| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GE Utilities Udhampur Name of Work: Repair/Maintenance of STPs and ETP at various locations under GE (Utilities) Udhampur Contract No: GE/U-67/2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Carrying samples for testing of treated water of STP (testing in NABL approved laboratory as approved by GE) and submission of detailed test report to the office of the Engr-in-charge. (a) Carrying out minimum essential testing of water as per IS 10500-1991 mandatory for chemical, odour, PH Value TSS, BOD COD residual chlorine total nitogen, sulphate, oil and grease ammonical Nitrogen (NH3-N) and Bacteriological total collifrom organisms per 100 Ml (MPN) and E colilie in 100 ml, complete all as specified and directed by Engr-in-Charge.Note - rate quoted shall deemed to be included for :-(i) Cost of sterilised bottle as required(ii) To and from transportation charges for collection of sample(iii) testing to be done every 3 months or as and when directed by engr in charge |
| 3 | Supply and fixing in replacement of following spare for Non clogging sub pump cap 2 HP to 3 HP, complete all as specified and directed by Engr-in-Charge. |
| 4 | SS roter sleeve |
| 5 | SS roter shaft ASS 410 |
| 6 | Water seal |
| 7 | CI Lower Housing chamber |
| 8 | CI upper housing chamber |
| 9 | Connetion plate |
| 10 | Remetaling of rotor & turning/grinding |
| 11 | GM suction ring |
| 12 | GM/CI Impeller |
| 13 | SS stud with nut |
| 14 | Impeller nut |
| 15 | Impeller key |
| 16 | Jointing of sub cable |
| 17 | Painting of sub pump set with one coat of red oxide and two coat of synthetic enamel paint |
| 18 | CI suction chamber |
| 19 | Repairing of stamping of stator |
| 20 | O ring set |
| 21 | Ball bearing 6306-2Z Make- SKF/ZKL |
| 22 | Roller Bearing 3308A Make-SKF/ZKL |
| 23 | Roller Bearing NU 305 Make-SKF/ZKL |
| 24 | Supply and fixing in replacement of cloth of sludge centrifuse machine of capacity 1 cum/hr, basket type complete all as specified and directed by Engr-in-Charge. |
| 25 | S&F New parts for single/double/monoblock stage pump of capacity 5HP/3HP/2HP as per manufacturer's composition of existing make of pump as below complete all as specified and directed by Engr-in-Charge. |
| 26 | Pump impeller made out of CI, complete all as specified and directed by Engr-in-Charge. Make : Kirloskar/Wilo Mather Platt or equivalent make as approved be GE. |
| 27 | Pump shaft stainless steel shaft complete with check nut and keys, complete all as specified and directed by Engr-in-Charge. |
| 28 | Casing bearing |
| 29 | Bearing housing |
| 30 | tyre coupling/star coupling |
| 31 | Gland cup with nut and bolts |
| 32 | Disconnecting electric connection of upto 10/15 HP motor, removing the UNSV motor from existing place by unscrewing the foundation bolts and nuts decoupling from the pump, setting aside and transporting to workshop for repairs including dismantling the motor,cutting/taking out burnt winding of stator, rotor, cleaning the slots, transporting back after repair/winding & re-assembling the same complete all as specified and directed by Engr-in-Charge.Note: (a) Rewinding of motor will be measured and paid separately under relevent item.(b) The rates quoted shall be deemed to include the cost of loading/unloading, transportation, grease, nuts, bolts and washers of any size and shape as required at site and refixing of serviceable motor duly functional and testing complete at its existing location/position complete all as specified and directed by Engr-in-Charge. |
| 33 | Description all as per ser item No 4.00 here-in-before but, of capacity 5HP/3HP/2HP. |
| 34 | Supply and fixing in replacement following parts of Induction motor of capacity 10/15 HP of existing make |
| 35 | Fan cover |
| 36 | Endshield |
| 37 | Terminal box |
| 38 | Supply and fixing in replacement following parts of induction motor of capacity 5HP/3HP/2HP of existing make, complete all as specified and directed by Engr-in-Charge. |
| 39 | Fan cover |
| 40 | Endshield |
| 41 | Terminal box |
| 42 | Removing the burnt out winding from the rotor and stator, cleaning the slots, providing high quality of class'B' paper insulation inside the slots, rewinding the motor of capacity 2/3/10/15 HP as per existing with super enamel copper wire of same size and guage as per existing rapping up with high quality cotton tape and varnising with super quality oil including drying upto desired temperature and desired time. complete all as specified and directed by Engr-in-Charge.Note:- Cost of labour for winding deemed to be included in the rate quoted. |
