| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GARRISON ENGINEER KOTA Name of Work: LOWERING, LIFTING AND REPAIRING OF PUMPING SETS, MOTOR STARTER PANEL AND CONNECTED WORKS AND REPAIR /MAINT OF SEWAGE PUMPS, MOTOR STARTER, PRESSURE PIPE AND CLEANING OF SEWAGE WELL AT MIL STN KOTA Contract No: GE/K- OF 2026-2027 Bidder Name : Schedule 'A' (PRICE SCHEDULE)(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Srl.No. Item Description Item Code / Make Approx Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT with Taxes TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | LOWERING, LIFTING AND REPAIRING OF PUMPING SETS, MOTOR STARTER PANEL AND CONNECTED WORKS |
| 3 | Supply and fixing in renewal of MV-1,AC-3, 3 pole power contactor of full load current rating 7.5 Amps, 415 volts, suitble for 5 HP, 3 phase induction motor, complete all as specified and directed |
| 4 | Supply and fixing in renewal of MV-1,AC-3, 3 pole power contactor of full load current rating 12 Amps, 415 volts, suitble for 7.5 HP, 3 phase induction motor, complete all as specified and directed |
| 5 | Supply and fixing in renewal of ML-1/1.5,AC-3, 3 pole power contactor of full load current rating 14 Amps, 415 volts, suitble for 10 HP, 3 phase induction motor, complete all as specified and directed |
| 6 | Supply and fixing in renewal of ML-1/1.5,AC-3, 3 pole power contactor of full load current rating 21 Amps, 415 volts, suitble for 15 HP, 3 phase induction motor, complete all as specified and directed |
| 7 | Supply and fixing in renewal of ML-2, AC-3, 3 pole power contactor of full load current rating 35 Amps, 415 volts, suitble for 20/25 HP, 3 phase induction motor, complete all as specified and directed |
| 8 | Supply and fixing in renewal of motor protection relay for capacity 5 HP to 7.5 HP motors, relay scale 4-11 Amps, with inbuilt earth fault protection having features such as overload, earth fault, locked rotor, single phasing, current unbalance, phase sequence reversal, under current, inbuilt CT's (1 A to 88 A), Trip indication, selectable trip class-10A, 10, 20 & 30 as per IEC 947-4-1, Aux. supply 240 V AC complete all as specified and directed. |
| 9 | Supply and fixing in renewal of motor protection relay for capacity 10 HP to 15 HP motors, relay scale 8-22 Amps, with inbuilt earth fault protection having features such as overload, earth fault, locked rotor, single phasing, current unbalance, phase sequence reversal, under current, inbuilt CT's (1 A to 88 A), Trip indication, selectable trip class-10A, 10, 20 & 30 as per IEC 947-4-1, Aux. supply 240 V AC complete all as specified and directed. |
| 10 | Supply and fixing in renewal of motor protection relay for capacity 20 HP to 25 HP motors, relay scale 16-44 Amps, with inbuilt earth fault protection having features such as overload, earth fault, locked rotor, single phasing, current unbalance, phase sequence reversal, under current, inbuilt CT's (1 A to 88 A), Trip indication, selectable trip class-10A, 10, 20 & 30 as per IEC 947-4-1, Aux. supply 240 V AC complete all as specified and directed. |
| 11 | Supply and fixing in renewal of single phase preventer complete all as specified and directed. |
| 12 | Supply and fixing in renewal of motor starter timer of suitable size and as per site requirement for pump motor of any capacities starters, complete all as specified and directed. |
| 13 | Materials and labour for servicing of existing LT panels/starter panels for tightning, cleaning with CRC solution, removing burn connection wire, replacement of cable end termination Al lugs as per existing sizes, replacement of u/s items, making necessary lociking arrenegment, weldings at hinges and proper conncting with earth GI wire/strips to nearest earth pit with nut/bolts complete all as specified and directed.Note: (i) Techinician shall be taking proper shutdown & prior intmation to JE IC/AGE permission.(ii) Minor spare i.e nuts bolts, washer, al lugs from XLPE LT cable (upto 180 Sqmm) , connecting copper wire up to single core 4 Sqmm of one ltr length is deemed to be included quoted rate.(iii) Necessary rust removal/carbon removal chemicla/CRC solution shall be provided by contractor.(iv) Incase of Major spare (MCCB, contactor, Relay etc) required for replacement shall be measured and paid under relevent item of this schedule. |
