. complete as required. Make- Lauritz Knudsen , Cat. No. EMNFD1 Gen Next or equivalant model of ABB/Seimens/Salzer |
| 42 | Supplying and Fixing of LED indicator of colour white/blue, size 22.5 mm in cluster design, suitable for DC/AC voltage in existing LT distribution panel including connection etc. complete as required. Make- Lauritz Knudsen , Cat. No. EPL Gen Next Pro or equivalant model of ABB/Seimens/Salzer |
| 43 | Supplying and Fixing of LED indicator of colour Red/Green/Yellow/amber in existing LT distribution panel of size 22.5 mm in cluster design, suitable for DC/AC voltage, etc complete as required.Make- Lauritz Knudsen , Cat. No. EPL Gen Next Pro or equivalant model of ABB/Seimens/Salzer |
| 44 | Supply and fixing Shock Treatment Chart duly mounted on a wooden frame with 5mm thick glass etc. as required .(approximate front area 1.20 sq meter). |
| 45 | Providing and fixing of portable First Aid box made of rust registant GI Sheet with multipartition storage, handle carry design, including medicine Antiseptics solution, Wound Care, Painkillers, Eye Care drop, cotton wool, Roller bandage, Safety pins, conforming to IS 13115: 1991 etc. completed as required. |
| 46 | Supplying and fixing of 40A/50A/63A, 10 KA rating, double pole, 415 V, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required. Make-Hager, Cat.No-NCN240N/NCN250N/NCN263N or equivalent model of Legrand/ABB. |
| 47 | Supply, Installation, testing and commissioning of one no. LED tube of frosted cover design, 18 Watt, 2100 lm, 50000 burning hours, size 1200 mm in existing single box or double box fittings complete as required. Tube equivalent to Philips Make, Cat No. Mas LEDTube 1200mm 18W 865 T8I-2100lm |
| 48 | Supply, Installation,testing and comissioning of 12 inch heavy duty, AC, Single Phase 230 Volt, 50 Hz, 1350 RPM, steel body exhaust fan in the existing opening, including, making good the damage, cable connection etc. as required Please Enable Macros to View BoQ information |