| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. a) Group C |
| 2 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 3 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 4 | b) 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 5 | Supplying and fixing metal box of 150mm X 75mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 3 pin 5/6 A socket outlet and 5/6 A piano type switch, connections, painting etc. as required |
| 6 | Supplying, Installation, Testing and Commissioning of 1 x 4' CRCA housing Box type luminaries suitable for T8 LED Tube (1 x 18 / 20W) similar to Bajaj Model No. BLRB-DB 118 or its equivalent make etc., as required. |
| 7 | Supplying of 20W LED Tube Light with Polycarbonate housing designed for high performance similar to Bajaj Model No. BLRB 20W CW LED or its equivalent etc., as required. |
| 8 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.a) Single Pole |
| 9 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.a) 40 A |
| 10 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) a) 6 Way, Double Door |
| 11 | Providing earthing with safe earthing electrode of galvanization 80 to 100 microns, length 2 mtr, outer dia 50 mm, inner dia 19 mm and inner space be filled with crystalline conductive mixture including filling -up with electrolite (Back fill compound) as required for safe earth electrode and providing masonary enclosure with cover plate having locking arrangement etc. as required. (Ashlok)(Proof/ Test Certificate should be enclosed) |
| 12 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 13 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. Please Enable Macros to View BoQ information |