| 14 | Material and labour for taking out carefully the monoblock / open well submerged type electric motors induction type single/three phase, taken out from potable water sump, cutting down and removing the old burnt winding wire from the starter assembly of motor unit, rewinding the same with new super enameled copper winding wire as per existing size/gauge of wire, providing necessary insulation by varnishing and drying the same upto specific temperature of heat, replacing insulation paper sleeves with connecting insulating material, tapping and providing necessary connection to the motors assembly commissioning and testing the pumping set upto good working performance complete all as specified and directed for the following capacities : - |
| 15 | Capacity 0.5 HP, Single Phase |
| 16 | Capacity 1 HP, Single Phase |
| 17 | Capacity 3 HP, three phase, 415 Volts |
| 18 | Capacity 7.5 HP, three phase, 415 Volts |
| 19 | Capacity 10 HP, three phase, 415 Volts |
| 20 | Capacity 20 HP, three phase, 415 Volts |
| 21 | Material and labour for taking out carefully the Centrfugal type pump set with electric motors induction type three phase, from foundation, cutting down and removing the old burnt winding wire from the starter assembly of motor unit, rewinding the same with new super enameled copper winding wire as per existing size/gauge of wire, providing necessary insulation by varnishing and drying the same upto specific temperature of heat, replacing insulation paper sleeves with connecting insulating material, tapping and providing necessary connection to the motors assembly commissioning and testing the pumping set upto good working performance complete all as specified and directed for the following capacities : - |
| 22 | Capacity 05 HP, three phase, 415 Volts |
| 23 | Capacity 05 HP to 7.5 HP, three phase, 415 Volts |
| 24 | Capacity 7.5 HP to 12 HP, three phase, 415 Volts |
| 25 | Capacity 15 HP, three phase, 415 Volts |
| 26 | Capacity 20 HP, three phase, 415 Volts |
| 27 | Capacity 25 HP, three phase, 415 Volts |
| 28 | Material and labour for taking out carefully the Non Clog sewage pump set sebmersible type, from sewage wells, cutting down and removing the old burnt winding wire from the starter assembly of motor unit, rewinding the same with new super enameled copper winding wire as per existing size/gauge of wire, providing necessary insulation by varnishing and drying the same upto specific temperature of heat, replacing insulation paper sleeves with connecting insulating material, tapping and providing necessary connection to the motors assembly commissioning and testing the pumping set upto good working performance complete all as specified and directed for the following capacities : - |
| 29 | Capacity 05 HP, three phase, 415 Volts |
| 30 | Capacity 7.5 HP to 10 HP, three phase, 415 Volts |
| 31 | Capacity 15 HP, three phase, 415 Volts |
| 32 | Capacity 20 HP, three phase, 415 Volts |
| 33 | Lifting of submersible pump set any size and capacity from tube/bore well with all PVC pipe/column pipes 80/100 mm dia by chain pulley block for necessary repairs and lowering after necessary repairs/replacement of unserviceable parts, complete all as specified and directed. Note :- Replacement of spare parts shall be measured and paid for separately as supply only under respective items here-in-after. |
| 34 | Supply only rubber gaskets for flanged joint superior quality for 80 mm bore flanged pipe, complete all as specified and directed. |
| 35 | Supply only rubber gaskets for flanged joint superior quality for 50 mm bore flanged pipe complete all as specified and directed. |
| 36 | Supply only jointing kit for submersible cable of size 6 Sqmm / 10 Sqmm and 3 core, complete all as specified and directed. |
| 37 | Supply only flanged column pipes made out of MS galvanised steel pipes 2.5 Mtr long medium weight having MS galvanised flange duly welded on ends or with ends duly threaded as required at site, size 80mm bore including three supports of the each flange and one cut of flange for cable, complete all as specified and directed. |
| 38 | Supply only flanged column pipes made out of MS galvanised steel pipes 2.5 Mtr long medium weight having MS galvanised flange duly welded on ends or with ends duly threaded as required at site, size 100mm bore including three supports of the each flange and one cut of flange for cable, complete all as specified and directed. |
| 39 | Supply only nuts, bolts and washers of stainless steel of suitable size for coupling, complete all as specified and directed. |
| 40 | Supply only stainless steel end coupling socket, heavy duty, size 80mm bore and 300 mm long, complete all as specified and directed. |
