Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Havells/Polycab/RR Kabel/Finolex(SAMPLE TO BE APPROVED BEFORE INITIATED) |
| 2 | Group C |
| 3 | Re-Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class steel/PVC conduit including dismenteling as required.Havells/Polycab/RR Kabel/Finolex(SAMPLE TO BE APPROVED BEFORE INITIATED) |
| 4 | Group C |
| 5 | Wiring for Light /Power Plug with 2 x 4 sq.mm FRLS PVC Insulated Copper Conductor single core cable in surface/Recessed medium class PVC Conduit along with 1 No. 4 sq.mm FRLS PVC Insulated copper conductor single core cable for loop earthing as required. Havells/Polycab/RR Kabel/Finolex(SAMPLE TO BE APPROVED BEFORE INITIATED) |
| 6 | Wiring for Circuit/Submain Wiring along with earth Wire with the following Sizes of FRLSPVC insulated copper conductor,single core Cable in surface/Recessed medium class PVC conduit as required. Havells/Polycab/RR Kabel/Finolex(SAMPLE TO BE APPROVED BEFORE INITIATED) |
| 7 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 8 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 9 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 10 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 11 | 4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
| 12 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess,including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. (Anti-Bacterial Series) |
| 13 | Supplying and fixing modular blanking plate on the existing modular plate and switch box excluding modular plate as required |
| 14 | Supplying and Fixing suitable size G.I box with modular plate and cover in front on surface or in recess,including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps modular witch,connection,painting etc. as required.(Anti-Bacterial Series) |
| 15 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (Anti-Bacterial Series) |
| 16 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 17 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding plate etc. as required (Anti-Bacterial Series) |
| 18 | 5/6 A switch |
| 19 | 15/16 A switch |
| 20 | 3 pin 5/6 A socket outlet |
| 21 | 6 pin 15/16 A socket outlet |
| 22 | Supplying and fixing of Modular base & cover plate on existing modular metal boxes etc. as required |
| 23 | 18 Module |
| 24 | 12 Module |
| 25 | 8 Module |
| 26 | 6 Module |
| 27 | 4 Module |
| 28 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 29 | Supply installation testing and commissioning of (BLDC) Ceiling Fan with Voltage Range 90 V to 300 V,Min. Air Delivery 212 CMM,Service Value 5.3 Cu.m/min/watt,Aluminium Blades ,including wiring the down rods of standard length(Upto 45 cm)with 1.5 sq.mm FR PVC insulated,copper conductor,single core cable including providing and fixing phenolic laminated sheet cover on the Fan Box etc as Required. |
| 30 | Supply,Installation,Testing and Commissioning 486 Cu.m/Hr. AC 220-240 Volts, 50 Hz exhaust fan and Noise Level not exceeding 37 dB of Following Sizes including connection etc. complete as required . |
| 31 | 300 mm |
| 32 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) (IP54) |
| 33 | 12 way (4 +36), Double door |
| 34 | 8 way (4 + 18), Double door |
| 35 | 6 way (4 + 24), Double door |
| 36 | Supplying and fixing following rating, Four pole, 415 V, 10 Ka M.C.B in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Legrand/L&T/ABB/Schneider) |
| 37 | 63 A F.P MCB 10 Ka \\"C\\" Curve |
| 38 | 40 A F.P MCB 10 Ka \\"C\\" Curve |
| 39 | Supplying and fixing 5 amps. to 32 amps.rating 240 volts 'C' series, miniature circuit breaker of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 40 | Single Pole |
| 41 | Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance value. |
| 42 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm diaincluding accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 43 | Earth pit chamber (300mm x 300mm) with CI cover for the above. |
