| 1 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required. |
| 2 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required |
| 3 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 4 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm. |
| 5 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal). |
| 6 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. |
| 7 | Supply of PVC insulated and FR PVC Sheathed multicore copper conductor 1.1KV grade, conforming to grade IS 694 as required . 3*1.5 Sq.mm |
| 8 | Supply of XLPE insulated,PVC sheathed Al.conductor Armoured Cable 1.1 KV grade Conforming to IS 7098/1988 of following Sizes 2 X10 SQmm |
| 9 | Supply of XLPE insulated,PVC sheathed Al.conductor Armoured Cable 1.1 KV grade Conforming to IS 7098/1988 of following Sizes 4X25 sqmm. |
| 10 | Supply of XLPE insulated,PVC sheathed Al.conductor Armoured Cable 1.1 KV grade Conforming to IS 7098/1988 of following Sizes 4X16 sqmm. |
| 11 | Drilling and laying i/c HDPE pipe of 40 mm outer dia with PN 4 rating by trenchless technology Confirming to IS 4984. |
| 12 | Supply and fixing of 50 watt IP65 decorative single piece LED fixtures with die cast aluminium housing frosted PMMA / PC diffuser, suitable for upward mounting with power LEDs white/warm white fitted with suitable extruded aluminium heat sinks, high voltage protection and suitable constant current LED driver extra as required. Technical Particulars i) Size of fiiting- 580mm x 340mm, base section inner dia 64mm and outer dia- 71mm ii) Total power of light fixture- 50 Watt iii) Input voltage-AC 120 to 270volt 50Hz iv) Power factor 0.95 v) Minimum lumen output of LEDs - 100 Lumen per watt vi) Luminaire protection - IP65 |
| 13 | S.I.T.C of Hot Press moulded SMC panel/Canopy Box of size(OD) 920 mm x 460 mm x 260 mm & (ID) 900 mm x 450 mm x250 mm , anti – corrosive, dust proof, rust proof, shock proof , Self-extinguishing property , resistant to heat , Vermin proof, Ultra Violet stabilized, Pilfer resistant, Suitable for mounting 1 no. 3 phase Starter, 1 no. 63 Amp 4 pole isolator and 1 no. 3 phase Energy meter, Socket for outgoing connection with pilferage proof SMC door duly welded with S/S handle having danger logo on its outer surface and with 1 no Hot Dip galvanized iron stand for a base of size 40 mm x 40 mm x 5 mm and height of the stand is 600 mm including 300 mm height below the ground with side strip of size 25 x 5 mm. |
| 14 | SITC of Pillar box size 900 mm x 450mm x 250mm suitable for mounting incomer of 250 A MCCB/Main switch 4 Pole and energy meter 3 phase complete with eleethoypic grade Aluminium bus bar of size 25mm x 19 mm mounted on galvanized M. S. body power quoted pilferage proof SMC door duly welded with S.S. with rain cover size 40mm x 40mm x 5mm x 600mm height in cutting 300 mm height below ground and covered with shade proof SMC sheet of 3 mm as required. |
| 15 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.100Amp, 30KA, FPMCCB. |
| 16 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A |
| 17 | Supplying and fixing 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double pole |
| 18 | Supplying and fixing 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole |
| 19 | P & F of following sizes top cover/ Cap of 6mm thick MS plate i/c locking arrangement etc as reqd. (a) 150 mm dia |
| 20 | S&F MS clamp made up of iron flat of size 50mmx 6 mm with 4 nut bolt for holding the 150 mm to 250 mm dia pipe etc as reqd. |
| 21 | Providing and laying cement concreat 1:2:4 mix for sanitary sealing of well at top of 450mmX 450mmX 500 mm deep from top comp as reqd. |
| 22 | Development of tube well with suitable capacity of air compressor i/c lowering of the necessary induction pipe or line i/c cost of fuel, hire charges of compressor etc as reqd. The development shall be considered complete when Gravel stop sinking, Discharge ceased to improve and the sand contents are not more than 10 PPM after 20 minutes of starting the pump complete as required. |
| 23 | Supplying, lowering, testing and commissioning of vertical type, multistage, totally enclosed water filled deep well submersible pumping set complete i/c connection etc. as reqd. Three Phase 5.0 HP having discharge of 300 LPM Approx. at 39 M Head |
| 24 | Supplying and fixing following sizes of insulated steel flexible safety rope for holding submersible pump set i/c clips etc complete as reqd. (a) 10 mm dia |
| 25 | P&F following sizes of PVC insulated & PVC sheathed copper conductor 3 core submersible cable confirming to IS.694/1990 etc. as reqd. (a) 3 X 6 sq.mm. |
| 26 | Supply, lowering and fixing following size of G.I.Pipe (M-Class) i/c cutting threading on both sides etc. ISI marked etc as reqd. (a) 40mm (Nominal bore) |
| 27 | S & F following sizes of GI Elbow as required 40 mm dia |
| 28 | S & F following sizes of GI Socket as required. 40 mm dia |
| 29 | S & F following sizes of GI Union as required.40 mm dia |
| 30 | S&F MS clamp made up of flat iron of size 50mmx 6 mm with 4 nut bolt for holding the G.I.Pipe from 40 mm to 65 mm dia pipe etc as reqd. |
| 31 | Supply, Installation, testing and commissioning of cubical type control panel board for single phase & Three Phase submersible pumping set of following rating complete with contactor, relay , MCB ,condenser ,voltmeter, ammeter and indication lamp etc including connections etc as required. (a) 5 H.P rating Submersible P/Set. |
| 32 | Providing and Fixing of Flexible LED Strip light fixtures suitable for rated voltage 220 Volt 50 HZ supply, in White/Green/Red/Warm White Color including all accessories like connectors, Endcap, Holding Cap and Connector Pins but excluding integrated LED adaptor etc as required. |
| 33 | providing and Fixing of integrated LED adaptor for flexible LED strip light fixture suitable for rated voltage 220 volts 50 HZ supply etc as required. |
| 34 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 and <135 lm/Watt).Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). 50 watt |
| 35 | Fabrication, supply & erection of 5.0 mtr height, minimum 3 mm thick, bottom dia of 130mm & top dia of 70mm base plate of size 225 x 225 x 12 mm thick flange mounted hot dip galvanized octagonal pole made from HT steel plate, window with flash cover with full verticle window cover at appropriate height from the base plate on existing cement concrete pedestal as required. i/c supplying and fixing of 6 mm thick laminated mounted sheet inside the window mounted on and i/c providing and welding 3 nos. GI strips 4 mm thick of suitable length and having suitable size tapped holes as reqd, terminal block suitable for 25 sq mm conductor – 4 nos. & shorting links on DIN channel i/cpdg and fixing DIN channel of suitable length,, 6 Amp. SPMCB ‘C’ characteristics, earth stud, cable support clamp suitable for 4x25 sqmm cable.Logo/Name of manufacturer shall be embosed on the pole, galvanization as per relevant IS codde etc as required. |
| 36 | Providing and laying in position M25 grade reinforced cement concrete foundation of size 450 mm (L) ×450 mm wide and 1000 mm deep i/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm dia- 960 mm long(approx)-8 nos. and reinforcement of cold twisted bars of 8 mm dia- 1400 mm (approx) -6 nos.(with 150 mm spacing) as required with supplying and positioning of 4 nos. foundation bolts 16 mm dia,600 mm long, J type i/c 2 nos. template anchor plates of size 225mm×225mm×3mm and providing DWC HDPE for cable entry and exit as required for 3 m and 5 mtr pole. |
| 37 | Fabrication, supplying and fixing class B galvanised double overhang arm bracket made out of 250 mm long galvanized top tube with cap and 250 mm long 32 mm dia galvanized pipe with tightening bolts complete as required. |
| 38 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥120 <135 lm/Watt) Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as er IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) 45 watt |
| 39 | Providing and Fixing name board made of MS Sheet 90x60 cm , 1mm thick with frame of MS angle 50x50x6mm, two diagonal braces at the back of the sheet of MS flat 40x6mm, total height of the board above ground level 2.40m, length of legs below ground 0.30m embeded in CC block 1:2:4(1 cement : 2 coarse sand: 4graded stone aggregate 20mm nominal size) 30x30x45cm including excavation and removal of surplus earth with in 50m lead, applying primary coat of approved steel primer, painting with synthetic enamel point of approved quality and lettering with enamel paint of approved colour (one side) as per drawing /direction of Engineer in charge. Please Enable Macros to View BoQ information |