| 41 | Supply only stainless steel end coupling socket, heavy duty, size 100mm bore and 300 mm long, complete all as specified and directed. |
| 42 | Supply and fixing in renewal of analog water pressure gauge (0-200 PSI) including necessary valves, reducers and nipple etc as per existing, complete all as specified and directed. |
| 43 | Supply and fixing in renewal of tube well cap made out of MS plate in two pieces with suitable fixing arrangement for 200 mm dia as per existing, complete all as specified and directed. |
| 44 | Supply, fixing, fabricating, tuning and metalling in renewal of gun metal bushes of submersible motor AC electric driven 3 phase, 415 volts of any size and capacity complete all as specified and directed. |
| 45 | Dismantling carefully the submersible motor AC electric driven 3 phase, 415 volts, cutting down and removing out the burnt winding wire, rewinding the same with new water proof PVC insulated copper wire of existing size/gauge, providing proper PVC insulation, connecting, tapping etc as required, assembling, re-fixing, lowering in bore well, commissioning and testing, complete upto good working performance, complete all as specified and directed for the following capacities: - |
| 46 | Capacity 5 HP to 7.5HP (RPM-2900) |
| 47 | Capacity 10 to 15 HP (RPM-2900) |
| 48 | S&F thrust bearing plate including coupling set suitable for submersible pump set AC electric driven for the following capacities, complete all as specified and directed for the following: - |
| 49 | Capacity 5 HP to 7.5HP (RPM-2900) |
| 50 | Capacity 10 to 15 HP(RPM-2900) |
| 51 | Dismantling carefully, taking out the water supply pumping set submersible AC electric driven RPM-2900, multistage, discharge capacity 06 LPS, head 60 mtr, coupled with 3 phase AC electric motor 415 volts 5 HP to 10 HP repairing with replacing the following items for (Make- Kirloskar/KSB) pumping sets & including lowering, testing and commissioning upto good working performance: - |
| 52 | Replacement of pump shaft |
| 53 | Gun Metal Impeller |
| 54 | Bowl bush Gun Metal |
| 55 | Stator assembly complete set |
| 56 | Rotor assembly complete |
| 57 | Materials and labour for disconnetion of exting 100/150mm bore DI connection and de-assembling header at Arjun Vihar, prepareing the necessary brick work for support , refixing at 1.2 mtr height from GL and changing the direction s of outlets ways direction 150mm dia butterfly valve and dead cap as per site requirement with necessary MS pipe of 150mm size with length of 1.5 mtr incl all bends, sockets, clanges , rubber gasket upto reconnecting the existing pipe line complete with reconstruction of damaged header support, re-assembling joints/valve after repair and testing complete all as specified and directed.Note: (i) Necessary 100 mm DI pipe & 150 mm MS pipe with welding/DI specials fittings end flanges eubber gasket shall be measured and paid seperatly under respective item of schedule. (ii) Direction of outlet ways from header shall be connect to existing 150mm DI lines at the height of 1.2 mtr from GL. |
| 58 | Attending complaints to all kinds of pump motors by qualified mechanic to check and test DOL/star-delta starter connections including settings of relay and timer, NO & NC contacts, main power connections, fixing of cable joints, fixing gland packing of approprate size to the pump motors, rectifying pump leakages by replacing flange, rubber packing and nut bolts of existing size and cleaning of pump motors to confirm the satisfactory running with renewal of following items. The cost of minor spares such as lugs of all size, wires, nut, bolts, washer, flanges, rubber packing, gland packing, cable joints etc are included in quoted rate by contractor complete all as specified and directed.Note :- Repair to defects after informing within 24 Hrs in case of failure noticed more than 24 Hrs recovery shall be effected @ Rs. 500 per Hrs beyond 24 Hrs. |
| 59 | M & L for lifting of centrifugal/open well submersible/VNC sewage pump set, anyize and capacity from pump house/sewage well with all column pipes 80/50 mm dia by chain pully block for necessary repairs and lowering the same after necessary repairs/replacement of unserviceable parts, complete all as specified and directed. Note :- Replacement of spare parts shall be measured and paid for separately as supply only under respective items here-in-after. |
