| 1 | BoQ BOQ Represent (%) Percentage having Above/ Below ( + or - denomination) the Lump sum pre price inserted by MES BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority : GARRISON ENGINEER TEZPUR (NORTH) NAME OF WORK : REPAIR/MAINTENANCE OF LT PANELS INCLUDING SWITCH GEARS, VOLTAGE STABILIZERS, APFC PANELS AND ITS ALLIED WORKS AT SECTOR I TO XI AREA AT AGE CHARDUAR UNDER GE (N) TEZPUR Contract No : GE(N)/TEZ/ OF 2026-2027 (File No. 8281/E8) Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Description of items of works Item Code / Make Approx No. of quentity required. Units Pre Priced Rate (in. Rs.) as Defined by MES Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures to be entered by the Bidder Rs. P. Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT (In INR) TOTAL AMOUNT With Taxes TOTAL AMOUNT (In Words) |
| 2 | Excavation in trenches n.exc 1.5m wide and n.exc 1.5m in depth and getting out in soft/loose soil for foundation, laying of cables/ GI pipes etc. complete all as specified and directed. |
| 3 | Returning filling in including spreading, levelling, watering and well ramming in layers not exc 25cm complete all as specified and as directed. |
| 4 | Removing excavated material / soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 5 | M&L sand cushioning (dry) in trenches for protection of UG cables (below, above and around the cable laid in trenches) of 230mm spreding thickness and consolidated (punned) upto 180mm thickness, complete all as specified and directed. |
| 6 | Supply and laying well burnt bricks sub class 'B' in trenches for cable protection of U/G cable complete all as specified and directed. |
| 7 | Supply, laying, jointing & testing in trenches or passing through pipe, 1100 volts grade, XLPE insulated PVC bedded, galvanized steel strip or wire armoured LT electric power UG cables, heavy duty with stranded aluminium conductor of cross sectional area 25 sqmm 3.5 core with and including all fixing & connecting accessories such as Aluminium cable lugs, cable gland, nut, bolts, washer etc complete all as specified and directed. NOTE: Earthwork & Excavation, GI pipe, bricks for protection etc shall be measured and paid separately under relevant items of this BOQ. |
| 8 | Supply, laying, jointing & testing in trenches or passing through pipe, 1100 volts grade, XLPE insulated PVC bedded, galvanized steel strip or wire armoured LT electric power UG cables, heavy duty with stranded aluminium conductor of cross sectional area 35 sqmm 3.5 core with and including all fixing & connecting accessories such as Aluminium cable lugs, cable gland, nut, bolts, washer etc including taking up old unserviceable existing UG cable complete all as specified and directed. NOTE: Earthwork & Excavation, GI pipe, bricks for protection etc shall be measured and paid separately under relevant items of this BOQ. |
| 9 | Supply, laying, jointing & testing in trenches or passing through pipe, 1100 volts grade, XLPE insulated PVC bedded, galvanized steel strip or wire armoured LT electric power UG cables, heavy duty with stranded aluminium conductor of cross sectional area 50 sqmm 3.5 core with and including all fixing & connecting accessories such as Aluminium cable lugs, cable gland, nut, bolts, washer etc including taking up old unserviceable existing UG cable complete all as specified and directed. NOTE: Earthwork & Excavation, GI pipe, bricks for protection etc shall be measured and paid separately under relevant items of this BOQ. |
| 10 | Supply, laying, jointing & testing in trenches or passing through pipe, 1100 volts grade, XLPE insulated PVC bedded, galvanized steel strip or wire armoured LT electric power UG cables, heavy duty with stranded aluminium conductor of cross sectional area 70 sqmm 3.5 core with and including all fixing & connecting accessories such as Aluminium cable lugs, cable gland, nut, bolts, washer etc including taking up old unserviceable existing UG cable complete all as specified and directed. NOTE: Earthwork & Excavation, GI pipe, bricks for protection etc shall be measured and paid separately under relevant items of this BOQ. |
