| 1 | Internal Electrification: 1.10: Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.1.10.1 Group A |
| 2 | 1.10.2 Group B |
| 3 | 1.10.3 Group C |
| 4 | 1.14: Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.1.14.1.2. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 5 | 1.14.2.2. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 6 | 1.14.3.2. 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 7 | 1.14.4.2. 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 8 | 1.14.10. 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 9 | 1.24: Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.1.24.1. 5/6 A switch |
| 10 | 1.24.3. 15/16 A switch |
| 11 | 1.24.4. 3 pin 5/6 A socket outlet |
| 12 | 1.24.5. 6 pin 15/16 A socket outlet |
| 13 | 1.24.8. Bell Push |
| 14 | 1.25: Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 15 | 1.27: Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.1.27.2 3 Module (100mmX75mm) |
| 16 | 1.27.3 4 Module (125mmX75mm) |
| 17 | 1.27.4 6 Module (200mmX75mm) |
| 18 | 1.27.5 8 Module (125mmX125mm) |
| 19 | 1.27.6 12 Module (200mmX150mm) |
| 20 | 1.28: Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.1.28.2 3 Module |
| 21 | 1.28.3 4 Module |
| 22 | 1.28.4 6 Module |
| 23 | 1.28.5 8 Module |
| 24 | 1.28.6 12 Module |
| 25 | 1.38: Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. |
| 26 | 2.2: Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.2.2.15 200 A, 36 KA, FGPMCCB |
| 27 | 2.2.16 250 A, 36 KA, FGPMCCB |
| 28 | 2.2.18 400 A, 50 KA, FGPMCCB |
| 29 | 2.2.19 630 A, 50 KA, FGPMCCB |
| 30 | 2.5: Supplying and fixing of followingf ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, commmon neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note: Vertical type MCB TPDB is normally used where 3 phase outlets are required).2.5.1 4 way, (4 + 12), Double door. |
| 31 | 2.10: Supplying and fixing 5A to 32A rating, 240/415V 10KA C curve, MCB suitable for inductive load of following pole in the existing MCB DB complete with connections, testing and commissioning etc. as required.2.10.1. Single pole |
| 32 | 2.13: Supplying and fixing following rating, four pole 415V isolator in the existing MCB DB complete with connection, testing and commissioning etc. as required.40 A |
| 33 | 2.14: Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.2.14.2 40 A |
| 34 | 2.14.3 63 A |
| 35 | 5.2: Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 36 | 5.7: Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. |
| 37 | 6.2: Providing and fixing of lighting conductor finial made of 25mm dia 300mm long GI tube having single prong at top with 85mm dia thick GI base plate including holes etc. complete as required. |
| 38 | 6.4: Jointing copper/ G.I tape (with another copper/ G.I tape, base of the final or any other metallic object) by riveting/ nut bolting/ sweating and soldering etc. |
| 39 | 6.7: Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet orsurface of wall for lightning conductor complete asrequired.(For horizontal run) |
| 40 | 6.8: Providing and fixing GI tape 20 mm X 3 mm thick on parapet or surface of wall for lighting conductor complete as required( For vertical run) |
| 41 | 7.1: Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.7.1.1 Upto 35 sq.mm |
| 42 | 7.1.2 Above 35 sq.mm and upto 95 sq.mm |
| 43 | 7.1.4 Above 185 sq.mm and upto 400 sq.mm |
| 44 | 7.4: Laying of one number additional PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size direct in ground in th same trench in one tier horizontal formmation including excavation and refilling the trench etc as required, but exceeding sand cushioning and protective covering.7.4.2 Above 35 sq.mm and upto 95 sq.mm |
| 45 | 7.1.4 Above 95 sq.mm and upto 185 sq.mm |
| 46 | MR-1: Supplying with including fitting fixing of 20 W three colour CCT change LED batten etc. as required and directed by the Deptt. |
| 47 | MR-2: Supplying with including fitting fixing of Aesthetically designed recessed mounted panel in a light weight plastic body available in LED 20 W etc. as required and direction by the Deptt. |
| 48 | MR-3: Supplying with including fitting fixing of ceiling Fan (1200 mmm) Swift 1 Star etc. as required and as directed by the Deptt. |
| 49 | MR-4: Supplying with including fitting fixing of Metal Exhaust Fan (300 mm) Aeroclean LD GBD etc. as required and as directed by the Deptt. |
| 50 | MR-5: Supplying with including fitting fixing of Wall Fan (400 mm) Mist Air Ultra etc. as required and as directed by the Deptt. |
| 51 | MR-6: Supplying of following size PVC/ XLPE insulated and PVC sheathed 1.1 KVC Gd. Solid Aluminium conductor up to 10 sqmm, balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, Armour (Aluminum wire for single core up to 70 sq. mm, balance Aluminum strip, Galvanished wire for cables up to 2 x 10 sq. mm, 3 x 10 sq.mm, 4 x 6 sq.mm & balance all galvanized stell strip), extruded PVC Type ST2 sheathed, 650/1100 V grade as per iS 7908 (Part-I) 1988 armoured U.G. cable as specified and directed by the Deptt. (Havells, RR or equivalent make as approved by this Deptt.) Considering 100 Mtr. length).(ii) 120.00 sq.mm 3 & 1/2 Core U.G. Cable |
| 52 | (iii) 300.00 sq.mm 3 & 1/2 Core U.G. Cable |
| 53 | MR-7: Design, fabrication &v supply of floor mounted compartmentalized dust and vermin proof Power Distribution Panel board (L.T-3 ph, 415 V, 630 Amp) made of M.S. sheet of not less than 16 swg duly welded & Powder Coated with Grey colour to both in interior & exterior. All wiring for control & metering shall be done by multistranded PVC insulated Finolex make single core copper flexible cable of not less than 1.5 sq.mm. Size and will be properly harnessed and drawn neatly clamped for incoming & out going cables, 4 (Four) separately electrolytic grade aluminum busbar (3 phase & Neutral) of 630 A will be layed in separate chamber. All the outgoing cable of the MCCB/MCB up to cable alley connector shall be connected by flat/round/flexible Copper cable etc. |
| 54 | MR-8: Design, fabrication & supply of floor mounted compartmentalized dust and vermin proof Power Distribution Panel board (L.T-3 ph, 415 V, 400 Amp) made of M.S. sheet of not less than 16 swg duly welded & Powder Coated with Grey colour to both in interior & exterior. All wiring for control & metering shall be done by multistranded PVC insulated Finolex make single core copper flexible cable of not less than 1.5 sq.mm. Size and will be properly harnessed and drawn neatly clamped for incoming & out going cables, 4 (Four) separately electrolytic grade aluminum busbar (3 phase & Neutral) of 400 A will be layed in separate chamber. All the outgoing cable of the MCCB/MCB up to cable alley connector shall be connected by flat/round/flexible Copper cable etc. |
| 55 | MR-9: Design, fabrication & supply of floor mounted compartmentalized dust and vermin proof Power Distribution Panel board (L.T-3 ph, 415 V, 400 Amp) made of M.S. sheet of not less than 16 swg duly welded & Powder Coated with Grey colour to both in interior & exterior. All wiring for control & metering shall be done by multistranded PVC insulated Finolex make single core copper flexible cable of not less than 1.5 sq.mm. Size and will be properly harnessed and drawn neatly clamped for incoming & out going cables, 4 (Four) separately electrolytic grade aluminum busbar (3 phase & Neutral) of 300 A will be layed in separate chamber. All the outgoing cable of the MCCB/MCB up to cable alley connector shall be connected by flat/round/flexible Copper cable etc. |
| 56 | MR-10: Design, fabrication & supply of floor mounted compartmentalized dust and vermin proof Power Distribution Panel board (L.T-3 ph, 415 V, 160 Amp) made of M.S. sheet of not less than 16 swg duly welded & Powder Coated with Grey colour to both in interior & exterior. All wiring for control & metering shall be done by multistranded PVC insulated Finolex make single core copper flexible cable of not less than 1.5 sq.mm. Size and will be properly harnessed and drawn neatly clamped for incoming & out going cables, 4 (Four) separately electrolytic grade aluminum busbar (3 phase & Neutral) of 200 A will be layed in separate chamber. All the outgoing cable of the MCCB/MCB up to cable alley connector shall be connected by flat/round/flexible Copper cable etc. |
| 57 | (B) Decorative LED Street light, Bollard light & 500 KVA D.G. set with Pad:MR-11: Supplying with fiting & fixing of highly effective front openable 90W IP66 Street light/ Campus light with aluminium pressure dia-cost housing, toughened glass in the front and peanut lens for batwing light distribution to ensure uniform light distribution, higher spacing between poles and maintenance free system etc. as rewuired and as directed by the Department (Orient, Bajaj, havells or equivalent make). |
| 58 | MR-12: Supplying with installation of 5.5 Mtrs. Height decorative pole with double bracket, SDP CID 5.5 M DOB with 40 W Post Top Lamp as required and directed by the Deptt. |
| 59 | MR-13: Supplying including fitting fixing of 10 W LED Bollard light (IP65) with robust design and efficient light distribution etc. as required and directed by the Deptt. |
| 60 | MR-14: Supplying of following size PVC/XLPE insulated and PVC sheathed 1.1 KV Gd. Solid Aluminium conductor up to 10 sqmm, balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, Armour (Aluminium wire for single core up to 70 sq. mm, balance Aluminium strip, Galvanised wire for cables up to 2 x 10 sq. mmm, 3 x 10 sq. mm, 4 x 6 sq. mm & balance all galvanized steel strip), extruded PVC Type ST2 sheathed, 650/1100 V grade as per IS 7908 (Part-I) 1988 armoured U.G. cable as specified and directed by the Deptt. (Havells, RR or equivalent make as approved by this Deptt.) Considering 100 Mtr. length)(i) 10.00 sq.mm 2 Core U.G. Cable |
| 61 | MR-15: Supplying, installation, testing and commissioning of 500 KVA/440 KW Jakson make SILENT & COOLANT Cooled DG set comprising Cummins engibne model QSM15-G1 developing 594 BHP at 1500 rpm duly coupled with Cummins make 500 KVA/ 415V (3 Phase) Stamford alternator mounted on a Common MS channel base fram including Standar Manual Panel, 745 Lt. Fuel Tank, 87 Ltr DEF Tank, Battery with leads, and with Acoustic Enclosure, (CPCB IV+) etc. as required and disrected by the Department. |
| 62 | MR_16: Supplying with fitting fixing of 800 A Change Over Switch (4 Pole) I-0-II (Manual Range) ISI approved inclusding all necessary connection etc. as required and as directed by the Department. |
| 63 | MR-17: Supplying with fitting and fixing of 3 H.P. V4 Submersible Pump set (Water Filled Motor)- 100W Series (2.2-5.5 KW) as required and directed by the department. (Crompton/ Kirlosker/ Usha or equivalent make). |
| 64 | CPWD(B) 2021/1.2.2: Construction of D.G. Pad with G.C.I. Roofing Shed M.S. Iron structure A-Type (Size= 4.5 m x 6 m) 35.0 Sq.m. Please Enable Macros to View BoQ information |