| 1 | REPLACEMENT OF WORN OUT/DAMAGED EQUIPMENT BY NEW ONE. (INCLUDING ALL CIVIL WORKS & EARTHING OF EQUIPMENTS AS DIRECTED BY THE ENGINEER INCHARGE) |
| 2 | 33 KV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type)with allied accessories and heavy duty pad clamps. |
| 3 | 33kV C&R Panel along with Differential Relay, O/C, E/F relays, mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Smart meter -5 Amps with RS-485 port, DLMS Compliant with RS-485 port |
| 4 | 33 kV Isolator With Earthing Blade with allied accessories and pad clamps (36kV,1250A, Outdoor, 3 poles, 25 kA) with multi fingered female contacts with tin coated contacts, The isolator is to be provided a locking arrangement for un-authorized operation and auxilliary switch box (set of 3 Nos.). |
| 5 | 33 kV Isolator Without Earthing Blade with allied accessories and pad clamps (36kV,1250A, Outdoor, 3 poles, 25 kA) with multi fingered female contacts with tin coated contacts, The isolator is to be provided a locking arrangement for un-authorized operation and auxilliary switch box (set of 3 Nos.). |
| 6 | 33 kV Current Transformer (33 kV, 1Φ, Multi Ratio Multi Core, Outdoor) (1 No. per Φ) |
| 7 | 33 kV Voltage Transformer (33 kV/110 V, 1Φ, Multi-Core, Outdoor), (1No. per Φ) |
| 8 | 30 kV Lightening Arrestors (30 kV, 10kA, Station class, ZnO, Polymer) gap less |
| 9 | 33 kV Polymer Post Insulator 36kV,170kV Impulse, creepage distance 1224m |
| 10 | Supply, Laying, Testing & Commissioning of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI,FRLS as per relevant Standards |
| 11 | Supply, Laying, Testing & Commissioning of 04Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI,FRLS as per relevant Standards |
| 12 | Supply, Laying, Testing & Commissioning of 02 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI,FRLS as per relevant Standards |
| 13 | Lugs, Ferrules etc. |
| 14 | Providing & Fixing 200 mm² ACSR Conductor Panther |
| 15 | Providing & Fixing of 630A T-clamps suitable for 0.2 ACSR Conductor having 8 no,'s GI bolts of 19mm thick, as per relevant Standards |
| 16 | Providing & Fixing of Aluminium Tention Fittings of 0.2 ACSR Conductor having 8 no,'s GI bolts of 19mm thick, as per Relevant Standards |
| 17 | Providing & Fixing Polymeric composite Disc Insulator 36KV, Lightening Impulse 170kV Positive and 180kV Negative, creepage distance 900mm,min failing load 70kN |
| 18 | GI Earth wire 7/4.00 mm sq. |
| 19 | Providing & Fixing of GI flat for earthing 50x6mm with epoxy insulator along with clamps as per relevant Standards |
| 20 | 11 kV VCB Panel Board (12 kV, 1250A, 25 kA, Outdoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port (1+4)SET |
| 21 | 11kV, Gapless Surge Arrestor,9 KV ,10 KA ,LA with Polymer housing, Stn. Type (4/5/6 Sets) |
| 22 | 11 kV 3- Core XLPE 400 mm² armoured, FRLS |
| 23 | 11 kV 3-Core XLPE 185 mm² armoured, FRLS |
| 24 | 11 kV Indoor Heat Shrinkable Cable Termination Kits 400sqmm |
| 25 | 11 kV Outdoor Heat Shrinkable Cable Termination Kits 400sqmm |
| 26 | 11 kV Indoor Heat Shrinkable Cable Termination Kits |
| 27 | 11 kV Outdoor Heat Shrinkable Cable Termination Kits |
| 28 | 11 kV Isolator, double break,3-pole, 600Amp, horizental mounting Type, with Earth Switch. |
| 29 | 11 Mtr. Long Pole (ST-410 SP56) |
| 30 | 9 Mtr. Long Pole(ST-410 SP33) |
| 31 | Galvanised iron of sorts including CH Angle brases Clamps etc. |
| 32 | 100 KVA, 33/0.04 KV, 3-Phase Distribution Transformer with Bimetallic Terminal connectors Energy Level -2 (Copper wound) (1No. Spare) |
| 33 | 120 mm² PVC LT Cable 4 Core, armoured, FRLS |
| 34 | Cement bottoming 1:2:4 mix as per REC standards 0.5cum per pole |