| 11 | Supply, laying, jointing & testing in trenches or passing through pipe, 1100 volts grade, XLPE insulated PVC bedded, galvanized steel strip or wire armoured LT electric power UG cables, heavy duty with stranded aluminium conductor of cross sectional area 95 sqmm 3.5 core with and including all fixing & connecting accessories such as Aluminium cable lugs, cable gland, nut, bolts, washer etc including taking up old unserviceable existing UG cable complete all as specified and directed. NOTE: Earthwork & Excavation, GI pipe, bricks for protection etc shall be measured and paid separately under relevant items of this BOQ. |
| 12 | Supply, laying, jointing & testing in trenches or passing through pipe, 1100 volts grade, XLPE insulated PVC bedded, galvanized steel strip or wire armoured LT electric power UG cables, heavy duty with stranded aluminium conductor of cross sectional area 150 sqmm 3.5 core with and including all fixing & connecting accessories such as Aluminium cable lugs, cable gland, nut, bolts, washer etc including taking up old unserviceable existing UG cable complete all as specified and directed. NOTE: Earthwork & Excavation, GI pipe, bricks for protection etc shall be measured and paid separately under relevant items of this BOQ. |
| 13 | Supply, laying, jointing & testing in trenches or passing through pipe, 1100 volts grade, XLPE insulated PVC bedded, galvanized steel strip or wire armoured LT electric power UG cables, heavy duty with stranded aluminium conductor of cross sectional area 185 sqmm 3.5 core with and including all fixing & connecting accessories such as Aluminium cable lugs, cable gland, nut, bolts, washer etc including taking up old unserviceable existing UG cable complete all as specified and directed. NOTE: Earthwork & Excavation, GI pipe, bricks for protection etc shall be measured and paid separately under relevant items of this BOQ. |
| 14 | M&L for GI pipe 50 mm bore, light grade with all fittings and fixtures (ISI Marked), laid in trenches, under road or fixing on wall/ pole /crossing drain /nallah etc. including taking up old unserviceable existing complete all as specified and directed. |
| 15 | M&L for GI pipe 80 mm bore, light grade with all fittings and fixtures (ISI Marked), laid in trenches, under road or fixing on wall/ pole /crossing drain /nallah etc. including taking up old unserviceable existing complete all as specified and directed. |
| 16 | M&L for GI pipe 100 mm bore, light grade with all fittings and fixtures (ISI Marked), laid in trenches, under road or fixing on wall/ pole /crossing drain /nallah etc. including taking up old unserviceable existing complete all as specified and directed. |
| 17 | Boring/Drilling (Horizontally) manually/mechanically under existing road (Maximum 10 M in width) suitable for inserting GI tubing upto 100 mm bore complete all as specified and directed. |
| 18 | M&L for painting of erected steel tubular swaged poles of LT over head line (Except embedded protion), 9 M long complete including all MS mounted/fixed with pole, earth protection & water pipe (if exists) with one coat of aluminium paint and providing 07 Nos bands/ straps with synthetic enamel paint (black and yellow 30 cm wide each) from top of plinth block and numbering of poles with black synthetic enamel paint on circular yellow background of complete all as specified and directed by Engnr-in-charge. |
| 19 | M&L danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps bolt and nuts of approved size, for HT 25x20 cm size including dismantling unserviceable one, complete all as specified and directed by Engnr-in-charge. |
