| 1 | Dismantling the existing pole above 6 m height with brackets, clamps, insulators, stay from the c.c. foundation and making the site clear by refilling the pits with excavated materials and bringing it to the ground level |
| 2 | Supplying and erecting G.I. pipe pole ‘B’ class 80 mm dia 6 m long with polecap, base plate in provided foundation as per specification (Make :As per ISI Standard specification, As approved sample as per UMC Specification ) |
| 3 | Making Cement concrete foundation including excavation (45 x 45 x 120)cmdeep in 1:3:6 cement concrete, 20 to 25 mm stone metal, (45 x 45 x 45)cm/ 45cmdia. x 45cm height plinth duly plastered, with necessary curing and finishingcomplete. (for 6m pole). Make: As per PWD specification |
| 4 | Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or20 mm dia. G.I. Rod complete with all accessories of GI materials & recordingthe results as per specification (Make :As per ISI Standard specification) |
| 5 | Supplying and erecting integrated LED street light fitting 45W IP65 & IK08class having single piece pressure die-cast aluminium housing with military green colour coating and embossed UMC logo on the body, having system lumens output of Min.5850 Lumens, min. efficacy of 130 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.95, operating range of 140-270V, inbuilt surge protection of 20 kV, Life class of 50,000 Hrs at L70B50 including driver complete with Uncondional 5 Years warranty as per specification (Make: Polycab/Orient/ Crompton Greaves. As per approved sample in UMC) |
| 6 | Supplying and erecting integrated LED street light fitting 90W IP65 & IK08class having single piece pressure die-cast aluminium housing with military green colour coating and embossed UMC logo on the body, having system lumens output of Min.11700 Lumens, min. efficacy of 130 lumen/W, CRI>70, CCT up to 6500K, THD<10%, p.f. >0.95, operating range of 140-270V, inbuilt surge protection of 20 kV, Life class of 50,000 Hrs at L70B50 including driver complete with Uncondional 5 Years warranty as per specification (Make: Polycab/ Orient/ Crompton Greaves. As per approved sample in UMC) |
| 7 | Supplying and laying (including excavation of suitable width & depth up to 90 cm) 120 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, complete (Make :As per ISI Standard specification) |
| 8 | Supplying and laying (including excavation of suitable width & depth up to 90 cm) 146 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete (Make :As per ISI Standard specification) |
| 9 | Supplying and erecting SS Steel Hose Clamp Sice 3\\" round shape Make:-As approved sample as per UMC Specification |
| 10 | Supplying and erecting Street light bracket for erection of Single fitting ontubular welded pole with 40 mm. dia 1.0 m long “B” grade G.I. pipe alongwith pole cap of 125mm dia 600 mm long duly welded as per specification (Make: As per approved sample in UMC) |
| 11 | Supplying and erecting Street light bracket for erection of Double fitting ontubular welded pole with 40 mm. dia 1.0 m long “B” grade G.I. pipe alongwith pole cap of 125mm dia 600 mm long duly welded as per specification no.24(Make: As per approved sample in UMC) |
| 12 | Supplying & Erecting of mains with ISI mark 2 x 6 Sq.mm 1100 V grade alluminium conductor PVC insulated and PVC sheathed Flatwire (Make: Polycab cables/Vishal cables /Finiloex cables As per approved sample in UMC specification) |
| 13 | Supplying & Erecting of PVC insulating PVC Round sheathed FR 2.5 sq mm (50 no.x0.25mm dia. ) 3 core flexible multi stranded copper industrial cable for voltage grade up to 1.1.kV Flat wire (Make: Polycab cables/Vishal cables /Finiloex cables As per approved sample in UMC specification) Please Enable Macros to View BoQ information |