| 35 | Earthing of 63 KVA Substation-Excavation of earth pit of dia 650 mm & depth 3000 mm installation of earthing pipe of 40 mm Nominal bore & 4 mm wall thickness & length 2.5 mtr long as per IS 1239 GI Strip[ for neutral earthing of size 75 mm x 10 mm & 50 mm x6 mm for connection of transformer body, G.O set & lightening arrestor as per IS 2629/85, GI Nuts & Bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover. |
| 36 | Supply ,Installation Testing and Commissioning of Earthing Complete by GI Pipe 40 mm or G.I Rod 20mm, 3.0 mtr long through welded with GI Strip 25x3 mm. |
| 37 | 11kV Bus Bar Fuse Set Out Door type for Auxilary Transformer |
| 38 | G.I Chainlink Fencing of 33kv yard by way of mass concreting in foundations and chainlink fencing of 6 ft height using G.I Angle of size 65x65x6mm and G.I Flat iron 50x6mm |
| 39 | RCC Cable Duct for laying of 11 KV XLPE Cable from Power transformer to Control Room and Control Room to O/G Structures as per REC Approved Standard Drawing. |
| 40 | a). Battery Bank 30 V,100 AH , of 15 No. cells of 2 V each, sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame retardant. b). 30V,100 AH , Float-Cum-Boost Charger With Full wave rectification for 220 V, 1Phase, 50 HZ AC Input Supply . |
| 41 | Distribution Panel (30 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, 12 No DP DC MCB (0-32A) including indication lamps and cables and other accessories |
| 42 | Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43. 200 Amps Switch Fuse disconnector for incoming supply and 5 No TPN MCB's (16-125 Amps ) and 5 No DP MCBs (0-32A), rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories |
| 43 | Providing of Bolt cutter of Taparia make BC-42 with allied accessories. |
| 44 | Providing of Rubber Mat 1mx2m 19mm thick |
| 45 | Providing of Fire Extingiusher Co₂/ABC Type of 4.5 kg capacity. |
| 46 | Providing of 3 Sand Bucket Fire Extingiusher with metallic stand andidentification plates |
| 47 | Providing of HV Detectors all voltages with fibre rod |
| 48 | Providing of Chrome vanadium forged Spanners of 10mm to 32mm sizering/u shaped. (set of 10 No.s) |
| 49 | Providing of Forged Adjustable wrench of 22mm and 32mm size |
| 50 | Providing of Screw drivers set flat cum star bit type dual end (set of 8 no.sof different sizes) |
| 51 | Providing of Nose Plier |
| 52 | Providing of Normal Plier |
| 53 | Providing of Sledge hammer of 2Kg with handle |
| 54 | SITC of AC Split type 1.5 Ton along with Stablizer etc complete. |
| 55 | Providing of HSS Cabron steel Hack saw with frame and set of 6 blade withtwo sided teeths |
| 56 | Providing of Measuring tape of 12 feet spring loaded |
| 57 | Providing of Precise 1 feet long bubble based water level |
| 58 | 600 watt hand drill with drill bits of HSS Hammer type |
| 59 | Providing of Tool Kit case plastic of Harry-kerry make of 2.5x1x1.5 feetdimensions with different chambers |
| 60 | Providing of Clamp meter with multi measuring parametersMarkoni/motwane/fluke make |
| 61 | Providing of Screw driver tester neon lamp based |
| 62 | Providing and fixing of industrial heavy duty chain block of 1 Ton capacitywith allied accessories complete |
| 63 | Providing of Chrome make socket set with ratchet and extension bars of10mm-32mm size sockets with allied accessories |
| 64 | Providing of Aluminum industrial ladder split 40 feet extension type with allied accessories |
| 65 | Executive Chair of reputed make. |
| 66 | Office Steel Chairs wih Armrest |
| 67 | Office Table of Standard Size with Sufficient Drawers |
| 68 | Office Almirah With Locker of reputed make |
| 69 | P/L of Red Oxide primer to existing rusted gantries structure, Mesh, mesh post etc in outer yard complete job. |
| 70 | Construction of Drain RCC for drainage of rain water. |
| 71 | Providing and Laying of Aluminium Paint 2- Coats in OD yard Gantry structures, Beams, LA, CT, PT , mesh , and mesh posts etc complete job. Please Enable Macros to View BoQ information |