| 1 | SCH 'A' PART-I To XIINote: This schedule is pre-priced by MES and the rate indicated under Col 5 signifies this fact only |
| 2 | Total amount of Sch 'A' Part-I (Building and Structures) |
| 3 | Total amount of Sch 'A' Part-II (Site Clearance, Excavation and Earthwork) |
| 4 | Total amount of Sch 'A' Part-III (Internal Water Supply) |
| 5 | Total amount of Sch 'A' Part-IV (Internal Electric Supply) |
| 6 | Total amount of Sch 'A' Part-V (Road, Paths & Culverts ) |
| 7 | Total amount of Sch 'A' Part-VI (Sewage Disposal) |
| 8 | Total amount of Sch 'A' Part-VII (Area Drainage) |
| 9 | Total amount of Sch 'A' Part-VIII (External Water Supply) |
| 10 | Total amount of Sch 'A' Part-IX (External Electric Supply) |
| 11 | Total amount of Sch 'A' Part-X (Hot Water Supply) |
| 12 | Total amount of Sch 'A' Part-XI (Rain Water Harvesting) |
| 13 | SCHEDULE 'A' PART-XII (MISCELLANEOUS B/R AND E/M WORKS)Note: This schedule is not pre-priced by MES and the rate indicated as \\"Rs 0.00\\" under Col 5 signifies this fact only. |
| 14 | S&F Double door Sheet metal enclosures factory made Vertical DBs 6 way TPN, 415 volts Concealed in Wall, protection class IP-43, suitable for fixing incoming MCCB and outgoing MCB DP/TPN etc, confirming As per IEC 61439-3, Suitable for Flush Mounting and Surface Mounting, With 250 A Copper Busbar, With Neutral bar, Earth bar and Cable ties for Cable management, Fully shrouded Neutral bars, Prefitted masking sheet complete all as specified and as directed.Note:- MCCBS/ MCBs DP/TPN will be measured and paid separately. |
| 15 | S&F Double door Sheet metal enclosures factory made Vertical DBs 4 way TPN, 415 volts Concealed in Wall, protection class IP-43, suitable for fixing incoming TPN and outgoing MCB DP/TPN etc, confirming As per IEC 61439-3, Suitable for Flush Mounting and Surface Mounting, With 200 A Copper Busbar, With Neutral bar, Earth bar and Cable ties for Cable management, Fully shrouded Neutral bars, Prefitted masking sheet complete all as specified and as directed.Note:- MCCBS/ MCBs DP/TPN will be measured and paid separately.MCCBS/ MCBs DP/TPN will be measured and paid separately. |
| 16 | S&F MCCB, 4P, AC, 415 Volts of 125 Amp capacity 25 KA, thermal and magnetic adjustable Ics=100% Icu, and making connections with suitable size of copper lugs etc complete all as specified and directed. |
| 17 | S&F MCCB, 4P, AC, 415 Volts of 100 Amp capacity 16 KA, thermal and magnetic adjustable Ics=100% Icu, and making connections with suitable size of copper lugs etc complete all as specified and directed. |
| 18 | S&F MCCB, 4P, AC, 415 Volts of 63 Amp capacity 16 KA, thermal and magnetic adjustable Ics=100% Icu, and making connections with suitable size of copper lugs etc complete all as specified and directed. |
| 19 | Supply & fixing MCB , DP, AC, 415 Volts of 40 Amp capacity 10 KA, 'C' series and making connections with suitable size of copper lugs etc complete all as specified and directed by Engineer-in-Charge |
| 20 | S&F LED Tubelight fitting 20 W extruded aluminium housing battens are equipped with high specification CISPR 15 compliant Electronic driver and milky white, special polycarbonate diffuser, for glare free efficient light distribution with uniform light output, with all accessories including its connection with and including 2 core sheathed copper conductor cable of size 0.5 Sqmm with complete with all accessories etc complete all as specified and directed. |
| 21 | S&F Decorative ultra slim square profile LED lighting fixture with extruded polycarbonate, environmental friendly, energy efficient ready to use pack LED Tube light fitting 10 Watt with uniform light output, with all accessories including its connection with 2 core sheathed copper conductor cable of size 0.5 Sqmm with etc complete all as specified and directed. |
| 22 | S&F Energy saving and environmental friendly long life LED street light 35 Watt (Bldg security light) made up of pressure die cast aluminium housing with high efficiency LED as lighting source and lens embedded PC cover having bottom Opening separate driver compartment with IP66 protection and impact resistance of IK08 fixed on wall with GI pipe of suitable dia and all fixing accessories including connecting up with & including twin core twisted flexible copper conductor cable of suitable size of 230V, 50 HZ etc complete all as specified and directed. |
| 23 | S&F Exhaust fan, PVC body AC single Phase. 230V of size 200 mm sweep with blades, and frame and louvers complete all as specified and directed. |
| 24 | M&L Earthing complete with galvanised steel earth plate electrode 600x600x6mm thick buried directly in ground. Earth pit not less than 2.25 m depth and top edge of the earth plate not less than 1.5 m below normal ground level connected to galvanised earth lead wire 4.0 mm dia by means of nuts, bolts & washer etc. Earth wire connected upto main earth point / DBs along with 15mm dia earth protection pipe from top edge of the earth plate to main earth point to be connected and 20mm dia watering pipe light grade with funnel and provn of PCC using cement concrete (1:2:4) mix type B1 using graded stone aggregate and RCC pit cover 50 mm thick precast RCC (1:2:4) mix type B1 duly reinforced with 8 mm dia of TMT bar @ 100 mm CIC, both way, lifting arrangement complete including all necessary earth work etc complete all as specified and directed by Engineer-in-Charge |
| 25 | Supply and laying Double Walled Corrugated (DWC) HDPE pipe of nominal bore 50 mm polyethylene with smooth internal and profiles external surface for non pressure under ground cable including 90 degree bends with coupler, fittings and rubber ring, conforming to IS: 16205 Part 24, 450 N laid in trenches for cable protection complete, all as specified and as directed. |
| 26 | Supply and laying Double Walled Corrugated (DWC) HDPE pipe of nominal bore 110 mm polyethylene with smooth internal and profiles external surface for non pressure under ground cable including 90 degree bends with coupler, fittings and rubber ring, conforming to IS: 16205 Part 24, 450 N laid in trenches for cable protection complete, all as specified and as directed. |
| 27 | Supply and laying Double Walled Corrugated (DWC) HDPE pipe of nominal bore 120 mm polyethylene with smooth internal and profiles external surface for non pressure under ground cable including 90 degree bends with coupler, fittings and rubber ring, conforming to IS: 16205 Part 24, 450 N laid in trenches for cable protection complete, all as specified and as directed. |
| 28 | Supply, installation, testing and commissioning of step down transformer, outdoor type, and conforming to IS 1180:2014, plinth mounted, HT 11 KV, 3 phase 433 volts, 4 wire, 50 Hz, delta/star connected, vector group DYN -11 double copper wound, ONAN, manual type off load tap changing facility on HT side to vary secondary voltage from minus (-) 7.5% to plus (+) 7.5% in steps of 2.5 %, continuous rating of capacity 160 KVA Level 3 including Cable entry box on HT Side, Cable entry box on LT side. The Transformer shall be completed with all standard fittings and accessories and first fill of transformer oil IS 335 ISI marked filtered & dehydrated oil etc, complete all as specified and directed and comprising of the following accessories :-Note :- Transformer shall be mounted on platform/plinth. (a) One cable entry box on primary HV side having cable glands suitable for HT XLPE Cable (consisting of 3 Nos porcelain HT bushings with brass/gun metal bushing rods complete with nuts and washers).(b) One cable entry box on secondary (LV) side consisting of 4 Nos porcelain bushing with GM bushing rods complete with GM nuts, and washers with one No cable gland suitable for reception of outgoing LT armoured cables of suitable size.(c) Oil conservator tank with filter type, drain valve and oil level gauge.(d) Dehydrating breather with first fill of dehydrating agent.(e) Thermometer pocket on tank cover. |
| 29 | (f) One No 100mm dia dial type thermometer vapour pressure type having range 0-120 degree centigrade with temp reading pointer, max temp indicator and resetting device.(g) Rating plate with terminal markings.(h) Two earthing terminals on tank/tank cover to facilitate fixing of 32x6m GI earth strip.(j) Oil Level gauge.(k) Oil drain and filter valves.(l) Oil filler hole with cap/plug with connections complete.(m) Lifting lugs.(n) Air relief valve plug.(o) Four plan solid cast steel detachable rollers.(p) First fill of fresh oil conforming to relevant IS and tested upto 50 KV dielectric strength upto top of core.(q) Extra bushing for neutral outside the LT cable box for providing independent earthing for neutral.(s) Any other fittings/accessories so as to confirm the whole transformer to IS-1180 Part-1:2014. |
| 30 | Supply ,Installing, commissioning and testing in replacement LT panel board, factory made, out door, cubical type , cubical type, vermin proof , dust proof, water proof, painted as per 7 tank processes & suitable for IP-56 protections, made out of 3.15 mm thick CRCA sheet and inner sheet of 2.0mm thick and angle iron frame of size 50x50x5mm inside depth not less than 50 cm and size suitable to accommodate the following accessories, with insulated aluminium busbar 500 amps capacity , 3 phase , 4 wire system, both sides openable (front and back), locking arrangement with CPRI approved , including cable trench duly painted with power coated with RAL 7032 internally and externally connecting with existing cable with lugs including internal wiring with copper cables of suitable size using lugs comprising the following accessories all as directed.( Main Panel)a)MCCB 315 Amp four pole with Breaking Cap 36 KA-01 No (Incoming)(b) MCCB, 160 Amps, with breaking cap 16KA - 01 Nos (For Living Accn)(c) MCCB, 63 Amps, with breaking cap 16KA - 01 Nos (For Cook house & Dining Hall)(d) MCB 32 Amps, with breaking cap 16 KA -01 (For Street Light)(e) MCB 32 Amps, with breaking cap 16 KA -01 (For Spare)(f) Multifunction meter digital type)-01 No(g) Phase indication lamps LED type with holder-01 Set(Set of Three) |
| 31 | (h) Timer Switch with connected accessories for on/off for Street Light.Notes: The rates quoted shall include for earth work and excavation for angle iron frame for foundation of panel board upto 0.50 m below GL in any type of soil and PCC 1.4:8 type D2 (40mm graded stone aggregate) filling in foundation. The ground clearance of panel board shall be 0.40 m from GL to the bottom of panel board) |
| 32 | S&F Vertical type air break switch, gang operated, triple pole, mechanically operated, outdoor type, with all fittings and accessories mounted on and including HT 11 KV porcelain insulators and steel channel frame, GI operating rod 25 mm dia of suitable length to worked from ground, including locking arrangements, suitable for 11000 volts, 200 Amps current rating complete including dismantling existing one all as specified and as directed. |
| 33 | S&F Drop out fuse unit, expulsion type for outdoor air break gang operated switch, single pole mounted on and including insulators for 11 KV working pressure fixed to and including MS channel with nuts, bolts and washer etc synthetic bounded fuse tube complete with line capacity suitable for current carrying capacity upto 100 Amps all as directed. |
| 34 | S&F Street light fitting (LED) of capacity 60 W, 6000-6500 Lumen- 6000 Lm, 10 KV in build surge protection IP-66, die cast aluminium housing and 4 Sqmm service wire for necessary connection etc complete all as specified and directed. |
| 35 | S&F PVC Junction box of size 200x175x100mm, IP 66 with hinged door including locking arrangement and MCB SP 6 Amp with necessary nut, bolt etc and including TPN aluminium bus bar mounted on insulators with suitable holes to provide incoming and outgoing LT cables and street light MCB compete all as specified and directed. |
| 36 | M&L Earthing complete with galvanised steel earth plate electrode600x600x6mm thick buried directly in ground.Earth pit not less than 2.25 m depth and top edge of the earth plate not lessthan1.5m below normal ground level connected to galvanised earth lead wire 4.0 mm dia by means of nuts, bolts & washer etc. Earth wire connected upto main earth point /DBs along with15mm dia earth protection pipe from top edge of the earth plate to main earth point to be connected and 20mmdia watering pipe light grade with funnel and provn of PCC using cement concrete (1:2:4) mix type B1 using graded stone aggregate and RCC pit cover 50 mm thick precast RCC (1:2:4) mix type B1 duly reinforced with 8mm dia of TMT bar@100mm C/C, both way, lifting arrangement complete including all necessary earth work etc complete all as specified and directed by Engineer-in-Charge |