| 44 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 45 | Supplying,Installation,Testing and Commissioning of Copper Earthing Electrode of Size 50 x 3000mm with Copper Pipe Outer Dia. 50 mm (+-) 5 %),Length 3000 mm,Inner & and Outer Strip Size 25X6mm (Copper),Terminal Hole Two Nos.,Terminal Hole Dia. 14 mm,Seal Plate Thickness 4 mm,Base Plate Thickness 4 mm,Inner filling Material – Highly Conductive Super Crystalline Mixture,Outer filling material - Highly Hygroscopic, Non corrosive Back Fill Compound 50 Kgs. |
| 46 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 47 | Supply & Fixing of 36W , 2x2 LED reccesse type Luminaire suitable for operating Voltage range of 150V-270V with inbuilt surge protection of 2KV and Color temprature 5700K ANSI BIN . Minimum system lumens 4320 and system efficacy >120 Lm/watt (Supported by in house NABL approved report of LM79 provided by OEM and duly signed by company manager not below rank of RM) . Luminaire should be suitable for armstrong /grid ceiling mounting with help of 4 Nos clips for suspension. Body made up of CRCA powder coated with Diffused Optics. Luminaire size should not be less than 595x595x60mm and power factor >=0.95, CRI>=80, THD<10%, Max system wattage should be 36 Watt, IP-20 ingress protection. NABL certification and BIS (both luminaire and driver) requried to be provided at the time of sample approval. |
| 48 | Supply installation testing and commissioning of IP20 led downlighter 18 W +/- 1 W LED Recess downlighter round shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV.(LM79/80 Approved Commercial light) |
| 49 | Supply installation testing and commissioning of IP20 led downlighter 15 W-18 W +/- 1 W LED Surface downlighter round shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV.(LM79/80 Approved Commercial light) |
| 50 | Supply installation testing and commissioning of IP65 led Street Light 90 W +/- 5 W complete with M.S/G.I Pipe(Duly Bracket embedded along with Parapet/Wall including complete connections as required .The P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80. The LED with Useful life of 50000 Hrs at L70. The Input voltage range shall be 150V to 265V. The Fixture should have In-built Surge Protection of 2.5kV |
| 51 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. (Anti-Bacterial Series) |
| 52 | Telephone socket outlet |
| 53 | Computer Socket RJ45 Modular type |
| 54 | TV antenna socket outlet |
| 55 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 56 | 1 or 2 Module (75mmX75mm) |
| 57 | Supplying and Fixing of Following sizes of PVC Conduit along with Accessories in surface/Recess including painting in case of surface conduit,cutting the wall and making good the same in case of recessed conduit as required. |
| 58 | 25mm PVC Conduit |
| 59 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 60 | 2 Pair |
| 61 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. |
| 62 | 1 run of cable |
| 63 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required. |
| 64 | Supply, installation, testing and commissioning of Junction Boxes/DB-10 Pairs with Original Krone module and Back Mount Frame and have Lock -n- key, complete in all respect as per specification and desired by EIC |
| 65 | Supply & Erection of lockable 12 U rack with 5A strip and two fan for distribution, mounting of patch panels, hubs, switches etc,, complete as per specification and as desired by EIC. |
| 66 | Supplying, installation, testing & commissioning of Giga Switch 24 port |
| 67 | Supplying, installation, testing & commissioning of Cable Manager |
| 68 | Supplying, installation, testing & commissioning of Patch panel 24 port |
| 69 | Supplying, installation, testing & commissioning of patch cord 1 mtrs |