| 60 | M&L for de-assembling header, repair of leakage in header of size 450 mm bore including welding/brazing etc as required at site, complete with reconstruction of damaged header supports, re-assembling joints/valves after repair and testing, complete all as specified and directed.Note :- Cost of spare parts such as flanges, nut bolts, washers, sockets etc shall be included in the quoted rate. |
| 61 | M & L for spray painting of pipe line incoming and outgoing (rising/ delivery) with two coats of synthetic enamel paint over & including a coat of primer after complete removal of existing treatment from the pipe lines, including writing name/capacity with black synthetic enamel paint on pipe, complete all as specified and directed. |
| 62 | M & L for spray painting of pump and motor sets of capacity upto 50 HP with two coats of synthetic enamel paint over & including a coat of red oxide primer after complete removal of existing treatment, including writing name/capacity of pump with black synthetic enamel paint, complete all as specified and directed. |
| 63 | Supply, install, testing and commssioning of horizontal axially split casing type pump of series UP80/38 bare shaft pump , CI impeller, gland packed. The pump should have minimum 35 mtr head and 1300 ltrs/min flow rate. Pump shall be duly coupled with existing induction motor including all accessories. The pump shall be fitted with 100mm bore pipe at suction side and 80mm bore on delivery side. The materials shall confirms to IS 210 (1978) Gr FG 260 the installation and commissioning shall be done by OEM only including dismantling old unsv pump from the foundation and deposite to MES store with 20 HP induction motor complete all as specified and directed. |
| 64 | Supply and fixing in renewal of PVC insulated and sheathed 1100 volts grade flat type submersible cable, three core, multi stranded copper conductor of following sizes, complete all as specified and directed :- |
| 65 | 6 Sqmm |
| 66 | 10 Sqmm |
| 67 | Supply and fixing in renewal of star delta Starter with sheet metal enclosure outdoor type of suitable size for 15 HP to 20 HP capacities motor in existing location including making electric connections with PVC insulated 1100 volts grade single core multi stranded copper conductor cable, complete all as specified & directed. |
| 68 | Supply and fixing in renewal of DOL Starter with sheet metal enclosure of suitable size for 3 HP to 5 HP capacity motor in existing location including making electric connections with PVC insulated 1100 volts grade single core multi stranded copper conductor cable, complete all as specified & directed. |
| 69 | Supply and installed, connecting and testing of sluice valve, class PN 1.6 double flanged CI body, wheel and brass spindle and nuts, non rising type, IS-14846 ISI marked including jointing materials such as rubber gasket, carbon steel nuts, bolts and washers etc & including taking down old unserviceable existing sluice valve complete all as specified and directed of the following sizes :-150mm bore |
| 70 | 100 mm bore |
| 71 | Supply and installing, connecting and testing of cast iron non return valve, double flanged/built weld end bolted cover, swing check type, ISI marked, designed as per BS-1868, pressure rating PN 10, including jointing materials such as rubber gasket, carbon steel nuts, bolts and washers etc & including taking down old unserviceable existing non return valve complete all as specified and directed of the following sizes :-150mm bore |
| 72 | 100 mm bore |
| 73 | Supply, fixing, testing and commssioning of 7.5 HP, Non clog vertical submersible pumps through OEM, head range not less than 21m, discharge-1900-2000 LPM with chrome steel impeller and cutter, non-clog to pass 35-40 mm size particles including suitable for star delta connection with and including fully automatic star delta starter suitable for pump with accessories like contractor, protection relay supply, installation with guide rail and lifting chain, cables, Earthing, testing& including taking down old unserviceable existing pump & deposit to MES store, complete all as specified and directed. |
| 74 | Supply, fixing, testing and commssioning of 15 HP, Non clog vertical submersible pumps through OEM, head range 21m, discharge-1900-2000 LPM with chrome steel impeller and cutter, non-clog to pass 35-40 mm size particles including suitable for star delta connection with and including fully automatic star delta starter suitable for pump with accessories like contractor, protection relay supply, installation with guide rail and lifting chain, cables, Earthing, testing& including taking down old unserviceable existing pump & deposit to MES store, complete all as specified and directed.Make: KIrloskar Cat No. 11000CW4P or techno commercially equivalent Makes as specified in PS. |
