| 1 | Supply, installation, testing and commissioning of 13 passenger capacity lift (MRL) in the existing lift shaft/pit at Central Office, BHU, complete with all necessary components and accessories for satisfactory operation, including machine, controller, guide rails, car, counterweight, suspension ropes, landing doors, car doors, wiring, safety devices, and all other associated works as required. The lift shall be equipped with ARD (Automatic Rescue Device) system of latest technology, suitable for operation in case of power failure. The lift shall serve G+1 floors with a rated speed of 1.0 m/s, complete in all respects as per relevant IS standards/CPWD Specifications. |
| 2 | CAMC of Lift |
| 3 | Comprehensive Annual Maintenance Contract (CAMC) for 1st Year (Included in SITC cost of lift, duration of 1 year as Defect Liability Period), complete as required. |
| 4 | Comprehensive Annual Maintenance Contract (CAMC) for 2nd Year, complete as required. |
| 5 | Comprehensive Annual Maintenance Contract (CAMC) for 3rd Year, complete as required. |
| 6 | Comprehensive Annual Maintenance Contract (CAMC) for 4th Year, complete as required. |
| 7 | Buyback of existing lift including dismantling and taking away from site all components such as guide rails, lift car, counterweight, motor, structural parts, suspension ropes, etc., complete as required. |
| 8 | Electrical Work |
| 9 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulatedcopper conductor single core cable etc. as required. Group A |
| 10 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 11 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 12 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 13 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 14 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 15 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 125 A,36KA,FPMCCB |
| 16 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . 4 way (4 + 12), Double door |
| 17 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. SPMCB (5-32A) |
| 18 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. TP MCB(5-32A) |
| 19 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 20 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 21 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 22 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. Please Enable Macros to View BoQ information |