| 1 | Fire Fighting |
| 2 | 18.4.2:(a) Supplying, installation, testing and commissioning of electric driven450lpm at 35m Head |
| 3 | OD46302/2025-2026:erection, testing and commissioning of Automatic Motor Control Panel for the electric driven terrace pump, with DOL Starters, switch gear and contactors shall be rated for motor HP. The panel shall include necessary indicating lamps for the RYB phases, ammeters and volt meter with selector switch. etc. The panel shall have Auto/Manual Selector Switch. The panel shall be powder red in color and shall have provision for wall mounting with all accessories as required complete. |
| 4 | 18.8.6:Providing, laying, testing and commissioning of C class heavy duty GI pipe conforming to IS 1239, i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required.80 mm |
| 5 | 18.8.7:Providing, laying, testing and commissioning of C class heavy duty GI pipe conforming to IS 1239, i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required.100 mm |
| 6 | 18.11.5:Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts ,washers ,gaskets conforming to IS 13095 of following sizes as required:100 mm dia |
| 7 | 18.14.5:Providing,installation,testing and commissioning of non-return valve of following sizes conforming to IS :5312 complete with rubber gasket, GI bolts , nuts, washers etc as required.100 mm dia |
| 8 | OD103072/2025-2026:Supply , installation ,testing commissioning of 25 mm dia Gun metal air release valve |
| 9 | 18.22:Providing and fixing of pressure switch in MS pipeline including connection etc as required: |
| 10 | OD103215/2025-2026:Supply and providing pressure gauge in the existing system as required |
| 11 | OD103223/2025-2026:Supply , installation ,testing commissioning of 25 mm dia cast iron body ball valve as per IS 5312 with ISI |
| 12 | 18.9.1:Supplying and fixing single headed internal hydrant valve with instantaneous Gun metal or stainless steel coupling of 63mm dia with cast iron wheel ISI marked conforming to IS 5290(Type A) with blank Gun metal or Stainless steel cap and chain as required:Single headed Gunmetal |
| 13 | 18.16.2:Supplying and fixing 63 m dia,15m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required: Stainless steel (Grade 304) |
| 14 | 18.18.2:Supplying and fixing 63 mm dia gun etal short metal branch pipe ith 20 mm nominal interanal diameter size nozzle conforming to IS 903 suitable for Instantaneous connection to Interconnect hose pipe coupling as required:Stainless steel (Grade 304) |
| 15 | OD104743/2025-2026:Supplyingand fixing of hose cabinet fabricated from 2 mm thick MS sheet with 6 mm thick glazed front doors and looking arrangements suitable for accommodate internal accommodate of 2 nos of 15 mtrs long hose pipe , 1 no branch pipe, fittings etc. the cabinet shall be painted with one coat of primer and 2 coats of synthetic enamel paint of post office red externally and white internally and shall be suitably mounted on concrete base. |
| 16 | 18.17.1:Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.a) 20 mm nominal Internal dia water hose thermoplastic(Textile reinforced) type-2 as per IS:12585b) 20 mm nominal internal dia gun metal globe valve &nozzlec) Drum and brackets for fixing the equipments on wall.d) Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.30 m |
| 17 | 17.1.9.2:Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections, interconnections as required.6 Zone |
| 18 | OD104842/2025-2026:Supply installation testing and commissioning of 6 Zone Automatic Fire Alarm Control panel conventional type micro processor based control made of MS sheet cabinet the powder coated, audio and digitel visual display, circuit open short functions, test/evaqvation mode, silience and reset options, common and zone wise hooter supply outputs, fault and fire mode auxilary contacts with 24 DC volt out put zone circuits, operating 230 / 50 Hz AC volts. |
| 19 | 17.5.2:CABLING & WIRINGSupplying & laying of 2x1.5 sq mm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
| 20 | 17.1.8:FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning talk back slave station in surface/ recess suitable for operation on simplex mode complete with P.T.T. knob & speaker/ microphone enclosed in a M.S.(16 SWG)/ ABS box with break glass in front etc. complete as required. |
| 21 | OD104888/2025-2026:FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning of manual call boxes of MS Construction in surface/recess with stainless steel chain & hammer assembly Complete with glass and push button etc. as required. |
| 22 | OD104906/2025-2026:Supply installation testing and commissioning of Audio alarm hooter ( sounder ) powder coated MS/ABS box fix on existing wall/frame, 24/12 Volt DC operated siren circuit with diaphram speaker, maxium sound 60 db intensity under stautory with necessary attachments. |
