| 1 | Supply, install, testing and commissioning of Diesel Generating Set 320 KVA/256 KW, 3 Phase, 4 wire, 415 Volts, 1500 RPM, 50 Hz, PSO 602 DG Controller, size 5000x1500x2465 mm (LxWxH), power supply with power factor 0.8 (lagging) specially designed to meet stringent MoEF/ CPCB norms of 75 dBA @1mtr at 75% load under free field conditions, CRCA sheets in Munsell green, 11 tank pre-treatment process and UV resistant powder coating to ensure long life in all weather conditions, High quality noise absorbent and fire-retardant grade acoustic Insulation material (Rockwool) IS 8183, Top lifting for easy handling at site, External fuel & DEF filling provision, Compact and Lower Foot Print, AVM Pad mounting type, 60 Litre DEF Tank capacity, 515 Litre standard fuel tank capacity inside enclosure under the base frame, IS/IEC 60034-1, ISO 1460, ISO 8528, ISO 3046, ISO 9001 & ISO 13027 conformance standards, Hospital grade silencer inside canopy with rain cap suitably optimized to meet stringent noise limit, Remote Monitoring System compact & robust device for real time DG status & monitoring, 4G compatible for 24 V DC, report & notification - Alerts & warning, Fuel Theft Alarm, Isolated RS 485 interface, Device location using triangulation. The design of integral acoustic enclosure should be any type approved by national Physical laboratory as per Central Pollution Control Board (CPCB-IV+) latest norms complete with AMF Panel, Fuel Tank, Batteries & Leads, Silencer - Residentia, AVM Pads, First Fill of Lube Oil and Acoustic Enclosure. PCC foundation as per OEM to be paid under srl item no1 above all as specified and as directed of Make Cummins/Kirloskar/Greaves or equivalent with the following specifications :- |
| 2 | Item No 1.00 Contd......./-(A) ENGINE - 6 number of Inline Cylinders, Turbo charged and Intercooled Radiator cooled engine 395 HP, Liquid Cooled (EG Compleat 50:50) cooling suitable for continuous operation generating 320 KVA at 1500 RPM, 415 Volts, 0.8 power factor (lagging) suitable for 50 Hz and compling with performance class of Generator set ISO 8528-5 G2 standard :- (i) Robust and efficient air handling system with Dry type and releaceable paper element air cleaner with restriction indicator and optimized turbocharger for increased altitude capabilities. (ii) 24V electrical starting system consisting of starter motor, charging alternator and 12V, 95AH, 02 Nos cummins pulse value plus battery. (iii) Common rail electronic injection system (CREI) fuel system.. (iv) Electronic type Governor.(iv) Cooling system is designed and tested for 50°C ambient conditions. (v) CK4 type lube oil. (vi) Exhaust pipe size of 6 inch as per site requirement.(vii) Electrical starter motor with soft start engagement feature. (viii) Battery charging alternator |
| 3 | Item No 1.00 Contd......./-(B) ALTERNATOR : HCI444D type alternator frame suitable for continuous operation generating 320 KVA at 1500 RPM, 415 Volts, 0.8 power factor (lagging) suitable for 50 Hz, 3 phase, 4 wire system Brushless type, Screen protected, Revolving field, Self excited alternator. The alternator has the following features : (a) ± 0.1% voltage regulation (max) (b) IP : 23 protection with insulated class H. (c) 40 Deg C Design Ambient Temperature. |
| 4 | Item No 1.00 Contd......./-(C) Controller functions provide :-(i) AMF Functionality is inbuilt(ii) Remote start-stop(iii) Modbus interface (RS485 RTU)(iv) Manual Run/ Off / Auto switch(v) Emergency stop(vi) Configurable glow plug control(vii) Theft proof fuel & DEF filling arrangement(viii) Data Logging : Engine hours, Control hours and upto 5 recent fault codes.(ix) Suitable for sync through External Sync controller |
| 5 | Item No 1.00 Contd......./-(D) Engine Protection/ Warning Functions includes :- (i) Low Lube oil pressure warning/ shutdown. (ii) High coolant temp warning/ shutdown. (iii) Low coolant temperature warning. sensor failure indication (iv) Low and High battery voltage warning (v) Weak battery warning (vi) Fail to crank shutdown.(vii) Low fuel level(viii) Cranking lockout : Control will not allow the starter to engage or to crank the running engine (ix) 4-20mA analog input compatible for oil pressure sensor and fuel level.(x) Maintenance due alarm based on Engine Run Time and due date.(xi) Exercisers scheduler.(xii) Overspeed shutdown. |
| 6 | Item No 1.00 Contd......./-(E) Alternator functions includes :-(i) Loss of AC High and Low AC voltage shutdown.(ii) Over current.(iii) High Voltage.(iv) Sleep mode.(v) Low voltage.(vi) Under / Over frequency. |
| 7 | Item No 1.00 Contd......./-(F) TECHNICAL SPECIFICATIONS OF ACOUSTIC ENCLOSURE FOR CBCP IV(i) Factory Fitted integrated -ACOUSTIC ENCLOSURE Silent DG Set Enclosure with Base frame with integral fuel tank is provided with drain plug, air vent, inlet and outlet connection, level indicator and provision for cleaning.(ii) The enclosure is fabricated out of CRCA sheet of 16 SWG.(iii) Top lifting for easy handling at customer site and Silencer Inside enclosure(iv) Theft proof Fuel & Def filing arrangement(v) Fuel filling arrangement Outside the enclosure(vi) CRAC sheet shall be 11 tank pretreatment process and UV resistant powder coating of all parts to withstand extreme environment.(vii) Enclosure is powder coated (inside as well outside) with a special pure polyester based powder. All internal Nuts and bolt are made of MS and all external Nuts and Bolts are made from stainless steel.(viii) The doors are gasketed with high quality EPDM gaskets to avoid leakage of sound.(ix) The door handles are lockable type.(x) Sound proofing of enclosure is done with high quality PU foam confirming to IS 8183 of 40 mm thickness and destiny at 28 kg /M3.(xi) The rock wool is further covered with fibre glass cloth and perforated powder coated MS sheet.(xii) Specially designed attenuators are provided to control sound at air entry to the container and exit from the container.(xiii) Adequate ventilation is provided to meet air requirement for combustion and heat removal.(xiv) Viewing window is fitted with toughened glass instead of acrylic sheet.(xv) As per CPCB norms with acoustic enclosure the noise level shall be 75 dBA at one meter in absence background noise AT 75% load upto 1000 KVA Please Enable Macros to View BoQ information |
| 8 | Item No 1.00 Contd......./-(F) TECHNICAL SPECIFICATIONS OF ACOUSTIC ENCLOSURE FOR CBCP IV(i) Factory Fitted integrated -ACOUSTIC ENCLOSURE Silent DG Set Enclosure with Base frame with integral fuel tank is provided with drain plug, air vent, inlet and outlet connection, level indicator and provision for cleaning.(ii) The enclosure is fabricated out of CRCA sheet of 16 SWG.(iii) Top lifting for easy handling at customer site and Silencer Inside enclosure(iv) Theft proof Fuel & Def filing arrangement(v) Fuel filling arrangement Outside the enclosure(vi) CRAC sheet shall be 11 tank pretreatment process and UV resistant powder coating of all parts to withstand extreme environment.(vii) Enclosure is powder coated (inside as well outside) with a special pure polyester based powder. All internal Nuts and bolt are made of MS and all external Nuts and Bolts are made from stainless steel.(viii) The doors are gasketed with high quality EPDM gaskets to avoid leakage of sound.(ix) The door handles are lockable type.(x) Sound proofing of enclosure is done with high quality PU foam confirming to IS 8183 of 40 mm thickness and destiny at 28 kg /M3.(xi) The rock wool is further covered with fibre glass cloth and perforated powder coated MS sheet.(xii) Specially designed attenuators are provided to control sound at air entry to the container and exit from the container.(xiii) Adequate ventilation is provided to meet air requirement for combustion and heat removal.(xiv) Viewing window is fitted with toughened glass instead of acrylic sheet.(xv) As per CPCB norms with acoustic enclosure the noise level shall be 75 dBA at one meter in absence background noise AT 75% load upto 1000 KVA Please Enable Macros to View BoQ information |