| 1 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth and getting out in any type of soil for laying cables/pipes/erection of poles etc complete all as specified and directed. |
| 2 | Removing surplus excavated meterial (soil) to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed. |
| 3 | Returning filling in soil including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and directed. |
| 4 | Supply and laying in trenches river sand clean including spreading/leveling, cushioning for underground cables complete all as specified and directed.Note : Punned thickness shall be measured for payment. |
| 5 | Supply and laying in replacement reinforced precast concrete cable cover, class HV, type 2, flat, size 450mmx180mmx40mm complete all as specified and directed. |
| 6 | Supply, laying and testing in repairs of HT cable XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured, electric power cables (Heavy duty) with aluminium conductor, 11000 volts grade cross section area 120 Sqmm 3 core complete laid in trenchers, duct, passing through pipe, fixed to poles complete all as specified and directed.Note : During cable passing through or laying by roads, pavement, contractor will redo existing surface as previous road and pavement without any extra cost to the Govt. |
| 7 | Supply and fixing in replacement Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 Sqmm complete all as specified and directed. |
| 8 | S&F Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washer, welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed. |
| 9 | Supplying and fixing in replacement and testing gang operated air breaker switch, triple pole, machanically operated mounted on insulators and steel frame with operatingmechanism worked from ground level using heavy duty GI pipe for current rating 400 Amps, out door type(confirming to IS specifications) HT 11 KV, tripple drop out HT fuse assembly, fuse carriker fitting, 12 insulator type mounted on MS channel operating rod with pad lock arrangement complete all as specified and directed. |
| 10 | S&F in replacement of Lightening arrestors gapless metal oxide type complete with all fittings, suitable for a system voltage of 11 KV and of class 10 KA complete all as specified and directed. |
| 11 | M&L in replacement GI tubing light grade 100mm dia with all fittings laid in trenches or fixed on wall along pole, complete for protection of electric cable complete all as specified and directed. |
| 12 | Dismantling & taking down existing ACSR conductor of any size by opening the binding wire from HT electric poles complete all as specified and directed. |
| 13 | Taking down old insulators off size & type complete all as specified and directed. |
| 14 | Taking down old cross arms, channels, angle iron, clamps, nut, bolts, stay wire, stay assembly, GI wire, anti climbing devices, danger notice boards etc complete all as specified and directed. |
| 15 | Notes :-An amount of Rs. 6579.00 on account of Credit Schedule for Schedule 'A' Part-II shall be deducted from total quoted amount of BOQ to arrive at the contract sum. Please Enable Macros to View BoQ information |