| 75 | Supply & laying/fixing, connecting, jointing and testing ductile iron pressure pipe for water mains,centrifugally cast with spigot and socket ends (for push on joints) class K-7, in any length in trenches, under floor, under road and including making and fixing suitable size clamps at place of CI/DI line joint, complete all as specified and directed for following bore pipes:-100 mm bore |
| 76 | 150 mm boreNote for item 53.00 & 53.01: (i) Rubber tyton or run lead joints of pipes shall be measured and paid separately under respective items here-in-after.(ii) Cast iron/ DI fittings/specials shall be measured and paid separately under respective items here-in-after. |
| 77 | M&L Ductile iron fittings of such as i.e. bends (any type, radius and angle), Tapers any type, (straight, bend, increasing , decreasing or double socket etc.) Tee pieces single branch, 'Y' junction, double branch, cross (all sockets or socket and spigot and/ or flanged ends as directed) including collars, caps and plugs, up to 150 mm bore of pipes, ISI Marked, complete all as specified and directed. |
| 78 | Supply and installed, connecting and testing of butterfly valve, class PN 1.0 double flanged, long type, lever operated, ISI marked (IS-13095:1991, reaffirmed 2003) & including jointing materials such as rubber gasket, carbon steel nuts, bolts and washers etc, fixed to water mains & including taking down old unserviceable existing butterfly valve complete all as specified and directed of the following sizes :-150mm bore |
| 79 | 100 mm bore |
| 80 | M & L in renewal of pressure switch of booster Pump of pressure ranges 2 to 14 Bar, operating pressure 17 bar (max), IP 30 rating complete all as specified and directed. |
| 81 | Supply and fix 0.5 HP to 1 HP booster pump of Head range 6-24 mtr, made up of casr iron, 220V, 50Hz, impeller material brass, flow rate 633 LPM, copper winding and including taking down of old unsv booster pump and deposit in MES store, complete all as specified and directed. |
| 82 | M & L for spray painting of pipe line incoming and outgoing (rising/ delivery) with two coats of synthetic enamel paint over & including a coat of primer after complete removal of existing treatment from the pipe lines, including writing name/capacity with black synthetic enamel paint on pipe, complete all as specified and directed. |
| 83 | Supply & laying/fixing in renewal of UPVC column pipe rating SCH-40 with & including all fitting, laid in bore well, fixing to pump motor suction and delivery side, complete all as specified and directed of following bore of pipes: -75/80 mm bore |
| 84 | Excavation in trenches not exc 1.5 m wide and not exc 1.5 m deep for foundation etc or for shafts, column footings or for laying cables/pipes etc not exc 10 Sqm on plan and getting out in soft/loose soil, complete all as specified and directed. |
| 85 | Returning filling in soil including spreading, leveling, watering and well ramming in layers not exc 25 cm thick, complete all as specified and directed. |
| 86 | Removal of excavated surplus soil to distance not exc 50 Mtr and deposting where directed at a level not exc 1.5 Mtr above the starting point complete all as specified and directed. |
| 87 | M & L for cement concrete in foundation, filling and mass concrete in M7.5(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed. |
| 88 | M & L for cement concrete M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate as in floor 150 mm thick finished even and fair complete all as specified and as directed. |
| 89 | M & L for C- channel for grade Fe-290 (Gde E- 165 ) fixing as in foundation for mounting pump motor set, channel shall be of size minimum 75x40x4.8 mm including nuts bolts as required complete all as specified and directed |
| 90 | Supply only of start & stop push button Green/ Red in colour complete all as specified and as directed. |