| 43 | Material & labour for cleaning the Dual media filter(DMF) installed at various location of STPs quartely from rep by checking the hardness of water, removing the silt and scrubbing the tank , checking the tightnesss of all valves and seal ,opening the tank,back washing, fast rinse ,descaling the surfaces and media with with measured dose of cleanasing agent complete all as specified and directed by Engr-in-Charge. |
| 44 | Material & labour for cleaning the Activated carbon filter (ACF) installed at various location of STPs quartely from authorised rep by checking the hardness of water, removing the silt and scrubbing the tank , checking the tightnesss of all valves and seal ,opening the tank,back washing, fast rinse ,descaling the surfaces and media with with measured dose of cleanasing agent complete all as specified and directed by Engr-in-Charge. |
| 45 | M & L for cleaning of Moving Bed Bio Reactor(MBBR) tank of storage capacity upto 200000 to 1000000 Ltrs and all drain thoroughly by removing mud, grits etc from tank complete all as required at site complete all as specified and directed by Engr-in-Charge by following method :-(a) Cleaning inner surface of tank complete by scraping with steel wire brush and and removing mud and sludge collected inside the tank manually at a distance not exceeding 50 mtr all as directed by engr-in charge (b) Washing with clean water and bleaching powder mixture throughly complete tank internally and removel of left out sludge if any at site at a distance not exceeding 50mtr all as directed by engr-in-charge |
| 46 | M & L for cleaning of Sludge Drying Beds (approx 12 Nos)by removing mud, grits etc from beds complete all as required at site and directed by the Engineer-in-Charge by following method :-(a) Cleaning inner surface of bed complete by removing mud and sludge collected inside the bed manually at a distance not exceeding 50 mtr all as directed by engr-in charge (b) Washing with clean water and bleaching powder mixture throughly complete bed internally and removel of left out sludge if any at site at a distance not exceeding 50mtr complete all as specified and directed by Engr-in-Charge. |
| 47 | M & L for cleaning of chlorine contact tank , filter feed tank and treated water tank all drain thoroughly by removing mud, grits etc from tank complete all as required at site and directed by the Engineer-in-Charge by following method :-(a) Cleaning inner surface of tank complete by scraping with steel wire brush and and removing mud and sludge collected inside the tank manually at a distance not exceeding 50 mtr complete all as specified and directed by Engr-in-Charge.(b) Washing with clean water and bleaching powder mixture throughly complete tank internally and removel of left out sludge if any at site at a distance not exceeding 50mtr complete all as specified and directed by Engr-in-Charge. |
| 48 | Material and labour for de watering the tube settler tank of STP plant capacty 1000 KLD and removing the sludge by means of sludge machine and disposal of same to a safe distance by transport and scrubbing of the internal surface using industrial vaccum machine and applying food grade paint to wall complete all as specified and directed by Engr-in-Charge. |
| 49 | Description all as per ser item No 14.00 here-in-before, but of capacity 300/400 KLD. |
| 50 | Material and labour for de watering the clear water tank of STP plant capacty 1000 KLD and removing the sludge by means of sludge machine and disposal of same to a safe distance by transport and scrubbing of the internal surface using industrial vaccum machine and applying food grade paint to wall complete all as specified and directed by Engr-in-Charge. |
| 51 | Description all as per ser item No 16.00 here-in-before, but of capacity 300/400 KLD. |
| 52 | Material & Labour for replacement of filter press bed cloth of poly proplene size 75 cm x 75 cm of 550 GSM for STPs complete all as specified and directed by Engr-in-Charge. |
| 53 | Material & Labour for replacement of PP filter press bed plate with cloth,tap and handle cloth of size 75 cm x 75 cm for STPs complete all as specified and directed by Engr-in-Charge. |
| 54 | Material & Labour for electronic liquid chlorine ( Sodium Hypochlorite) Dozing pump 230V AC 50 Hz capacity upto 10 LPH @ 5 Kg/Cm2 pressure,pump head PP with Glass filled,Teflon Diaphragm with suction and discharge tubing 3 mtr along with PVC injector with NRV,FRP Tank 150 Ltrs capacity heavy duty FRV tank complete all as specified and directed by Engr-in-Charge. |