| 70 | Supplying, installation, testing & commissioning of patch cord 3 mtrs |
| 71 | Supplying, installation, testing & commissioning of complete I/O Box |
| 72 | Supplying, installation, testing & commissioning of Dynamic Rack 12 U full Loaded |
| 73 | Supplying, installation, testing & commissioning of maincontrol and indicating panel made out of 16 SWG MS sheet to accommodate the following items duly powder coated in approved colour with louvers for ventilation, locking arrangement, audio and visual indication for fire alarm and public address system, monitoring system including connections, interconnections etc complete as required. 6 zone panel for fire alarm system100 watt amplifier racks suitable for operation on 230VAC/24V DC supply conforming to IEC-268-3 complete with all Talk back master station with LED PTT (press to talk) push button for operation on 230V AC/24 V DC supply conforming to IEC-268 for simplex mode of operation/communication suitable for 20 Nos.talk back unit -1 set.Annoucement control desk suitable for selection of different zones selectively and ON ALL CALL switch with visual indication etc., complete as required- 1 set.Amplifier change over switch for inter changing amplifier- 1 No.Monitor panel for loudspeaker complete output selectorON/OFF switch, fuse visual indications etc. complete asrequired- 1 No.Gooseneck microphone with stand and ON/OFF switch -1 No.Mains ON/OFF switch, fuse indication lamps, DC and ACvoltmeters & ammeters terminal blocks etc. complete asrequired -1 set.Battery charger trickle cum boost to take complete load of fire alarm & PA system complete with all accessoriesincluding providing & fixing of 2 nos. 12 volt,30 AH eachsealed maintenance free batteries -1 set. |
| 74 | Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required. |
| 75 | Supplying, installation, testing & commissioning fire alarmsounder with facility to make announcement, mounted in M.S.box (16 SWG) with hinged cover plate & suitable for operationwith amplifier i/c line matching transformer etc. complete asrequired. |
| 76 | Supplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required. |
| 77 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required |
| 78 | 2 x 1.5 sq. mm |
| 79 | Supplying,Installation,Testing and Commissioning of Ceiling Mounted Automated Modular Fire Suppression System (ABC MAP90 Powder Based ) - 10KG suitable for Class A, B, C and Electrically started fires. |
| 80 | SITC of Dry Type Co2 Type Fire Extinguisher 4.5 Kg |
| 81 | SITC of ABC Type Fire Extinguisher IS 15683 4.0 Kg Having Deep drawn and CO2 MIG welded can construction ,Epoxy polyester powder external coating,Epoxy powder internal coating,Body Thickness 1.6 mm(Cease fire) |
| 82 | Supplying,Installation,Testing and Commissioning of Cubical Type Main LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars,Interlocking, Synchronising etc. as required as per the Following Description.(IP:42) type tested panel IS (61439)(Legrand/L&T/ABB/Schneider) |
| 83 | INCOMER |
| 84 | ACB 800 A F.P 50 Ka Icu=Ics=Icw=100% (01 Nos) |
| 85 | MCCB 500 Amps FP Icu=Ics=100% with BreakingCapacity 36 KA (01 Nos) |
| 86 | Indicating Lamps RYB (02 Set) |
| 87 | Voltmeter-0-500 Volts(02 Nos) |
| 88 | Ammeter(0-1000 A)(01 Nos) |
| 89 | Ammeter(0-600 A)(01 Nos) |
| 90 | Selector Switch (04 Nos) |
| 91 | Current Transformer 800/5 A 10 VA Burden,Class-1(01 sets) |
| 92 | Current Transformer 500/5 A 10 VA Burden,Class-1(01 sets) |
| 93 | Aluminium Busbar 1250 Amps FP |
| 94 | Aluminium Busbar 600 Amps FP |
| 95 | Digital Load Manager(02 Nos) |
| 96 | SP MCB 2 A(06Nos) |
| 97 | Motorised Changeover 630 A F.P With Aux-C 2000 Controller or Equivalent(01 Nos) |
| 98 | Indicating Lamps ON OFF TRIP( 02 Nos) |
| 99 | OUTGOINGS |
| 100 | Adj. TMR Based MCCB 500 Amps FP Icu=Ics=100% with Breaking Capacity 36 KA with Extendable ROH (02 Nos) |
| 101 | Adj. TMR Based MCCB 400 Amps FP Icu=Ics=100% with Breaking Capacity 36 KA with Extendable ROH (01 Nos) |
| 102 | Adj. TMR Based MCCB 320 Amps FP Icu=Ics=100% with Breaking Capacity 36 KA with Extendable ROH (02 Nos) |
| 103 | Adj. TMR Based MCCB 200 Amps FP Icu=Ics=100% with Breaking Capacity 36 KA with Extendable ROH (01 Nos) |
| 104 | Adj. TMR Based MCCB 100 Amps FP Icu=Ics=100% with BreakingCapacity 36 KA with Extendable ROH (06 Nos) |
| 105 | Adj. TMR Based MCCB 63 Amps FP Icu=Ics=100% with Breaking Capacity 36 KA with Extendable ROH (05 Nos) |
| 106 | Indicating Lamps ON OFF TRIP( 17 Nos) |
| 107 | Load Bearing Members to be made out of 2.0 mm CRCA Sheet. |
| 108 | Partitions to be made out of 1.6 mm CRCA Sheet |
| 109 | Gland Plates to be 3.0 mm Thick. |
| 110 | Supplying,Installation,Testing and Commissioning of Cubical Type UPS LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars,Interlocking etc. as required as per the Following Description.(IP:42) type tested panel IS (61439)(Legrand/L&T/ABB/Schneider) |
| 111 | INCOMER |
| 112 | Adj. TMR Based MCCB 100 Amps FP Icu=Ics=100% with Breaking Capacity 25 KA with Extendable ROH (01 Nos) |
| 113 | Indicating Lamps RYB (1 Set) |
| 114 | Voltmeter-0-500 Volts(1 Nos) |
| 115 | Ammeter(0-150 A)(1 Nos) |
| 116 | Selector Switch (2 Nos) |
| 117 | Current Transformer 100/5 A 10 VA Burden,Class-1(1 sets) |
| 118 | Aluminium Busbar 150 Amps FP |
| 119 | Digital Load Manager(1Nos) |
| 120 | SP MCB 2 A(03Nos) |
| 121 | Indicating Lamps ON OFF TRIP( 01 Nos) |
| 122 | OUTGOINGS |
| 123 | M.C.B F.P 63 A 10 Ka 'C' Curve (05 Nos) |
| 124 | M.C.B D.P 25 A 10 Ka 'C' Curve (10 Nos) |
| 125 | Load Bearing Members to be made out of 2.0 mm CRCA Sheet. |
| 126 | Partitions to be made out of 1.6 mm CRCA Sheet |
| 127 | Gland Plates to be 3.0 mm Thick. |
| 128 | Supplying,Installation,Testing and Commissioning of Cubical Type Floor Distribution Panel -1 Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars,Interlocking etc. as required as per the FollowingDescription.(IP:42) type tested panel IS (61439)(Legrand/L&T/ABB/Schneider)(Basement Floor) |
| 129 | INCOMER |
| 130 | Adj. TMR Based MCCB 200 Amps FP Icu=Ics=100% with Breaking Capacity 25 KA with Extendable ROH (01 Nos) |
| 131 | Indicating Lamps RYB (1 Set) |
| 132 | Voltmeter-0-500 Volts(1 Nos) |
| 133 | Ammeter(0-200 A)(1 Nos) |
| 134 | Selector Switch (2 Nos) |
| 135 | Current Transformer 200/5 A 10 VA Burden, Class-1(1 sets) |
| 136 | Aluminium Busbar 250 Amps FP |
| 137 | Digital Load Manager(1Nos) |
| 138 | SP MCB 2 A(03Nos) |
| 139 | Indicating Lamps ON OFF TRIP( 01 Nos) |
| 140 | OUTGOINGS |
| 141 | M.C.B F.P 63 A 10 Ka 'C' Curve (03 Nos) |
| 142 | M.C.B F.P 25 A 10 Ka 'C' Curve (02 Nos) |
| 143 | Adj. TMR Based MCCB 125 Amps FP Icu=Ics=100% with Breaking Capacity 25 KA with Extendable ROH (02 Nos) |
| 144 | Load Bearing Members to be made out of 2.0 mm CRCA Sheet. |
| 145 | Partitions to be made out of 1.6 mm CRCA Sheet |
| 146 | Gland Plates to be 3.0 mm Thick. |
| 147 | Supplying,Installation,Testing and Commissioning of Cubical Type Floor Distribution Panel-2 Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars,Interlocking etc. as required as per the FollowingDescription.(IP:42). type tested panel IS (61439)(Legrand/L&T/ABB/Schneider)Ground Floor/3rd Floor |
| 148 | INCOMER |
| 149 | Adj. TMR Based MCCB 100 Amps FP Icu=Ics=100% with Breaking Capacity 25 KA with Extendable ROH (01 Nos) |
| 150 | Indicating Lamps RYB (1 Set) |
| 151 | Voltmeter-0-500 Volts(1 Nos) |
| 152 | Ammeter(0-150 A)(1 Nos) |
| 153 | Selector Switch (2 Nos) |
| 154 | Current Transformer 100/5 A 10 VA Burden,Class-1 (1 sets) |
| 155 | Aluminium Busbar 150 Amps FP |
| 156 | Digital Load Manager(1Nos) |