| 91 | M&L for Earthing with galvanized steel earth plate electrode of size 600 mm x 600mm x 6.0 mm, buried directly in ground (earth plate not less than 2.25 Mtr below normal ground level) connected to galvanized earth strip of 25x4 mm dia by means of bolts, buts, check nuts and washers of galvanized iron on steel including 50 mm bore light grade GI tubing for protection of earth strip, MS sheet metal funnel with wire mesh, watering pipe medium grade 20 mm bore, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC 1:3:6 type 75 mm thick precast RCC (1:2:4) type B1 pit cover reinfored with 8 mm dia deformed bar and suitable handle made of 10 mm dia round bar including GI earth strip of 32x6 mm size for extension of earth lead and necessary excavation, earth work, in soft/loose soil and disposal of spolis to a distance not exc 50 Mtr and necessary connection and testing complete all as shown in electrical plate No. 3 and including dismantling of old u/s earthing complete all as specified and directed.complete all as specified and directed. Notes: - (a) Irrespective of whatever is shown in plate No 3 of SSR, earth pit shall be casted in PCC (1:3:6) type C-1 and precast cover of RCC (1:2:4) type B-1 with suitable handle. (b) Item includes the cost of GI pipe for protection of earth wire and earth lead strip upto 7.5 m. |
| 92 | Supply only chlorine dioxide chemical (SCS-10K, CLO2) required to achieve desired parameters of trated water and required spares for operation of plant at least one month requirrement of the metarials shall be kept at site at a time etc complete all as specified and directed |
| 93 | M&L for display boards made with of ABS acrilic materials of sizes 5'x3'x0.5' (LxBxT) with containg blue back ground with white in colour of capital letters 50mm heights with showing layout of pump houses details as given by Engr-in-Charge and fixing at wall of various pumps/motors/sewages pumps/bore wells along with fixing arrengment complete all as specified and directed.Notes: - (a) Display details/drgs/board list shall be approved before finalise the printing at Engr-in-Charge. |
| 94 | M&L for Cleaning and desilting the sewage well of dia 3 mtr to 7 mtr and depth up to 10.5 mtr de-watering the complete well, removing out the deposited sludge, soil & other material including bailing/pumping out muddy water from the well by manually or by providing pump sets from bottom level of well and cleaning and removing the sludge to a distance not exc 50 mtr and depositing etc. complete all as specified and directed.Notes :- The rate quoted by tenderer shall be deemed to be inclusive of equipments / all necessary arrangements required for cleaning of sewage well and supporting items. |
| 95 | M&L for Lifting of VNC sewage pump set, any size and capacity of 7.5 HP from sewage well with all PVC pipe/column pipes 80/50 mm dia by chain pulley block for necessary repairs and lowering the same after necessary repairs/replacement of unserviceable parts, complete all as specified and directed. Note :- The rate of spare parts is deemed to be included under quoted rate. |
| 96 | M&L for Lifting of VNC sewage pump set, any size and capacity of 10 HP to 15 HP from sewage well with all PVC pipe/column pipes 80/50 mm dia by chain pulley block for necessary repairs and lowering the same after necessary repairs/replacement of unserviceable parts, complete all as specified and directed. Note :- The rate of spare parts is deemed to be included under quoted rate. |
| 97 | Material and labour for cleaning of surrounding area of sewage treatment plant complete upto fencing level and one meter outside of the fencing by surface excavation upto 10 CM average depth including removing shrubs, grass, implant, small bushes, branches of tree and other unwanted materials / stones etc and levelling complete for every months of contract etc. including spray of herbicide chemical on grass at all round area of STP, complete all as specified and directed.Note :- (a) The cost of herbicide chemical for grass, petrol to run grass cutting machine and other T&P for cutting of grass/branches of tree deemed to be included in the quoted rate.(b) In case of failure noticed more than 07 days, recovery shall be effected @ Rs. 500/- per day beyond 07 Days. |
| 98 | Supply and fix in renewal of MV-1, AC-3, 3 pole power contactor of full load current rating 7.5 Amps, 415 volts, suitable for 5 HP, 3 phase induction motor complete all as specified and directed. |
| 99 | Supply and fix in renewal of motor protection relay for 15 to 20 HP motors, relay scale 10-32 Amps, with inbuilt earth fault protection having features such as Overload, Earth Fault, Locked Rotor, single Phasing, Current Unbalance, Phase Sequence Reversal, Under Current, Inbuilt CT’s (1 A to 88 A), Trip indication, Selectable trip class - 10A, 10, 20 and 30 as per IEC 947-4-1, Aux. Supply: 240 V AC etc. complete all as specified and directed. |