| 20 | M&L for Cleaning of electric substation by uprooting unwanted grass, bushes and trimming of branches, surface dressing not exc.15cms deep in loose/soft soil to cut the grass,throne busehs and other any type of grass upto root level surrounding the installation and depositing the same at nearby garbage pit, refreshing and re-spreading aggregates inside the premises of sub station if any including cleaning of road/path/fencing etc, maintenance of transformer platform complete all as specified and directed by Engnr-in-charge. |
| 21 | M & L for writing letters and figures in white enamel of black Roman, Italic or Indian of 10 cm height including circular back ground with black enamel paint of two coats incl white circular border over steel/RCC surfaces of electric poles complete all as specified and directed by Engnr-in-charge. |
| 22 | S& F for GI earthing strip 25x4 mm with nut and bolts comoplete including taking down old unserviceable complete all as specified and directed by Engnr-in-charge. |
| 23 | S&F of GI Strip ISI marked of size 32 x6 mm complete with nuts, bolts and washers,buried in ground complete all as specified and directed by Engnr-in-charge. |
| 24 | Earthing complete with galvanised steel earth plate electrode of size 60cm x 60cm x 6.3 mm thick burried directly in ground( earth pit not less than 2.25 m deep below the normal groungnd level) with top edgee of the plate not less than 1.5m below normal GL connected to GI earth strip of size 25x4mm by means of bolts, nuts, check nuts washers of GI or steel all as shown in electrical plate No-5 of SSR Part I connected to machanery/equipments installed power house/sub station all as specified including testing on completion complete all as specified and directed by Engnr-in-charge.Note No-1 the unit rate shall also include for excavation earth work in any type of soil PCC (1:3:6) type C1 pit RCC 1:2:4 type B-1 cover reinforced with 8 mm dia CTD bars @ 150mm C/C both ways funnel with 15mm bore GI watering pipe 20mm dia bore GI protection pipe wire mesh and copper lugs complete in addition to item No 1(a) to (e) of preamble ( Notes) Under sub heading earthing specified on SI page NO-389 of SSR Part-II 2004. |
| 25 | Supply, install, testing & commissioning in replacement of LT busbar chamber of size (0.60x0.60x1.0)m CPRI approved, outdoor type, factory made fabircated to CRCA sheet of 3.15 mm thickness, angle iron of size 50X50X6mm thick of length 0.6 m from pcc, frame work and tee section (frame) of suitable size double door front/rear opening and locking arrangement, floor mounted on plateform of suitable size, Al bus bar chamber (enclosed) incl rust free spray painting with two coat of synthetic enamel paint over a coat of red oxide primer mounted on PCC blocks, fixed with grouted bold, nuts and washer and making complete including PCC foundation comprising of following accessories:- BUS-BAR & INTERNAL CONNECTIONS with a MCCB of 100 amp capacity ,4P with ICS=ICU=100%-1Nos. The bus-bars shall be made up of 04 Nos Aluminium 300 A rated not less than 60mmx10 mm, duly insulated with 1100 V grade standard colour coded PVC sleeves. |
| 26 | S & F in replacement Moulded Case Circuit Breaker (MCCB), 250Amps 25KA, 4P, 415V, 50 Hz, Adjustable Thermal & Fixed magnetic type Conforms to IS13947-2 & IEC-60947-2 Ics=100%Icu as per IEC 60947-II,Adjustable Overload setting Ir=[0.8 to 1.0] xIn, complete all as specified and directed by Engnr-in-charge. |
| 27 | S & F in replacement Moulded Case Circuit Breaker (MCCB), 200Amps 25KA, 4P, 415V, 50 Hz, Adjustable Thermal & Fixed magnetic type Conforms to IS13947-2 & IEC-60947-2 Ics=100%Icu as per IEC 60947-II,Adjustable Overload setting Ir=[0.8 to 1.0] xIn, complete all as specified and directed by Engnr-in-charge. |
| 28 | S & F in replacement Moulded Case Circuit Breaker (MCCB), 160Amps 25KA, 4P, 415V, 50 Hz, Adjustable Thermal & Fixed magnetic type Conforms to IS13947-2 & IEC-60947-2 Ics=100%Icu as per IEC 60947-II,Adjustable Overload setting Ir=[0.8 to 1.0] xIn, complete all as specified and directed by Engnr-in-charge. |
| 29 | Supply and fixing in replacement LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and directed by Engnr-in-charge. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |