| 1 | Excavation in trench not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth and not exceeding 1.5m for laying of LT under ground cables/GI pipes getting out as in soft /loose soil complete all as specified and directed. |
| 2 | Returing & filling in trench spreading ,leveling watering and well ramming in layers not exceeding 25 cm deep as in deep as in soil Complete all as specified and as directed by Engr-In-Charge. |
| 3 | Removing excavated material n.exc 50 mtrs and deposting where directed at a leve n.exc 1.5 mtrs above starting point as in soil Complete all as specified and as directed by Engr-In-Charge. |
| 4 | Supply & Fixing in replacement 20 mm dia CPVC brass elbow complete all as specified. |
| 5 | Supply & Fix in repairs Bib taps, cast copper alloy 15mm fancy type, chrominium plated screwed down,crewed high pressure with capstan head, screwed down for iron pipe complete all as specified. |
| 6 | Supply & laying CPVC pipes SDR 13.5 pipes & plain CPVC SDR 11 fittings walls/ceiling or laying in floors including taking down the old unserviceable GI pipe from trenches/walls/floors complete all as speicfied and directed for following sizes :- |
| 7 | All as per item No.06 above but with 20 mm dia |
| 8 | All as per item No.06 above but with 25 mm dia |
| 9 | All as per item No.06 above but with 40 mm dia |
| 10 | All as per item No.06 above but with50 mm dia |
| 11 | Supply & laying 20 mm GI pipe fittings Tubes, 'medium grade' galvanised with all fittings complete laid in trenches including taking down the old unserviceable GI pipe from trenches complete all as specified and directed for following sizes. |
| 12 | Supply & laying 40 mm GI pipe fittings Tubes, 'medium grade' galvanised with all fittings complete laid in trenches including taking down the old unserviceable GI pipe from trenches complete all as speicfied and directed for following sizes. |
| 13 | Supply & Fixing in repairs Gun metal gate valve 50mm with inner wheel head, screwed both ends in iron pipe and fixed in the following sizes |
| 14 | Supply & Fix in repairs Ball valves high pressure of PTMT with epoxy coated Aluminium rod & high density plastic ball screwed for iron pipe and fixed of following sizes as under :- |
| 15 | 15 mm dia with minimum weight 142 grams Complete all as specified and as directed by Engr-In-Charge. |
| 16 | 20 mm dia with minimum weight 210 grams Complete all as specified and as directed by Engr-In-Charge. |
| 17 | 25 mm dia with minimum weight 455 grams Complete all as specified and as directed by Engr-In-Charge. |
| 18 | Material & labour for scrubbing, cleaning thoroughly for removing the dirts,sediments,silts etc from the internal surfaces of UG sump (bottom & walls) by using brushes and bleaching powder and other cleaning materials as required including pumping arrangement for drain out the water and applying two coats of lime wash inside the wall surface of the tanks ,and two coats of colour applying(colour should be light yellow) on outside walls of sump including writing the words \\"military engineering services, tank capacity, date of cleaning and next due date\\" in capital letters of suitable size on outside visible surface of sump with synthetic enamel paint(white colour) over black background , and all the steel surfaces shall be painted with two coats of synthetic enamel paint(blue colour) after preparation of the surfaces at DAD pump house for the following sizes sump capacities as under :- |
| 19 | UG sump of capacity 1.65 lakhs gallon at DAD/DCA pump house area |
| 20 | UG sump of capacity 1 lakh gallon at RWH sump in DAD/DCA area |
| 21 | Demolition of existing old unserviceable brick masonary valve chamber including demolition of unserviceable M.S iron cover and frame and construction of new valve chamber 60x60x60 cm inner dimensions, brick masonary in CM 1:4 PCC base in 1:3:6 of 7.5 cm thick & plastering 15 cm thick in CM 1:4 in inner side/coping of all chamber fabrication of iron frame 40x40x6 mm size angle iron MS cover 3mm thick with hinges and locking arrangements duly painted including excavation and earth work complete all as specified and directed by Engr-in-charge. |
| 22 | Supply and fixing in repairs new cast iron foot valve 80 mm dia flanged ends swing type operation,as per IS-4038 with necessary bolt and nuts etc, including taking down old unserviceable foot valve complete all as directed by Engr-in-charge . Make kirloskar/kartar |
| 23 | Supply and fixing in repairs new cast iron foot valve 100 mm dia flanged ends swing type operation,as per IS-4038 with necessary bolt and nuts etc, including taking down old unserviceable foot valve complete all as directed by Engr-in-charge . Make kirloskar/kartar |
| 24 | S&F gland packing of 10mm dia |
| 25 | S&F gland packing of 12 mm dia |