| 157 | SP MCB 2 A(03Nos) |
| 158 | Indicating Lamps ON OFF TRIP( 01 Nos) |
| 159 | OUTGOINGS |
| 160 | M.C.B F.P 63 A 10 Ka 'C' Curve (03 Nos) |
| 161 | M.C.B F.P 40A 10 Ka 'C' Curve (02 Nos) |
| 162 | Load Bearing Members to be made out of 2.0 mm CRCA Sheet. |
| 163 | Partitions to be made out of 1.6 mm CRCA Sheet |
| 164 | Gland Plates to be 3.0 mm Thick. |
| 165 | Supplying,Installation,Testing and Commissioning of Cubical Type Floor Distribution Panel-3 Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars,Interlocking etc. as required as per the FollowingDescription.(IP:42) type tested panel IS (61439)(Legrand/L&T/ABB/Schneider)First Floor/2nd Floor |
| 166 | INCOMER |
| 167 | Adj. TMR Based MCCB 100 Amps FP Icu=Ics=100% with Breaking Capacity 25 KA with Extendable ROH (01 Nos) |
| 168 | Indicating Lamps RYB (1 Set) |
| 169 | Voltmeter-0-500 Volts(1 Nos) |
| 170 | Ammeter(0-150 A)(1 Nos) |
| 171 | Selector Switch (2 Nos) |
| 172 | Current Transformer 100/5 A 10 VA Burden,Class-1(1 sets) |
| 173 | Aluminium Busbar 150 Amps FP |
| 174 | Digital Load Manager(1Nos) |
| 175 | SP MCB 2 A(03Nos) |
| 176 | Indicating Lamps ON OFF TRIP( 01 Nos) |
| 177 | OUTGOINGS |
| 178 | M.C.B F.P 63 A 10 Ka 'C' Curve (04 Nos) |
| 179 | M.C.B F.P 40A 10 Ka 'C' Curve (02 Nos) |
| 180 | Load Bearing Members to be made out of 2.0 mm CRCA Sheet. |
| 181 | Partitions to be made out of 1.6 mm CRCA Sheet |
| 182 | Gland Plates to be 3.0 mm Thick. |
| 183 | Supply,installation with foundation as per approved Drawing 9 Mtr ST Pole. |
| 184 | Creation of Cement Concrete bed platform (8x8x6) feet with mesh fencing as required at site. |
| 185 | Supply, installation of G.I Structural Steel as per Standard Approved Drawing. |
| 186 | Supply,Installation and Commissioning of 11 KV Air Break Switch (200 Amps). |
| 187 | Supply,Installation of 11 KV L.A 10 ka (Station Class). |
| 188 | Supply,Installation of 11 KV HG Fuse Unit . |
| 189 | Supply,Installation of Disc Insulator. |
| 190 | Supply and Installation of B&S Hardware Fittings. |
| 191 | Supply and Installation of 100 Sq.mm Conductor. |
| 192 | Supply,Installation of 11 KV Pin Insulator. |
| 193 | Supply and Erection of 150 mm Dia. Heavy Class G.I Pipe for the Cable Protection. |
| 194 | Supply,Installation and Commissioning of 11 KV Trivector Meter with suitable size Out door Type 35/5 A C.T/ P.T's unit with connection complete job as required. |
| 195 | Supply, Installation Testing and commissioning of 630 KVA Copper Wound Transformer with the Following Specifications:- |
| 196 | Capacity in KVA : 630 Kva Level-II Transformer.Reference Standards Transformer design & testing IS:1180 Part 2 (2014) Loading: IS 6600 Oil:- IS 335Porcelain bushing :- IS 3347Tolerance on electrical parameters:- IS 2026 Duty :-Continuous dutyWindings:- EG Copper, Double wound Core :-CRGOType:- OutdoorInput Voltage:- 11 KV Output Voltage :-433 V Frequency :-50 Hz+/-3 Hz No. of Phases :-3Input configuration:- ( HV) Delta Output Configuration:- ( LV) Star Vector Group:- Dyn 11Cooling:- ONANMax. ambient temperature :-50º C Max. oil temperature rise:- 45º C Max. winding temperature rise :-55º CHV side High voltage withstand test :- 28 KV LV side High voltage withstand test :- 3 KV% impedance at 75º C :-4.5%Mounting of cooling radiators :- Direct mounting on tankTapping :-Off circuit tap changer shall be provided on HV winding in variation from +/-5% in steps of 2.5%. |
| 197 | Supplying and Laying of XLPE Insulated and PVC Sheathed Power Cable of 11KV/ 1.1 KV Grade of the following size direct in Ground including excavation,sand Cushioning,Protective Covering and Refilling the Trench as Required. |
| 198 | 3 C x 150 mm² 11 KV XLPE insulated Aluminum. conductor PVC outer sheathed armoured HT Cable with Earth (A2XFY with Earth HT Cable). |
| 199 | HT CABLE TERMINATION :- |