| 37 | M&L Earthing with galvanised steel earth plate electrode of size 600 x 600 x 6mm thick buried vertically in ground not less than 2.25 mtr below ground level with top edge of the plate not less than 1.5 mtr below ground level and connected to Gl strip 32x6 mm by means of nuts, bolts and washers and encased in and including 15 dia Gi medium grade pipe upto 2.4 mtr height form ground level fixed by MS flat iron clamp 40mm x 5mm with nut, bolt and washers, Gl strip fixed to base along pole and connected to over head line for providing earthing to HT pole/feeder AB switch LA complete with charcoal dust, salt packed around plate 150 mm thick including watering Gl pipe, medium grade 40 mm dia with blanking cap 1.5 mtr long fixed to funnel with wire mesh complete with PCC chamber and RCC chamber over all as per Electrical Plate No 5 of SSR Part 1-2009 including excavation and earth work in any type of strata and testing on completion complete all as specified and as directed.Note: Any length of Gl strip and 15 mm dia GI medium grade pipe shall be provided as per actual requirement at site |
| 38 | M&L Construction of PCC solid block valve chamber including earth work described as under complete all as specified for the Internal Dimension 1200 mm x 1200 mm x 1000 mm :(a)100 mm thick hard core (b)PCC foundation 1:4:8 type D2 (using 40 mm graded stone aggerate) (c) 200 mm thick block masonry graded C-5 built in CM 1:6. (d) 15 mm internal and external plaster in CM 1:4. (e) 3mm thick MS sheet chamber cover and 50 x 50 x 6 mm thick angle iron frame including painting with two coats of synthetic enamel paint over one coat of red oxide primer on all exposed surface including locking arrangements complete all as specified and as directed. |
| 39 | Cutting and tapping cast iron/ductile iron water mains, in position, for branch connections of the internal dia 80 mm complete all as specified and directed. |
| 40 | Supply, installation, connection, testing and commissioning of Storage Type Water Cooler of 80-litre storage capacity and 40 litres per hour cooling capacity, stainless steel, electric driven, single phase, working on eco-friendly refrigerant R-134a, including necessary electrical connections, extending drain outlet pipe up to the nearest drain, complete all as specified and as directed. |
| 41 | Supply, installation, connection, testing and commissioning of Desert Air Cooler, electric driven, single phase, having nominal air flow capacity of 4000 cubic metres per hour (or nearest higher capacity), with Plastic/PVC body, including all fittings, accessories and electrical connections, complete all as specified and as directed. |
| 42 | Supplying, Installing, Connecting, Testing and Commissioning Refrigerator electric driven (Single Phase) of capacity 215 litres, 220 volts, 50 Hz, BEE 5 Star rated based on eco friendly gas complete all as specified and directed. |
| 43 | Supply, Installation, Commissioning of Metal Top Deep Freezer 400 litre capacity having double door, single phase 240 volt, 50 Hz complete all as specified and directed. |
| 44 | Supplying, Installing, Connecting, Testing and Commissioning Digital copper wound automatic Voltage Stabilizer for automatic operations, single phase naturally air cooled, indoor type and designed for input variation between 170 V to 250 V with out put voltage stabilized at 230 volts with accuracy of (±) 2.5% and capacity 1 KVA complete all as specified and directed. |
| 45 | Supplying, Installing, Connecting, Testing and Commissioning Digital copper wound automatic Voltage Stabilizer for automatic operations, single phase naturally air cooled, indoor type and designed for input variation between 170 V to 250 V with out put voltage stabilized at 230 volts with accuracy of (±) 2.5% and capacity 2 KVA complete all as specified and directed. Please Enable Macros to View BoQ information |