| 1 | S&F servo voltage stabilizer, 3 phase unbalanced type 315 KVA capacity copper wound 3 phase oil cooled input variation 380-460V AC, output voltage 415V +/- 1% with all accessories as per standard protection complete all as specified and directed by Engineer-in-Charge. (Note :- Rate for plate form of voltage stabilizer, cable of sqmm size for connection with input and output alongwith all connected accessories deemed to be included in quotated rates). |
| 2 | Taking down carefully aluminium/ copper point wiring for light, fan, bell, socket of point complete fittings such as switches ceiling roses pendents, regulator socket etc complete at site and making good to the disturbed surfaces of walls, floors etc. |
| 3 | M&L for point wiring with PVC insulated and PVC unsheathed single core multistranded FRLSH copper conductor cable of size 1.5 Sqmm (nominal area) using approved colour coding, 1100 volts grade, ISI marked, including PVC conduit heavy grade, 20 mm or higher dia with fittings concealed in wall/ on surface for ceiling with continuous earth wire of PVC insulated and PVC unsheathed single core multistranded FRLSH copper conductor cable of size 1.5 Sqmm (nominal area) 1100 volts grade, ISI marked and connecting to the common earth dolly including provn of 3mm thick plastic laminated sheet of appropriate size and sunken CI/ pressed steel terminal boxes for mounting switches, sockets and regulators etc including cutting chases and making good to the disturbed surfaces as per existing specifications for One light point/fan point/ bell point controlled by one, one way switch complete all as specified and directed. |
| 4 | All as per Srl item No 3 here-in-before but for one 5 Amp socket outlet on independent board |
| 5 | All as per Srl item No 3 here-in-before but for one 5 pin socket outlet 5 Amp on same board |
| 6 | All as per serial item No 3 here-in-before but wiring with 2.5 Sqmm FRLSH copper wire incuding earth wire 2.5 Sqmm of copper for 15 Amp 3 pin socket outlet. |
| 7 | S&F modular fan regulator 5 step type size 100 watt complete all as specified and as directed by Engineer-in-Charge. |
| 8 | S&F lamp holder, PVC/ polycarbonate type insulated body with back plate suitable for batten/ angle fittings complete all as specified and directed. |
| 9 | M&L for ceiling rose, surface bakelite 65x50mm three terminal. |
| 10 | S&F modular switch 1 way, 1 module 6 amps single pole one way all as specified and directed. |
| 11 | S&F modular socket, 2 module 6A 2/3 pin all as specified and directed. |
| 12 | S&F modular switch 1 way, 16 amps, 1 module all as specified and directed. |
| 13 | S&F modular socket, 6A/ 16A -2/3 pin combined, 2 module all as specified and directed. |
| 14 | S&F surface mounting universal box type housing made of powder coated CRCA sheet suitable for upto 1 x 18/20 W LED tube including taking down existing old unserviceable housing complete all as specified and as directed. |
| 15 | S&F LED tube 18/20W ultra bright LED polycarbonate tube with efficiency minimum 2000 lumens, CCT > 6500K, PF > 0.90 suitable for fitting into exsting/ new batten housing and connections to ceiling rose using PVC insulated and overall sheathed flexible copper conductor wire of size 0.75 sqmm 3 core and taking down existing old unserviceable tube complete all as specified and directed. (Note :- The contractor shall submit the LM-80 and LM-79 report form manufacturer to Engineer-in-Charge for approval before incorporating the items in work). |
| 16 | M&L for sub main wiring with two runs of single core multi stranded PVC insulated, copper conductor, grade 1100 Volt, FRLSH cable of size 6 sqmm including 6 sqmm multistranded copper conductor FRLSH cable PVC insulated for earthing duly connected with earth dolly, with approved colour coding including PVC conduit heavy grade of appropriate dia. concealed in wall with accessories including cutting chases and making good to the disturbed surfaces as per existing and taking down old unserviceable wiring complete all as specified and directed. (Note :- Three run of cable alongwith PVC conduit together shall be measured as single run). |
| 17 | M&L for sub main wiring with two runs of single core multi stranded PVC insulated, copper conductor, grade 1100 Volt , FRLSH cable of size 4 sqmm including 4 sqmm multistranded copper conductor FRLSH cable PVC insulated for earthing duly connected with earth dolly, with approved colour coding including PVC conduit heavy grade of appropriate dia. concealed in wall with accessories including cutting chases and making good to the disturbed surfaces as per existing and taking down old unserviceable wiring complete all as specified and directed. (Note :- Three run of cable alongwith PVC conduit together shall be measured as single run). |
| 18 | S&F in repair sheet metal enclosure double door for DB’s when MCB’s to be used of 240 volt 8 way with 200 amps rated bus bar SPN double door complete all as specified and directed. (Note:- All the connection of incoming and outgoing wire in MCB will be made with thimble suitable size as direced). |
| 19 | S&F in repair MCB single pole 6 amps to 32 amps complete all as specified and directed. |
| 20 | All as per item Srl No 19 here-in-before but single pole and neutral 32-63 amps complete all as specified and directed. |
| 21 | S&F in repair indoor type decorative recess mounted direct/indrect 60cm x 60cm luminaries light fixures 36 watt LED netural white complete including making connection with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed. |
| 22 | Taking down fan, sealing cable end, dismantling blades and removing fan and blades to store all as specified and directed. |
| 23 | Hanging only ceiling fan and connecting up including proviion of cable from ceiling rose or connector to fan complete all as specified and directed. |
| 24 | Taking down geyser with nuts, bolts and washers and removing connections from taps complete all as specified and directed. |
| 25 | M&L for grounting of nuts and bolts for fixing of 50/25 ltrs capacity on existing wall including cement and sand mortal 1:2 and finishing as per existing complete all as specified and directed. |
| 26 | M&L for cable protection GI tubing light grade fixed along the pole/ under road/ along the wall of size 40mm bore with necessary clamps complete all as specified and directed. |
| 27 | M&L for replacement of distribution board made out of CRCA sheet DB vertical type double door TPN 4 way including fixing in the wall, cutting chases, grounting and making good to match with the existing including making connections all as directed containing the folowings:- (a) MCCB 4 Pole 63 Amps 16 KA breaking capacity with thermal release: 01 No (In coming). (b) Bus bar 200 Amp factory made made out of aluminium duly insulated with wire adhesive tape RYB & black :4 Nos. (c) MCB SPN 40 Amp: 4 Nos, MCB SP 40 Amp: 08 Nos (Out going). (d) Connection from MCCB to bus bar will be made with aluminium strip of suitable capacity as directed. |
| 28 | M&L for earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the earth plate not less than 1.5 metres below ground level connected to galvanised iron earth lead wire 4.0 mm dia by means bolts, nuts, check nuts and washers of galvanised iron or steel all as shown inelectrical plate connected to earthing test point including testing on completion including water pipe 20mm bore medium grade 15mm bore light grade GI pipe for protection of earth lead including provision of concrete pit cement concrete 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) pre-cast RCC (1:2:4) type B-1 (using 20mm graded crushed stone aggregate) cover slab 54cm x 54cm x 5 cm including 8mm dia TMT bars both ways @ 15cm centre to centre with one handle for lifting made out of 8mm dia MS bar, funnel and wire mesh, excavation and earth work in any type of soil complete including dismantling existing all as specified and directed by Engineer-in-Charge. |
| 29 | S&F distribution box and MCB combo with sheet steel enclosure of 25 Amp capacity MCB SP complete all as specified and directed. |
| 30 | M&L for 16 meter high galvanised mast light suitable for 8 light symmetrically made out of heavy duty MS pipe selection recuring from bottom to top 15mm thick bottom plate fixing arrangementg with 20mm dia foundation bolt grouted in RCC foundation including necessary civil work etc complete with fixing arrangement for suspension system with steel wire rope of 6mm dia and dia double drum which comprising of following :- (a) Provision of single point air termination rod and necessary fitment required for protection against lightening protection (earthing shall be measured and paid for separately). (b) Provision of motorised hosting and lowering of light carriage for repairs. (c) Provn of aviation light indicator all as specified and directed by Engineer-in-Charge. (Note :- The foundation work and design shall carried out by the contractor as per manufacturer's instructions and nothing extra shall be paid on contractor). |
| 31 | S&F energy saving environmental friendly, long life, exclusive innovative die-cast aluminium IP 66 flood light with high power LEDs as light source, suitable for high lighting retails space 200 watt LED replacement metal halide flood light hoarding light luminaire complete all accessories, connecting up with twin core 4 sqmm copper conductor cable all as specified and directed by Engineer-in-Charge. |
| 32 | Excavation in trenches in soft/ loose soil including cutting road surfaces n.exc 1.5 mtr wide and n.exc. 1.5 mtr in depth for poles, stay, cable, pipe etc getting out all as specified. |
| 33 | Returning, filling in, including spreading, leveling,watering and well ramming in layers each n.exc 25 cm thick in soft loose soil all as specified. |
| 34 | Removal of excavated soil to a distance not exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 35 | Supply and lay brick common burnt sub class \\"B\\" old size (compressive strength not less than 75 kg per sqcm) for protection of cable laid in trenches for under ground cable all as specified. |
| 36 | M&L for sand cushioning trenches using fine sand to under ground cable, laid in two layers 15cm before laying the cable & 8cm after laying the cable complete all as specified and directed. |
| 37 | Supply and laying in replacement XLPE insulated armoured (under ground) heavy duty electic cable with stranded aluminim conductor 1100 volts grade cross sectional area 16 Sqmm 4 core laid in trenches/ducts/ through pipes/in floor road/along the pole etc all as specified & directed by Engr-in-charge. |
| 38 | M&L for earthing complete with galvanised steel earth plate electrode 60cm × 60cm × 6mm thick, buried directly in ground vertically to a depth not less than 2.25 metres deep below ground level with top edge of the earth plate at a depth not less than 1.5 metres below ground level earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common saft filling in alternate layers and electrode connection by using earth lead GI wire 4mm dia (8 SWG) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and other end of the earth wire connected to main switch board protected by galvanised iron light grade pipe 15mm bore in wall/ floor/ and GI pipe 20mm bore light grade for watering with funnel and wire mesh PCC chamber in cement concrete 1:3:6type C-2 and RCC pit cover including necessary excavation and earth work in any type of soil, returning filling with approved soil and disposed of surplus soil to a distance not exc 50 mtr away complete all as shown in electrical plate No 3 of SSR 2020 (Part-I). |
| 39 | S&F and commessioning of LT outdoor total enclosed/ LT panel board size 0.75 x 0.50 x 30 meter approx total enclosed made out of 3mm thick CRCA sheet, dust and vermin proof with front opening 440V, 3 phase, 4 wire having 200 amps capcity aluminium bus bar insulated with sleeves, incoming MCCB TPN 63 Amps capcity 440 volt 25 KA -01 No and copper wiring with multistranded cable including timer switch electronic type 01 No with necessary MCBs 20 Amps 09 Nos contractors etc, cable glands, lugs and two coats of synthetic enamel paint over a coat of red oxide primer and making necessary pedastal 300mm height from floor level and PCC work and provison of wiring from panel to light fitting with 2 core 4 sqmm copper conductor cable drawn through M rigid/ flexible conduit with necessary fitting etc. |
| 40 | A Schedule of Credit for old/unserviceable demolished/ dismantled items has been catered for in the tender. The Schedule of Credit is pre-priced by MES. The final amount of the tender shall be arrived at after deducting the total amount of Schedule of Credit Rs. 12.242/- from the total amount of BoQ as per General Summary sheet catered for after Schedule of Credit. Please Enable Macros to View BoQ information |