| 26 | Taking out old unserviceable star delta starter, supply and fix star dalta fully automatic in sheet metal enclosure type MN with SSP features suitable for operation of pumping set connected with induction motor of 25 HP Capaity 3 phase 415 Volts 50Hz AC supply complete all as specified and directed. Make L&T |
| 27 | Taking out old unserviceable DOL starter, supply and fix DOL fully automatic in sheet metal enclosure type MN with SSP features suitable for operation of pumping set connected with induction motor of 15/12.5 HP Capaity 3 phase 415 Volts 50Hz AC supply complete all as specified and directed. Make L&T |
| 28 | Dismanling old unserviceable of MCB/MCCB any type any capacity |
| 29 | S&F in replacement of MCCB 3/4 pole as reqd 415 volt adjustable type of capacity 200 Amps with breaking capacity 36 KA Complete all as specified and as directed by Engr-In-Charge. |
| 30 | S&F in replacement of MCCB 3/4 pole as reqd 415 volt adjustable type of capacity 160 Amps with breaking capacity 25 KA Complete all as specified and as directed by Engr-In-Charge. |
| 31 | S&F in replacement of MCCB 3/4 pole as reqd 415 volt adjustable type of capacity 125 Amps with breaking capacity 16 KA Complete all as specified and as directed by Engr-In-Charge. |
| 32 | S&F in replacement of MCCB 3/4 pole 415 volt adjustable type of capacity 100 Amps with breaking capacity 16 KA Complete all as specified and as directed by Engr-In-Charge. |
| 33 | S&F in replacement of MCCB 3/4 pole as reqd 415 volt fixed type of capacity 63 Amps with breaking capacity 16 KA Complete all as specified and as directed by Engr-In-Charge. |
| 34 | S&F MCCB TP 100Amps capacity with rupturing capacity 15KA On the existing panel board including taking down old MCCB connecting complete all as directed Make -L&T |
| 35 | Supply and fixing in replacement NRV of size 100 mm including taking down old U/s NRV Complete all as specified and as directed by Engr-In-Charge. |
| 36 | M&L for scraping the rusted surfaces and peeled off paint of entire pumping set including pipe lines of various sizes along with base foundation plates applying metallic paint on surfaces and making the surface smooth and applying a coat of synthetic enamel paint of existing shade and writing the MES/SM number on the motor/pump/pipes/etc set all as directed. |
| 37 | M&L for scraping the rusted surfaces and peeled off paint of entire pumping set including pipe lines of various sizes along with base foundation plates applying metallic paint on surfaces and making the surface smooth and applying a coat of synthetic enamel paint of existing shade and writing the MES/SM number on the motor/pump/pipes/etc set all as directed. |
| 38 | Supply and fixing in replacement LT Panel board outdoor type fabricated out of 3.15mm thick CRCA Sheet steel factory made vermin proof duly painted with two coat of synthetic enamelled paint over a coat of red oxide primer or powder coated, double door, water proof dust and vermin proof hinged and lockable doors inlcuding rain protection cover on top and complete with interconnections, with copper wires, tapes, opening from both sides with cable entry from bottom, with cable alley and bus bar chamber, bonding to earth and painting, including angle iron frame of size minimum 40x40x6mm having 4 legs 0.60 mtr long including grouting in PCC 1:4:8, to the reqd depth all as specified and directed by Engineer-in-Charge. INCOMING(a) MCCB 315 amps 4 pole 50 KA adjustable thermal and fixed magnetic setting - 01 NoBusbar : - Aluminium busbar 3 phase 4 wire of 400 Amps supported with ebonite insulators -1setOUTGOING(b) MCCB 100 Amps 3 pole 16 KA with adjustable thermal and fixed magnetic setting – 08 Nos(c) Multifuction meter suitable to display voltage, current, frequency, power factor and other relavent parameters for three phase 4 wire 415 Volts System including three nos CTs of appropriate ratio – 01 No (d)LED indicator RYB-03 Nos |
| 39 | Dismentling of Feeder piller box of any type any size complete all as directed. |
| 40 | Supply and fixing in replacement LT Feeder pillar Panel board outdoor type fabricated out of 3.15mm thick CRCA Sheet steel factory made vermin proof duly painted with two coat of synthetic enamelled paint over a coat of red oxide primer or powder coated, double door, water proof dust and vermin proof hinged and lockable doors inlcuding rain protection cover on top and complete with interconnections, with copper wires, tapes, opening from both sides with cable entry from bottom,double door type with both side opening of doors with locking provision and gaskets at opening , with Aluminum bus bar chamber three phase four wire 415 Volts type of rating 400 Amps with provision for mounting of MCCB of rating upto 250 Amps, including Digital type Voltmeter and Ammeter, bonding to earth and painting, including angle iron frame of size minimum 40x40x6mm having 4 legs 0.60 mtr long including grouting in PCC 1:4:8, to the reqd depth including under mentioned Items all as specified and directed by Engineer-in-Charge. |
| 41 | Taking down carefully old unserviceable UG cable of any size from the trenches/wall/pole from site after affording credit including removal of brick cable cover Complete all as specified and as directed by Engr-In-Charge. |
| 42 | S & F of Onload front handle change over switch of capacity 100Amp 415 volt 50 Hz 4P with encloser, matching with existing including taking down of unserviceable change over complete all as specified and as directed by Engr-InCharge. Make- Indoasian/havells/Legrand |
| 43 | S & F of Onload front handle change over switch of capacity 200 Amp 415 volt 50 Hz 4P with encloser, matching with existing including taking down of unserviceable change over complete all as specified and as directed by Engr-InCharge. Make- Indoasian/havells/Legrand |
| 44 | Supply, laying dry river sand in trenches for cable cushioning all as specified in clause 19.75 of SSR part-I. Note :- Punned thickness of sand only will be measured & paid.Complete all as specified and as directed by Engr-In-Charge. |
| 45 | Supply, laying, testing and commissioning of LT under ground cable XLPE in repair insulated armoured, heavy duty, elelctric cable, size 10 Sqmm 2 Core with stranded aluminium conductor, 1100 Volts grade conforming to IS -7098 (Part-I) 1988 laid in trenches /walls/floors /ducts etc fixed with saddle and clamps or passing through pipes complete with cable ends connection with proper thimbles nut bolts washer Complete all as specified and as directed by Engr-In-Charge. |
| 46 | All as per item No.45 but of size 10 Sqmm x 4 core |
| 47 | All as per item No.45 but of size 16 Sqmm x 4 core |
| 48 | All as per item No.45 but of size 25 Sqmm x 4 core |
| 49 | All as per item No.45 but of size 50 Sqmm x 3.5 core |
| 50 | Supply and lay burnt bricks cable cover, class LV, type 1, flat, size 230mm x 115mm x 70mm in replacement of burnt bricks used as cable protection covers Complete all as specified and as directed by Engr-In-Charge. |
| 51 | Supply & Laying in repair GI tubing light grade of size 40 mm with necessary fittings as in cable protection laid in trenches/road/fixed on wall / floor including necessary clamps bolts and nuts complete all as specified and directed. |
| 52 | M&L preperation of surfaces of pole for painting of steel tubular pole, vertical with one coat of aluminium paint including painting black and white strip or as ordered by Engr-in-charge on poles up to 1.5 mtr high above coping level and numbering with writing letters or figures (Block), height not exceeding 30 cm high & letters and figures not exc 10 Nos complete all as directed. |
| 53 | M&L preperation of surfaces of pole for painting of PCC pole, vertical with one coat of aluminium paint including painting black and white strip or as ordered by Engr-in-charge on poles up to 1.5 mtr high above coping level and numbering with writing letters or figures (Block), height not exceeding 30 cm high & letters and figures not exc 10 Nos complete all as directed. |
| 54 | Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and as directed. |
| 55 | All as per No.54 but of 60watts |
| 56 | All as per No.54 but of 90watts |
| 57 | Supply and fixing LED flood light 210 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp.Complete all as specified and as directed by Engr-In-Charge. |
| 58 | Supply and fixing GI pipe bracket made of 40 mm bore light grade pipe made to shape of overall length of 1.2 mtr for fixing of security light fitting including MS clamps , nuts & bolts of required size Complete all as specified and as directed by Engr-In-Charge. |
| 59 | S&F in replacement of LED street light fittings driver for various capacity 45/60/90 watts Complete all as specified and as directed by Engr-In-Charge. |
| 60 | S&F inreplacement PVC conduit pipe from PVC junction boxes to street light bracket for protection of cable, fixing of clamp on PCC polesComplete all as specified and as directed by Engr-In-Charge. |
| 61 | S&F PVC 3 core copper cable 1.5 sqmm insulated for fixing of junction boxes to street light fittings Complete all as specified and as directed by Engr-In-Charge. |
| 62 | Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the earth plate at a depth of not less than 1.5 mtr below ground level connected to galvanized iron strip 25 x 4 mm as earthing lead by means of bolts, nuts and washers made out of GI/steel earth strip protected by GI light grade pipe of 40 mm dia and connecting to main panel board/switch board/control board all shown in electrical plate No 3 of SSR Pt I incl PCC chambers in 1:2:4 and RCC cover slab with 8mm dia MS bars reinforced at 10 cm center to center both ways incl earth work like excavation, returning filling back disposal etc complete. Please Enable Macros to View BoQ information |