| 1 | Supply, Installation, testing and commissioning of retrofit emission control device for diesel generator of any make / vintage / category of the following capacities :-Application:- Reduce particulate matter (PM 2.5), Carbon Monoxide and Hydrocarbons emitted from Diesel Engine.Technology/Type:- ESP (Electrostatic Precipitator), Wet Scrubbing, Diesel Oxides Catalyst Guaranteed specified Particulate matter (PM 2.5) Carbon Monoxide, Hydrocarbon reduction efficiency (Min) 70% for all DG sets.Scope of Installation :-a) Installation of Emission Control Retrofit Device when offered by the vendor is inclusive in the scope of supply and shall be done by the seller/ OEM. b) Construction of suitable earthing station and necessary connections shall be done by the seller.c) Warranty/Service :- 12 monthsd) Number of preventive maintenance visits offered during warranty period will be 2 visits. it will cater filter cleaning and replacement of filter, pressure and temperature sensor, display unit fitted for RECD if necessiated. |
| 2 | Back Pressure due to the Emission Control retrofit device :- Maximum back pressure exerted by the Emission Control retrofit device at max prescribed load by DG OEM(as per the capacity of the DG set).TEST REPORTSCertification :- The device must be 'Type Approved' in accordance with the Central Pollution Control Board's System and Procedure for Emission Compliance Testing of Retro-fit Emission Control Devices (RECD) for Diesel Power Generating Set Engines, dated 01/02/2022, as well as provide a type testing certificate for all KVA families of required generators.Adhering to this, RECD to be ‘Type Tested’ for an equivalent kVA family as per the System and Procedure from any one of the four Central Pollution Control Board, Govt, of India, recognized/approved test agencies / laboratories as given below: (a) Automotive Research Association of India (ARAI, Pune)(b) International Centre for Automotive Testing (ICAT, Manesar)(c) Indian Institute of Petroleum (IIP, Dehradun)(d) Vehicle Research Development Establishment (VRDE, Ahmednagar): |
| 3 | General Technical Requirments(GTR)/Commissioning:-a) Emission control retrofit device shall be complete with safety precution to ensure no damage should be done to the DG set operations under anycircumstance.The Emission control retrofit device should be closely coupled with the DG exhaust to ensure 100% of the exhaust passes through the Emission control retrofit device.b) Anti vibration mountings shall be provided for complete Emission control retrofit device in case of flaxible coupling with the DG exhaust c) Emission control retrofit device should have protection against under voltage,over voltage,under frequency ,over frequency,lowbattery voltage,over current,earth fault,short circuit ,phase sequence change etcd) The Emission control retrofit device shall be with corrosion resistive and HR paint.e) Unloading and placement of the Emission control retrofit device at the time of delivery is in the scope of work. f) The contractor shall provide the trail of the Emission control retrofit device at least two hours on site. |
| 4 | g) All exhaust piping, any extra work, distribution board shall be provided by the contractor in the scope of work. h) contractor shall provide the pollution test report of DG set before and after installing the RECD. Make : CPCB / ARAI / ICAT certified manufacturer of RECD: Cummins Technologies india Pvt Ltd / Chakr innovation Pvt Ltd / JBDS Power Project / Platino Automotive Pvt Ltd / Pi Green Innovation Pvt Ltd and equivalent. |
| 5 | 250 KVA capacity DG Set. |
| 6 | 200 KVA capacity DG Set. |
| 7 | 160 KVA capacity DG Set. |
| 8 | 125 KVA capacity DG Set. |
| 9 | 82.5 KVA capacity DG Set. |
| 10 | 62.5 KVA capacity DG Set. |
| 11 | Supply, install test and commissioning of AMF Panels suitable to 58.5 KVA DG Sets with connected acessories as follows:- Switch Gear:Incommer:(a) MCCBs Thermal 100A, FP, 36 KA - 2 Nos (with Spreader Links)(b) Contactor Assembly(2 Nos) - 100A (c) Aluminium Bus Bar as per contractor Rating(d) Electronics Time Delay timer 0-30 SEC(2 Nos)Metering:(a) MFM with Inbuilt selector switch, 3Ph, Acc. CL: 1, Aux Supply: 80‐300V AC, Size:96X96 Cat no: WL440510OOOO(b) Ampere meter with Inbuilt selector switch, 3Ph, Acc. CL: 1, Aux Supply: 80‐300V AC, Size:96X96 with CT ratio AR Cat no: WL131010OOOO |
| 12 | Indications:(a) Red LED Indicator 22.5 mm, Voltage: 240V AC (2 Nos)(b) Yellow LED Indicator 22.5 mm, Voltage: 240V AC (2 Nos)(c) Blue LED Indicator 22.5 mm, Voltage: 240V AC (2 Nos)(d) Green LED Indicator 22.5 mm, Voltage: 240V AC (2 Nos)(e) Amber LED Indicator 22.5 mm, Voltage: 240V AC (2 Nos)Auxiliaries:(a) Microprocessor microcontroller-based DGC-6D automatic generator start with Emergency stop (1 Nos)(b) SMPS 10 A AC INPUT: 110/220 V, DC OUTPUT: 24V Battery Charger with metering MCB 6A, SP, 10KA -10 Nos (1 Nos)(c) AC Electromagnetic relay 5 A ,Coil 240V (2Nos)(d) DC Electromagnetic relay 5 A ,Coil 240V (2 Nos)(e) Auto/Manual Selector Switch (1 Nos)(f) Push Button ON and OFF with NO & NC elements.(2 Nos)(g) VMR Meter, Emergency Stopper, Complete connecting wiring Please Enable Macros to View BoQ information |