| 200 | The scope also includes after HT termination Electrical contractor has to perform the High voltage test as per IS, If test is Ok then proceed further. |
| 201 | Supply, Installation testing and commissioning of indoor type termination kit for 3 C x 150 mm² 11 KV XLPE insulated Aluminum. conductor PVC outer sheathed armoured HT Cable with Earth (A2XFY with Earth HT Cable).(Raychem make) |
| 202 | Supply, Installation testing and commissioning of outdoor type termination kit for 3 C x 150 mm² 11 KV XLPE insulated Aluminum. conductor PVC outer sheathed armoured HT Cable with Earth (A2XFY with Earth HT Cable).(Raychem make) |
| 203 | EARTHING OF SUB STATION |
| 204 | Supply, installation, testing and commissioning of 75 mm Cu. Pipe Filled with Crystalline conductive Mixture with Copper Strip of Size 40 mm x 6 mm of Length 2 mtr with Ecofriendly Backfill Compound 50 Kg. Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance value & Earth pit chamber (300mm x 300mm) with CI cover for the above as required complete Job. Makes:- Genus/Ashlok/ G-MAXX/ JMV/ Fastrack or equivalent makes |
| 205 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 206 | Supply, Installation, Testing and commissioning of 630 kVA Copper wound Automatic Servo Voltage Stabilizeras per the Specifications Below:- |
| 207 | EQUIPMET - SERVO VOLTAGE STABILIZERMAKE - GTB/A.E/Recons/Numeric/Fuji / AE or Equivalent.CAPACITY - 630 KVAInput Voltage: 260 V-460V (Phase to Phase)Output Voltage: 415 V + 2 %DESIGN & TESTING STANDARDS - IS:9815/IS 2026 COOLING - ONANWINDING - Copper FREQUENCY - 50 HzPHASE - 3 PhaseTYPE - UNBALANCED TYPE –Suitable for unbalanced input voltage and unbalanced load, OutdoorDUTY CYCLE - 100% ContinuousFIRST FILL OF OIL - As per IS:335/1983(Included) TEMERATURE RISE IN OIL - 50 degree C TEMPERATURE RISE IN WINDING - 55 degree C OVER LOAD CAPACITY - 100% for 1 minuteVOLTAGE DISPLAY - Voltmeters for input and outputCURRENT DISPLAY - Ammeter with CT's & Selector SwitchOPERATION - Auto/ ManualWHEEL - Unidirectional wheels EARTHING - 2 Earthing terminalsCABLE BOX & BUS BAR - Suitable size of cable box with 6 bus bars( 3 for input,3 for output & 1 for neutral)REGULATORS - Rolling contact typePROTECTIONS - Under voltage , over voltage , short circuit, overload protection through suitable capacity MCCBBY PASS ARRANGEMENT - Bypass arrangement shall be provided through suitable capacity by pass switch. |
| 208 | Supplying and Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size direct in groundin Existing DWC Pipe including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 209 | 3.5 C X 300 Sq.mm A2XFY |
| 210 | 3.5 C X 95 Sq.mm A2XFY |
| 211 | 3.5 C X 50 Sq.mm A2XFY |
| 212 | 3.5 C X 25 Sq.mm A2XFY |
| 213 | Supply and Making end Termination with Brass Compression Gland and Aluminium Lugs for the Following Sizes of PVC insulated and PVC Sheathed/XLPE Aluminium Conductor Cable of 1.1 KV Grade as Required (Comet) |
| 214 | 3½ X 300 sq. mm (70mm) |
| 215 | 3½ X 95 sq. mm (45mm) |
| 216 | 3½ X 50 sq. mm (35mm) |
| 217 | 3½ X 25 sq. mm (28mm) |
| 218 | Supply, installation, testing and commissioning of 75 mm Cu. Pipe Filled with Crystalline conductive Mixture with Copper Strip of Size 40 mm x 6 mm of Length 2 mtr with Ecofriendly Backfill Compound 50 Kg. Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance value & Earth pit chamber (300mm x 300mm) with CI cover for the above as required complete Job. Makes:- Genus/Ashlok/ G-MAXX/ JMV/ Fastrack or equivalent makes |
| 219 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 220 | Supply, Load, Transport to site, Receive & Unload at site, Store, Unpack, Erection, Testing & Commissioning of (CPCB Norms: 4) Diesel generator set of 320 kVA capacity (at 40o C Ambient temperature),with electronic governor as per specification. Also the cost shall include the freight & insurance. DG to be of prime / continuous duty application as per IS. Alternator to be provided with Class 'H' insulation & with cable termination box for LT Cables. Alternator to be provided with local isolator indoor/ outdoor type for maintenance purpose.DG set coupling to be with double bearing type, teethed gear coupling. The cost shall also include Engine Control Panel (Type: EGCP / Power Command Control) with RS 485 common port. DG sets shall be suitable for auto synchronizing with auto load sharing and remote monitoring & control arrangement compatible with the existing electrical system. DG Set with Alternator with Integral Acoustic Enclosure shall include the following components and accessories completea). Residential type Silencer.b). Anti‐Vibration Mounts (as required).c). Battery and Charger Dynamo (24V, 160AH minimum with leads)d). 990 Ltrs MS Fuel Tanks with float/ limit switch indicator for low & high fuel level. Required number of contacts to be provided for connecting the level limit switch for indication in DG Control Panel. |
| 221 | 320 KVA DG Set |
| 222 | Supply, installation, testing and commissioning of 75 mm Cu. Pipe Filled with Crystalline conductive Mixture with Copper Strip of Size 40 mm x 6 mm of Length 2 mtr with Ecofriendly Backfill Compound 50 Kg. Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance value & Earth pit chamber (300mm x 300mm) with CI cover for the above as required complete Job. Makes:- Genus/Ashlok/ G-MAXX/ JMV/ Fastrack or equivalent makes |
| 223 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 224 | Supply, transportation,Unloading , installation,testing & Commissioning of the following rating of UPS System(IGBT Based) including unloading,transportation from store to site ,errection instlattion,testing of UPS System including Battery and Battery rack errection & Installation under the supervision of supplier of UPS. Note:- Contractor has to submit the drawings & battery selection detail before procurement.Specification of UPS system shall be provided with Static by pass and Maintenance by pass facility with distribution board (Having Battries back up 48000 VAH) |
| 225 | 60 KVA UPS , Input 3 Phase 4 wire and output 3 phase 4 wire with15 min. Back up |
| 226 | Wiring for Circuit/Submain Wiring along with earth Wire with the following Sizes of FRLSPVC insulated copper conductor,single core Cable in surface/Recessed medium class PVC conduit as required. |
| 227 | 1X 70 sq. mm Multistrand Wire |
| 228 | Supply, installation, testing and commissioning of 75 mm Cu. Pipe Filled with Crystalline conductive Mixture with Copper Strip of Size 40 mm x 6 mm of Length 2 mtr with Ecofriendly Backfill Compound 50 Kg. Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance value & Earth pit chamber (300mm x 300mm) with CI cover for the above as required complete Job. Makes:- Genus/Ashlok/ G-MAXX/ JMV/ Fastrack or equivalent makes |
| 229 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 230 | Supply,installation with foundation as per approved Drawing 9 Mtr ST Pole. |
| 231 | Creation of Cement Concrete bed platform (8x8x6) feet with mesh fencing as required at site. |
| 232 | Supply, installation of G.I Structural Steel as per Standard Approved Drawing. |
| 233 | Supply,Installation and Commissioning of 11 KV Air Break Switch (200 Amps). |
| 234 | Supply,Installation of 11 KV L.A 10 ka (Station Class). |
| 235 | Supply,Installation of 11 KV HG Fuse Unit . |
| 236 | Supply and Installation of B&S Hardware Fittings. |
| 237 | Supply and Installation of 100 Sq.mm Conductor. |
| 238 | Supply,Installation of 11 KV Pin Insulator. |
| 239 | Supply and Erection of 150 mm Dia. Heavy Class G.I Pipe for the Cable Protection. |