| 55 | Material & labour for disposable bleaching stick for drinking water disinfection containing non granular solouble solid chlorine with zero sludge suitable for direct use in reservoirsand dosing system with the following features,complete all as specified and directed by Engr-in-Charge. :- (a) Length of stick 25 cm -35 cm,(b) Dia - 05 Cm,(c) Over chlorination risk prevention capability control release of active ingredients,(d) No release of chlorine dust during handling 100% tamper proof system,(e) Automatic stick replacement indication complete all as specified and directed by Engr-in-Charge.Make Declibac or equivalent model of any other model. |
| 56 | Material & labour for bleaching stick suspender with following specifications:- (a) Metalic dead weight min 4kg,cylindrical configuration with base grip, (b) Suspension Length 06 mtr to 10 mtr,(c) Stick holding Capacity 05, (e) Fastening Mode - thermoplastic hook Make Declibac or equivalent complete all as specified and directed by Engr-in-Charge. |
| 57 | M&L for repair of Hypo dosing pump of discharge cap 0-6 LPH complete all as specified and directed by Engr-in-Charge. |
| 58 | Supply and fixing in replacement following parts of LT Panel & Starter, complete all as specified and directed by Engr-in-Charge. |
| 59 | MCCB 100 Amp 4 Pole 36 KA |
| 60 | Contactor 3 pole with AC coil AC-3 duty rating at 415 Volts 50 Hz, frame size1 suitable for 3 HP to 15 HP pump set |
| 61 | © Relay 3A, 4 Pole, 240V AC |
| 62 | Cyclic Timer |
| 63 | Fusible combination starter disconnect switch |
| 64 | Wiring single core 1 sqmm |
| 65 | Indicating lamps RYB as per existing |
| 66 | Selector switch for ON-Off as per existing |
| 67 | Analog Voltmeter Range (0-500V) |
| 68 | Analog Ampere meter (0-60A) |
| 69 | S&F in replacement of MS stud bolts of existing size with nuts suitable for pumps and motors of various capacity installed at installations, complete all as specified and directed by Engr-in-Charge. |
| 70 | Supply & Fixing in replacement of CI butterfly valve PN 1.6 of following size/bore conforming to IS 13095 complete all as specified and directed by Engineer-in-Charge. |
| 71 | 150mm dia |
| 72 | 125 mm bore |
| 73 | 100 mm bore |
| 74 | 80 mm dia |
| 75 | 65 mm dia |
| 76 | 40/50 mm dia |
| 77 | Supply only PVC insulated, sheathed, Copper conductor flexible cable, 1100 volts grade Heavy Duty, cross sectional area 4 sqmm, Four core round flexible complete all as specified and directed by Engineer-in-Charge. |
| 78 | Supply only of PVC insulated sheathed copper conductor flexible cable 1100 volts grade heavy duty of size 4 Sqmm nominal cross section area 3.5 core, complete all as specified and directed by Engineer-in-Charge. Make of cable Polycab /Plaza /Grandlay. |
| 79 | Supply only PVC insulated, sheathed, Copper conductor flexible cable, 1100 volts grade Heavy Duty, cross sectional area 6sqmm,six core round flexible complete all as specified and directed by Engineer-in-Charge. |
| 80 | Supply & laying of flexible pipe of 40 mm dia used for wiring purpose complete all as specified and directed by Engineer-in-Charge. |
| 81 | Supply & pouring Bio-Culture (Bio reme )in aeration tank/MBBR tank at STPs complete all as specified and directed by Engineer-in-Charge. |
| 82 | Supply and mixing of Bioculture (Bio Reme STP for developed bacteria in equilisation tank, MBBR 1 and MBBR 2 tanks of STP chamber complete all as specified and directed by Engr-in-Charge. Make: IFFCO or equivalent make as specified. |
| 83 | S&F in replacement of auto air release valve of capacity 3HP, discharge 17.3 cum/hr complete all as specified and directed by Engineer-in-Charge. |
| 84 | S&F in replacement of Pressure gauge with needle valve & bush of 100 mm dia having pressure range 0-7 Kg/sqcm complete all as specified and directed by Engineer-in-Charge. |
| 85 | S&F in replacement of NRV (Sandwich type) of size 65 mm dia complete all as specified and directed by Engineer-in-Charge. |
| 86 | M&L for brick/ stone masonary valve pit chamber of size 0.75 mtr x 0.75 mtr x 0.75 mtr internal dimention) with 3.15 mm thick MS cover including 50 x 50 x 6 mm angle iron frame with 100mm hinges embedded in coping with locking arrangement and painting the MS surfaces with two coat of redoxide primer & syntheatic enamel paint. The chamber shall be of PCC 1:4:8 type D2 40mm graded aggregate for foundation, brick work in cement mortar, 75mm PCC coping with PCC 1:3:6 type C1, 15 mm thick plastering in cement mortar 1:4 including necessary excavation, earth work and colour washing internally and externally surfaces complete all as specified and directed by Engineer-in-Charge. |