| 100 | Taking up cast iron water mains/DI (including all fittings), 100 mm nominal size, with spigot and socket ends and lead joints including burning out joints and recovering lead complete all as specified and as directed. |
| 101 | Taking up cast iron water mains/DI (including all fittings), 150 mm nominal size, with spigot and socket ends and lead joints including burning out joints and recovering lead complete all as specified and as directed. |
| 102 | M & L for rubber gasket joints (push on joints) for spigot/socket end ductile iron water mains/ductile iron specials complete for 100 mm nominal dia complete all as specified and as directed. |
| 103 | M & L for rubber gasket joints (push on joints) for spigot/socket end ductile iron water mains/ductile iron specials complete for 150 mm nominal dia complete all as specified and as directed. |
| 104 | Supply & fixing in renewal of heavy duty ball type MS foot valve 100 mm bore, ISI marked, flanged type with SS mesh PN 10.0 swing type operation with rubber seat as per IS 4038, including jointing material such as rubber/fibre board gasket, nuts, bolts and twin washers, complete all as specified and directed. |
| 105 | Supply & fixing in renewal of heavy duty construction this 12mm x 20m length twisted rope, made from high strength materials, making it suitable for marine, industrial and outdoor application for anchoring and supporting to existing sewage pumps & openwell submersible pumps at various UG sumps, sewage wellalongwith necessary tieing clamps complete all as specified and directed. |
| 106 | Supply & laying in renewal synthetic rubber insulated mats 2mm thick for voltage upto 3.3 Kv for eletric as per IS 15652-2006 (superseding IS 5424)suitable for electric shock safety of sizes 2m x 1m complete all as specified and directed. |
| 107 | M&L for pin-up boards with aluminum frame at outside and blue in background of velvet cloth surfaces for easy pinning of duty rosters of size 900cm x 600cm including hanging arrangement at all pump houses complete all as specified and directed. |
| 108 | Supply and fixing in renewal of star delta Starter with sheet metal enclosure outdoor type of suitable size for 10 HP capacities motor in existing location including making electric connections with PVC insulated 1100 volts grade single core multi stranded copper conductor cable, complete all as specified & directed. |
| 109 | S & F of fire extinguiser ball of capacity 1.3 Kg including iron stand for fixing at near LT panels inside the E/M installation complete all as specified & directed. |
| 110 | Supply, installing, testing and commissioning, factory made and tested (incl CPRI type test certified), LT feeder pillar box (KIOSK) of appropriate dimensions (as per Indian Electricity rules) to accommodate following components, indoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated Copper bus bars 200 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front & rear opening type, with aprons for cable entry, with double door shutter and locking arrangement, internal wiring with PVC insulated, multistranded copper conductor, FRLSH cables, IS-694 marked of adequate size but not less than 4 sqmm and including taking down of old unsv existing Panel complete all as specified and directed. The scope of work includes the following :-Incoming :- (a) Aluminium bus bar of rating 200 Amps for four pole including PVC heat shrink sleeves (RYB & N ) : 01 Set (b) MCCB four pole 100 Amp ('C' Curve), 415 Volts, rupturing capacity- 26 kA, 415 Volts Adjustable Thermal & Fixed Magnetic type- 01 No (c) Digital multi funtion meter -01 No(d) Indicating light red 220 V AC-01 No(e) Indicating light yellow 220 V AC-01 No(f) Indicating light green 220 V AC-01 No(g) Protection MCB 6A SP -03 Nos(h) CT 100/5A - 03 Nos |
| 111 | Star delta connection starter upto 5HP x 02 NosOutgoing :- (a) MCB three Pole 32 Amps ('C' Curve), rupturing capacity- 10 kA, - 03 Nos (b) Power contactor MV1 three pole - 03 Nos(c) Bimetallic over load relay 6-10 Amp - 03 Nos(d) Aux Block 03 Nos(e) Push button start/stop 220 V - 02 Nos(f) Auto manual selector switch - 01 No(g) Indicating light ON/OFF/TRIP 220 V - 03 Nos(h) Control MCB SP 6A, 10 Ka - 03 nos(j) Single phase preventor - 03 Nos Note :Necessary approval of drawings of LT feeder pillars to be taken from GE before placing order by the contractor. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |