| 1 | Preliminary works for construction of 1 no. 132 KV D/C tower |
| 2 | Surveying, reconnaissance of terrains, line route, detail survey including check survey, jungle clearance & fixing of stone burjees. Geoglogical investigations and earth resistivity recording along the trans. Line |
| 3 | Design, engineering and Supply of material |
| 4 | Design, Engineering, Supply of Galvanised Tower structure including stubs as per the specifications mentioned in SBD (D+6 type) |
| 5 | Phase Plates 3 No Per Tower for D/C |
| 6 | Number Plates 1 No Per Tower |
| 7 | Circuit Plates 1 No. Per Tower for D/C |
| 8 | Nuts & Bolts |
| 9 | 200 mm² ACSR Conductor,(a) Alumunium=30/3 mm(b) Steel=7/3 mm Overall dia 21mm.Approximate Wt 976Kg/Km Ultimate breaking Load=89.67 KN;including 1.5%sag and jumpering |
| 10 | Mid Span Joints |
| 11 | Vibration Dampers |
| 12 | Repair Sleeves For Conductor |
| 13 | Arching horn |
| 14 | Anti Climbing Device |
| 15 | Aluminium Tape 1 No Per Km Of Line |
| 16 | Long rod polymer insulator 120 KN for 132 KV Transmission Line |
| 17 | Single Tension Fittings for panther shall have minimum failing load of 100% ultimate strength of Bundle cnductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. |
| 18 | Double Tension Fittings for Panther |
| 19 | Tag welding of towers |
| 20 | Earth wire of size 7/3.15 mm |
| 21 | Mis Span Joint for earth wire |
| 22 | Vibration damper for earth wire |
| 23 | Tension clamps for earth wire |
| 24 | Erection, testing and commissioning |
| 25 | Galvanised Tower structure including stubs as per the specifications mentioned in SBD (D+6 type) |
| 26 | Phase Plates 3 No Per Tower for D/C |
| 27 | Number Plates 1 No Per Tower |
| 28 | Circuit Plates 1 No. Per Tower for D/C |
| 29 | Nuts & Bolts |
| 30 | 200 mm² ACSR Conductor,(a) Alumunium=30/3 mm(b) Steel=7/3 mm Overall dia 21mm.Approximate Wt 976Kg/Km Ultimate breaking Load=89.67 KN;including 1.5%sag and jumpering |
| 31 | Mid Span Joints 3 No/Km |
| 32 | Vibration Dampers 2 No/Phase/Tower |
| 33 | Repair Sleeves For Conductor 9 No / Km for D/C |
| 34 | Arching horn |
| 35 | Anti Climbing Device |
| 36 | Aluminium Tape 1 No Per Km Of Line |
| 37 | Long rod polymer insulator 120 KN for 132 KV Transmission Line |
| 38 | Single Tension Fittings for panther shall have minimum failing load of 100% ultimate strength of Bundle cnductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. |
| 39 | Double Tension Fittings for Panther |
| 40 | Tag welding of towers |
| 41 | Earth wire of size 7/3.15 mm |
| 42 | Mis Span Joint for earth wire |
| 43 | Vibration damper for earth wire |
| 44 | Tension clamps for earth wire |
| 45 | Civil Works including material |
| 46 | Design, Engineering of Foundation of D type tower as per Site requirement and specifications laid in SBD |
| 47 | Earthing of Tower as per soil resistivity and site conditions( Normal type /Counter Poise) Please Enable Macros to View BoQ information |