| 23 | 90.12.7.13:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 6 sq mm with factory made clamp |
| 24 | 90.12.39.6:Supply & laying of one number PVC insulated and PVC sheathed armoured copper power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3 core 6 sq mm |
| 25 | 90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp |
| 26 | 90.12.39.33:Supply & laying of one number PVC insulated and PVC sheathed armoured copper power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm |
| 27 | 90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size |
| 28 | 9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm) |
| 29 | OD112263/2025-2026:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 6 sq. mm (20mm) |
| 30 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 31 | 90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG) |
| 32 | 18.19.1:Supplying and fixing fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia M.S. Pipe connection conforming to IS 904 as required:2 way-100 mm dia M.S.Pipe |
| 33 | OD105686/2025-2026:Supply & installing in position laminated sheet of FIRE EVACUATION PLAN of suitable size fixed on wall & necessary accessories to fix the plan on wall |
| 34 | OD105861/2025-2026:Supply installing in positionLED FIRE EXIT sign boards of suitable size with battery backup |
| 35 | OD105871/2025-2026:Supply erection of Assembly Point sign board 16x16 |
| 36 | OD106356/2025-2026:Supply and providing ABC type fire extinguisher 6 kg capacity with installation brackets conforming to IS 15222 as required |
| 37 | OD106382/2025-2026:Supply and providing emergency fire escape lighting system consisting 2 nos lamp ,7 AH MF battery charging unit ,exit sign display etc in MS enclosure |
| 38 | OD106473/2025-2026:Supply and providing Glow SIgn boards of 3mm PVC foam board. |
| 39 | OD106477/2025-2026:Charges for preparation of electrical/fire and drawing per A3 sheet first copy |
| 40 | OD106487/2025-2026:Charges for preparation of electrical/fire and drawing per A3 sheet additional copy |
| 41 | 90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame) |
| 42 | 90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc. |
| 43 | 90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet |
| 44 | 90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required. |
| 45 | 90.14.7:Supply and providing copper earth bus in the panel board |
| 46 | OD112320/2025-2026:Supplying and fixing LED indicators for all Voltage ranges- Red Green Black Yellow or Orange Colour |
| 47 | OD112703/2025-2026:MCCB Accessories Supply and fixing one number Earth Leakage Relay 240-415V AC with CBCT- (Moulded case) for Type A & AC Current. |
| 48 | OD112326/2025-2026:supply and fixing Digital Multifunction meter to read: V, A, F, PF-3 phase accuracy class 1 LED |
| 49 | OD112403/2025-2026:Supplying and fixing 2 amps rating, 240 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole |
| 50 | OD112726/2025-2026:Supply and wiring with PVC insulated stranded single core copper conductor cables for interconnecting the control devices/ equipments including the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required. 1.00Sqmm single run |
| 51 | OD112728/2025-2026:Supply and wiring with PVC insulated stranded single core copper conductor cables for interconnecting the control devices/ equipments including the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required. 4.00Sqmm single run |
| 52 | 2.1.1:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.32 Amp TP & N |
| 53 | 2.1.2:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.63 Amp TP & N |
| 54 | 90.14.10.12:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.160A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC |
| 55 | OD115726/2025-2026:Supply and fixing of spreader/ terminal adapter kitextended terminal for 4 pole MCCB of rating up to 160A (8pcs)and giving connections etc as required. |
| 56 | OD115512/2025-2026:Supply and fixing 250/5 A, 5 VA, accuracy class 1, Tape wound Metering CT |
| 57 | 5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 58 | OD112974/2025-2026:Providing and fixing 2 X 25 mm X 3 mm G.I. strip test joint for earthing system |
| 59 | OD112975/2025-2026:Providing and fixing 25 mm X 3 mm G.I. strip earth lead from the test joint to the earth plate |
| 60 | OD112983/2025-2026:Supply and providing 25x6mm brass nut and bolt etc. as required. |
| 61 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 62 | OD113907/2025-2026:Charges for dismantiling the existing Panel Board , making good the damages of walls and conveying the dismantled materials to section store. Please Enable Macros to View BoQ information |