| 240 | Dismenteling and Re-errection of existing 400 Kva transformer including providing of HT/LT Cable connection with acessories complete job. |
| 241 | Supplying and Laying of XLPE Insulated and PVC Sheathed Power Cable of 11KV/ 1.1 KV Grade of the following size direct in Ground including excavation, sand Cushioning, Protective Covering and Refilling the Trench as Required. |
| 242 | 3 C x 150 mm² 11 KV XLPE insulated Aluminum. conductor PVC outer sheathed armoured HT Cable with Earth (A2XFY with Earth HT Cable). |
| 243 | HT CABLE TERMINATION :- |
| 244 | The scope also includes after HT termination Electrical contractor has to perform the High voltage test as per IS, If test is Ok then proceed further. |
| 245 | Supply, Installation testing and commissioning cable ends termination kit for 3 C x 150 mm² 11 KV XLPE insulated Aluminum. conductor PVC outer sheathed armoured HT Cable with Earth (A2XFY with Earth HT Cable).(Raychem make) |
| 246 | EARTHING OF SUB STATION |
| 247 | Supply, installation, testing and commissioning of 75 mm Cu. Pipe Filled with Crystalline conductive Mixture with Copper Strip of Size 40 mm x 6 mm of Length 2 mtr with Ecofriendly Backfill Compound 50 Kg. Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance value & Earth pit chamber (300mm x 300mm) with CI cover for the above as required complete Job. Makes:- Genus/Ashlok/ G-MAXX/ JMV/ Fastrack or equivalent makes |
| 248 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 249 | Shifting of existing 250 KVA silent DG set . |
| 250 | Supply, installation, testing and commissioning of AMF Panel for 250 KVA silent DG Set with all acessories. . |
| 251 | Supply, installation, testing and commissioning of 75 mm Cu. Pipe Filled with Crystalline conductive Mixture with Copper Strip of Size 40 mm x 6 mm of Length 2 mtr with Ecofriendly Backfill Compound 50 Kg. Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance value & Earth pit chamber (300mm x 300mm) with CI cover for the above as required complete Job. Makes:- Genus/Ashlok/ G-MAXX/ JMV/ Fastrack or equivalent makes |
| 252 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 253 | Supplying,Installation,Testing and Commissioning of Cubical Type Distribution Panel Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars,Interlocking etc. as required as per the Following Description. (IP:56) Outdoor Type(Legrand/L&T/ABB/Schneider |
| 254 | INCOMER |
| 255 | MCCB 400 Amps FP Icu=Ics=100% with Breaking Capacity 50 KA (01 Nos) |
| 256 | Indicating Lamps RYB (1 Set) |
| 257 | Voltmeter-0-500 Volts(1 Nos) |
| 258 | Ammeter(0-200 A)(1 Nos) |
| 259 | Selector Switch (2 Nos) |
| 260 | Current Transformer 400/5 A 10 VA Burden,Class-1(1 sets) |
| 261 | Aluminium Busbar 500 Amps FP |
| 262 | OUTGOINGS |
| 263 | M.C.B F.P 250 A 36 Ka 'C' Curve (01 Nos) |
| 264 | M.C.B F.P 125 A 10 Ka 'C' Curve (03 Nos) |
| 265 | M.C.B F.P 63A 10 Ka 'C' Curve (02 Nos) |
| 266 | Load Bearing Members to be made out of 2.0 mm CRCA Sheet. |
| 267 | Partitions to be made out of 1.6 mm CRCA Sheet |
| 268 | Gland Plates to be 3.0 mm Thick. |
| 269 | Dismentelling , Shifting by way of mechanical means and Re-errection Testing and commissioning existing 400 kVA Copper wound Automatic Servo Voltage Stabilizeras.BY PASS ARRANGEMENT - Bypass arrangement shall be provided through suitable capacity by pass switch with all acessories. |
| 270 | Supply, installation, testing and commissioning of 75 mm Cu. Pipe Filled with Crystalline conductive Mixture with Copper Strip of Size 40 mm x 6 mm of Length 2 mtr with Ecofriendly Backfill Compound 50 Kg. Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance value & Earth pit chamber (300mm x 300mm) with CI cover for the above as required complete Job. Makes:- Genus/Ashlok/ G-MAXX/ JMV/ Fastrack or equivalent makes |
| 271 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail