| 1 | Supply and erection of SwitchDisconnector Fuse Unit with HRC Fuses(Suitable for DIN HRC Fuses) in sheetenclosure on the existing surfaceConfirms to IS 13947 (Part-III), IEC 60947-3 complete with G.I. Bolts, Nuts &Connections on both sides of switchwith suitable size of thimbles, includingcost of DIN HRC fuses as per PWDGeneral Specifications:-SDF TP&N 630Amp., 415volts (With SheetEnclosure) |
| 2 | SDF TP&N 400Amp., 415volts (With SheetEnclosure) |
| 3 | Supply and erection of On Load Changeover Switch with advance neutral UNIT(Panel mounting Cubical type) in theexisting Cubical Panel Confirms to IS13947 (Part-3) complete with G.I. Bolts,Nuts & Connections on both sides ofswitch with suitable size of thimbles asper PWD General Specifications:-On Load Change Over Switch Four Pole800amp., 415volts |
| 4 | Supply and erection of PVC insulated FRsingle core Unsheathed copperconductor cable (ISI marked) suitableupto 1100 volts grade confirm toIS:694/1990 left bare in pipe or casing ofsuitable size complete in all respect asdesired by the Engineer-in-charge:-Overall size 2.5sq.mm (Un-sheathed) |
| 5 | Overall size 4sq.mm (Un-sheathed) |
| 6 | Overall size 10sq.mm (Un-sheathed) |
| 7 | Designing, Supply, Erection, Testing &commissioning of indoor Type LT cubical panelenclosure (dust, vermin and interchangeablemodules with facilites for extensions or reduction as per the space or requirments). The Panel shall be suitable for operation at 415+6% Volts, 50HZ, 3 phase 4 wire & earth system. The assembly manufacturer should be ISO approved and CPRI tested for short circuit of (minimum 50kA) as well as IP degree of protection (IP 54/55). Fabrication:- Panel shall be made from 14/16 SWG CRCA sheet, conforming to IS 8623/1977-82. The sheet metal used for the fabrication of controlpanel will be 2mm for load bearing member’s door and fittings plates etc. the partitions and other non load bearing members will be fabricated out of 1.6mm sheet, the sheet will be of mild steel CRCAtype. The base channel will be made out of 75 x 40 x 5mm rolled channel.-LT Panel enclosure having space for 1No.Incomer MCCB 630Amp. and 6Nos.outgoing MCCB's 40amp. to 250amp.(Option: MCCB 200-250amp.= 1No. andMCCB's 40-100amp.= 5Nos.) according tothe requirement at site (Approx. size 1475 x1800 x 400mm) |
| 8 | Supply and erection of Moulded CaseCircuit Breaker (Panel mounting Cubicaltype) in the existing Cubical Panel(confirm to IEC:60947-2) havingIcs=100% Icu, 100% neutral withspreader terminal links, Extended rotaryhandle and relevant PWD generalspecifications complete with G.I. Bolts,Nuts & Connection on both sides ofMCCB with suitable size of thimbles etc:-MCCB Four Pole 630amp., 415volts, ≥36kAMicroprocessor Based Adjustable Thermaland Magnetic Setting |
| 9 | Supply, laying and erection of aluminiumconductor XLPE insulated PVC sheathedarmoured and served cable 1100 voltsgrade as per IS:7098 (Part-1)1988 to belaid (On Surface) as per PWD GeneralSpecifications:-Overall size 300sq.mm (3½ Core) Armoured(On-Surface) |
| 10 | Overall size 150sq.mm (3½ Core) Armoured(On-Surface) |
| 11 | Overall size 95sq.mm (3½ Core) Armoured(On-Surface) |
| 12 | Supply & erection of PVC Conduit Pipes(ISI marked) as per IS9537:Part-III &HDPE pipes (ISI marked) as perIS:4984:1995 for wiring purposesincluding bends, junction boxes, Steelhooks, M.S. saddle clamps and otherpetty materials etc., as per PWD GeneralSpecifications:-HDPE Electrical Conduit Pipe 20mm dia.(On Surface) |
| 13 | Supply and erection of PVC flexible pipecomplete without compression glands,locking arrangement, check-nuts asrequired:-PVC Flexible Pipe 20mm dia. |
| 14 | Supply and erection of Miniature CircuitBreaker MCB's for circuit protectionagainst overload and short circuitcurrent fault suitable for 240/ 415 volts50cycles AC supply with breakingcapacity of 10kA, Curve-C and low wattlosses as per IS/IEC 60898-1, energylimitation class-3, true contactindication, label holder facility in theexisting MCB distribution board as perPWD General Specifications includingconnections with suitable size ofthimbles/lugs:-MCB Single Pole 6-32amp. (10kA, Curve-C) |
| 15 | MCB Double Pole 6-32amp. (10kA, Curve-C) |
| 16 | MCB Four Pole 50, 63amp. (10kA, Curve-C) |
| 17 | Providing and fixing commercial plywood18mm thick |
| 18 | Cutting chase in brick walls in cement or infloor for embedding G.I. or C.I pipes line andmaking good the same to its original condition.-Size 75 mm x 75 mm |
| 19 | Providing, Laying , fixing & jointing of P.V.C.Pipes as per ISI-4985 (ISI marked with theprior approval of Engineer-in-Charge) alongthe Trenches and laying the same inTrenches to correct alignment and gradients,cutting, jointing and testing complete as perspecifications.75mm o/d pipe of 6 Kgf. / sqcm |
| 20 | Providing, laying, jointing, fixing and testingISI Marked uPVC Pipe with G.I. specials asper ISI-4985, including cost of G.I. specialssuch as tees, bends, sockets, elbows etc.testing inside building complete.uPVC Pipe 10 Kgf/cm2 -20mm i/d |
| 21 | Wall painting with plastic emulsion paint ofapproved brand and manufacturer to give aneven shade (two or more coats) |
| 22 | 12.5 mm thick cement plaster 1:4 |
| 23 | Cutting holes upto 23cm square for pipes infloor and roofs of cement concrete, reinforcedconcrete or reinforced brick work and makinggood the same & finishing according toexisting finish where required.Through floor or roof 11.5cm thick Please Enable Macros to View BoQ information |