| 87 | M & L for painting of DMFs, ACFs, Pipelines of STPs, Header (naming of delivery lines of header with white colour) & sluice valve of Pump houses including surface preparation by scrapping with emery paper and painting with one coat of red oxide primer and two coats of synthetic enamel paint of existing colour of approved make complete all as specified and directed by Engineer-in-Charge. |
| 88 | Supply and mixing of Bioculture (Bio Reme N& P) booster for developed bacteria in equilisation tank, MBBR 1 and MBBR 2 tanks of STP chamber complete all as specified and directed by Engr-in-Charge. Make: IFFCO or equivalent make as specified. |
| 89 | Material & labour for air grid system with difusers for equilisation tank 300KLD 7.5 Mtr dia made out of suitable dia GI pipe with connection to the inlet pipe made grid system of suitable size stainless steel pipes of branch pipe with 100/80mm with coarse bubble diffuser 12 nos of air flow rate not less than 8(M3/Hr) of bubble diameter 3mm complete all as specified and directed by Engineer-in-Charge. |
| 90 | Material & labour for PVC flexible suction hose pipe 100 mm dia of wall thickness 6mm suitable for sewage pumping which are reinforced with a spiral or rigid pvc or a helix of embedede steel wire with temperature range of - 10 degree to 60 degree celsius complete all as specified and directed by Engineer-in-Charge. |
| 91 | Material and labour for prepration of seprate suction pipe for ETP non clog submerssible pump with MS pipe 100mm dia medium grade of approx 10 mtr length with foot valve and connection to the existing pump with fabrication of necessary welding works ,jointing with flanged ends, nut bolts and rubber gaskets complete all as specified and directed by Engineer-in-Charge. |
| 92 | Material and labour for disconnecting the electric connection from ETP/STP non clog sbmerssible pump 3HP and dismantiling the pump and motor servicing the same with grease/ oil for bearing ,shafts and tightening the nut bolts, gland cup and packing with new gland, dismantiling the pump and removing the cloged particles from impeller side, refixing the same with motor and checking the allignment of shaft,pump with motor once in a quarter tightening the electrical connection complete all as specified and directed by Engineer-in-Charge.Note.- Minor parts such as mechanical seal,O ring, washers, gasket, included in the quoted rate. |
| 93 | Material and labour for disconnecting the ETP/STP filter press screw pump and motor servicing the same with grease/ oil for bearing ,shafts and tightening the nut bolts, gland cup and packing with new gland, dismantiling the pump and removing the cloged particles from impeller side, refixing the same with motor and checking the allignment of shaft,pump with motor once in a quarter tightening the electrical connection complete all as specified and directed by Engineer-in-Charge.Note.- Minor parts such as mechanical seal,O ring, washers, gasket, included in the quoted rate. |
| 94 | Material and labour for disconnecting the ETP/ STP agiator motor upto 1 HP servicing the same quartely with grease/ oil for bearing ,shafts and tightening the nut bolts, refixing the same with motor and checking the allignment of shaft with motor tightening the electrical connection complete all as specified and directed by Engineer-in-Charge.Note.- Minor parts such as mechanical seal,O ring, washers, gasket, included in the quoted rate. |
| 95 | Material and labour for disconnecting the STP non clog sbmerssible pump ,dismantilling the suction line and taking up complete set with the help of chain pulley servicing the same with grease/ oil for bearing and tightening the nut bolts, gland cup and packing with new gland, dismantiling the pump and removing the cloged particles from impeller side, refixing the same with motor and checking the allignment of shaft,pump with motor once in a month tightening the electrical connection, lowering the pump and making the electric connection complete all as specified and directed by Engineer-in-Charge. |
| 96 | Material and labour for annual maintenance of Air Blower twin lobe positive displacement type (Everest Make) from authoriesed rep of pressure upto 6000 MMWC and capacity upto 500 Cum/hr at different locations including disconnecting from chanel frame and electrical panel for repair of Gear Box, refitting of gear box after oiling, greasing, alingment of motor and re-fixing/ assembling testing to make it functional complete inciuding cleaning of all dirt, dust etc. complete all as specified and directed by Engineer-in-Charge. |
| 97 | Supply and fixing in replacement following parts of Air blower twin lobe positive displacement type and pressure rating upto 6000 MMWC, complete all as specified and directed by Engineer-in-Charge. |
| 98 | Bearing Set |
| 99 | Set of oil seals & O-rings |
| 100 | Air filter |
| 101 | Set of Piston Bush |
| 102 | Set of piston ring Bush |
| 103 | Set of Piston ring |
| 104 | Set of retainer |
| 105 | Gasket Set |
| 106 | Pulley Spacer Bush |
| 107 | Pressure guage |
| 108 | EBBO oil (Air compressor oil) |
| 109 | Design, supply & installation of filter press in cast iron frame and polypropelene plates of size 24”x24” (min) with 10 plates with manual operated system complete in every respect required for efficient operation. Horizontal single stage open impeller suitable for solids upto 65 mm coupled to a horizontal TEFC electric motor 2HP capacity and mounted on a MS fabricated base plate, with pressure gauge on each pump outlet, automatic duty switchover after each operation complete all as specified and directed by Engineer-in-Charge.Pump Capacity 3 Cum/hour |
| 110 | M&L PCC 1:3:6 type C-2 (using 40 mm graded crushed stone aggregate) cement concrete in as in foundation filling of pillar complete all as specified and directed by Engineer-in-Charge. |
| 111 | Fabrication, Supply & Installation of fine bar screen in MSEP of suitable size for 1.0 MLD and capable of holding particles upto 6 mm.- 02 Nos |
| 112 | Material & labour for disposing the sludge quartely by means of transport from STPs plant complete all as specified and directed by Engineer-in-Charge. |
| 113 | Material & Labour for supplying chemicals and disinfectants for water supply installation,STP, ETP as below complete all as specified and directed by Engineer-in-Charge. |
| 114 | Poly Aluminium Chloride |
| 115 | Ferrous sulphate |
| 116 | Caustic Soda |
| 117 | Sodium Hypochlorite |
| 118 | Supply and fixing fan belt suitable for ETP pressed filter of size B 43 suitable for heat and oil resistant complete all as specified and directed by Engineer-in-Charge. |
| 119 | Supply and fixing fan belt suitable for STP pressed filter of size A 52 suitable for heat and oil resistant complete all as specified and directed by Engineer-in-Charge. |
| 120 | Supply and fixing fan belt suitable for air blower size 16 inch suitable for heat and oil resistant complete all as specified and directed by Engineer-in-Charge. |
| 121 | Supply only lithium base grease AP3 in 20 Kg pack suitable for application to ball bearing with operating temp 30 to 120 degree celsious drop point 174 degree celsious, colourlight fawn complete all as specified and directed by Engineer-in-Charge. |
| 122 | Supply and fix Gland packing type 3 of size 12 mm made of asbustus grip with silicon complete all as specified and directed by Engineer-in-Charge. |
| 123 | Material & labour for MBBR media black colour polyproplene material of size 16mm x22mm cylindrical type suitable for existing one complete all as specified and directed by Engineer-in-Charge. |
| 124 | Supply, laying, jointing and testing MS ERW pipe class 'B' of bore 150 mm having wall thickness 6 mm with permissible tolerance + 10% conforming to IS-3589, ISI marked alongwith circular welding joints laid in trenches/ along road/ on surface/ slopes/pillars/ culverts/ causeways etc, complete all as specified and directed by Engr-in-Charge. |
| 125 | Description all as per Ser item No 59.00, here-in-before, but of size 100mm dia |
| 126 | Description all as per Ser item No 59.00, here-in-before, but of size 80mm dia |
| 127 | Description all as per Ser item No 59.00, here-in-before, but of size 65 mm dia |
| 128 | Description all as per Ser item No 59.00, here-in-before, but of size 50mm dia |
| 129 | Description all as per Ser item No 59.00, here-in-before, but of size 40mm dia |
| 130 | Material & labour for Horizontal single stage open impeller screw pumps suitable for solids upto 65 mm coupled to a horizontal TEFC electric motor and mounted on a MS fabricated base plate, with pressure gauge on each pump outlet, complete in all respects.Pump Capacity 5 Cum/hour at 10 m head - 01Nos Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |