| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GE (ARMY) AHMEDABAD NAME OF WORK : SPECIAL REPAIR AND REPLACEMENT OF MCCB, DB, EARTHING, BUS BAR PANEL AND OTHER E/M ELECTRICAL SUPPLY RELATED WKS AT GE (A) AHMEDABAD CONTRACT AGREEMENT: GE (A)/ABD/ OF 2026-2027 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description of Item of Work Item Code / Make Quantity Unit Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT (in Words) |
| 2 | Supply and fixing in replacement of following accessories installed in existing panel (Indoor/Outdoor) including making in coming / out going electric connections complete all as specified and directed with suitable size of copper wire:- |
| 3 | MCCB Four pole 250 Amp, 36/35kA, 415 V, Thermal magnitc adjustable type including over load and short circuit protection, 415 Volts as per existing make & model |
| 4 | All as above but rating FP 200 Amp, 36 kA,as per existing make & model |
| 5 | All as above but rating FP 160 Amp, 36 kA ,as per existing make & model |
| 6 | All as above but rating FP 125 Amp, 25 kA, as per existing make & model |
| 7 | All as above but rating FP 100 Amp, 16 kA,as per existing make & model |
| 8 | All as above but rating FP 63 Amp, 16 kA, as per existing make & model |
| 9 | All as above but rating TP 100 Amp , 16kA. as per existing make & model |
| 10 | Supply, Installed & fix maintenance free earthing copper bonded steel earth rod of 10 feet long having diameter of 17.2mm with copper bonding thickness of 250 micron,UL listed,CPRI Tested at 25 KA fault current for one second and is provided with universal clamp made of SS earth enhancing compound shall be of 50kg/pit(resistivity is less than 0.12 Ohm meter). The above arrangements shall be provided with heavy duty earth poly plastic pit cover of 5000 kg load bearing capacity (Size:270 x 240 x 200mm) and FRLS insulated copper conductor of size 6 sqmm, single core cable drawn through and including medium grade rigid PVC conduit upto 7 mtr incl cutting and chases on wall / floor and making good using PCC work complete all as specified and directed. |
| 11 | Supply, errect, test and commissioning LT panel out door type, slanting top, from CPRI type tested approved manufacturer fabricated, powder coated, dust & vermin proof, air vent gasket for natural air flow including removal cable entry gland plate, power coated 440 volts, 3 phase, 4 pole, 50 cycles outdoor type weather proof made out of 3.0 mm thick CRCA sheet, seperated chamber will be made with 2.0 mm thick CRCA for each switch gear and bus bar with MS Chanel base frame of size 75mmx75mmx6mm, hinged door, double locking arrangement with 'U' shape gasket on on door panel with aluminium bus bar 600 Amps capacity insulated, fixed with epoxy based Digital ammeter 0-600 amps, with CTs, Digital voltmeter 0-600 volts , LED indicating lamp with Kit-Kat control fuses for RYB installed and including on PCC 1:3:6 type C1 as per OEM drawing size of foundation minimum 60cm from normal ground level comprising the following:- (i) Incoming (Main) :- One numbers MCCB 400 amp, 4 pole, 50 KA, 415 volts,ICU=100% of ICS 50 Hz Make Legrand |
| 12 | Material and labour for servicing, repairing and welding to out door LT Panel / LT Feeder Piller box by (i) Cleaning with blower, (ii) Cleaning with CTC/Petrol (iii) Replacement of damaged copper/aluminium lugs (iv) Replacement of deteriorated copper wiring with existing sizes of cable (v) Cleaning and tightening of MCCB terminals (vi) Replacement and fixing of sheared rubber beadings (vii) Rectifying of loose connections of incoming and outgoing cables (viii) Painting two coat of smoke gray colour over one coat of primer and black paint on base channel after rubing with emery paper and making smooth finishes by using spray machine inclusive of writing SM / MES No / name of feeders etc. (not exceeding of height 5 cm each) (ix) Providing of door locking arrangement with of sliding bolts on panel door (x) Proper welding of Panel door/roof as required (xi) Connecting / cleaning of earth wire /earth strip (x) Two coat of white distemper on foundation. |
| 13 | M&L for cleaning away all grass, vegetation, saplings, shrubs, undergrowth, roots and trees up to 50 cm girth from the area surrounding of E/M installations, 4/2 pole structures, transformer, installations, yards, surrounding valve chamers and removing the rubbish upto a distance 50 mtr outside the periphery of the area under clearance and dressing the area etc complete all as specified and directed. |
| 14 | Supplying and erecting cast iron cable indicator plate of 150 mm dia 6 mm thick bolted to 40 mm x 40 mm x 4 mm angle iron grouted in PCC 1:3:6 type C1 concrete block of size 150 mm x 150 mm x 300 mm deep including two coats of aluminium paint on metal work over a coat of red oxide primer burried along with route of cable complete all as directed. |
| 15 | M&L in repalcement of existing any type or any size aluminium conductor, steel reinforced including binding wire and jumper connect with PG clamp made out of aluminium alloy accodring to IS-617 complete all as specified and directed. |
| 16 | Labour for laying of existing cable , of any size aluminimum armoured type from existing overhead complete all as directed. |
| 17 | Taking down old rusted galvanized iron pipe including supply & Fix galvanized pipe 100 mm bore light grade in trenches / road / nallah or fixed along wall/ pole including mild steel clamps, screws etc, complete all as specified and directed. |
| 18 | All as per Item no-9 above but of size 80 mm complete all as specified and directed. |
| 19 | All as per Item no-9 above but of size 40 mm complete all as specified and directed. |
| 20 | Supply, laying and testing of LT UG cable, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of following sizes complete all as specified and directed.Note: Earth work ( Excavation, Returning & refilling and removal), cable protection HDPE pipe, GI protection pipe shall be measured and paid for seperately under respective item of Sch 'A'. |
| 21 | 120 sq.mm 3.5 core |
| 22 | 95 sq.mm 3.5 core |
| 23 | 70 sq.mm 3.5 core |
| 24 | 50 sq.mm 3.5 core |
| 25 | 35 Sqmm 3.5 core |
| 26 | 25 sq.mm 4 core |
| 27 | 16 sq.mm 4 core |
| 28 | 10 sq.mm 4 core |
| 29 | Excavation in trenches in any type of hard/dense soil n exc 1.5 mtr in width and n. exc 1.5 mtr in depth and getting out all as required for laying of cables,Foundation filling of poles or stays. |
| 30 | Returning filling, in including spreading ,leveling, watering and well ramming in layers not exc 25 cm each all as required. |
| 31 | Removing excavated material to a distance not exceeding 50 meters and depositing where directed at a level not exc 1.5 mtr above the starting point. |
| 32 | Material and labour for Double wall corrugated HDPE pipe, ISI marked of outer dia 50mm, inner dia 38mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etc for protection of LT cable XLPE grade 1100 volts complete all as specified and directed. |
| 33 | All as per Item no-14 above but of size outer dia 120 mm and inner dia 103 mm |
| 34 | Supply and fixing Onload Change over switch of capacity 400 A, 4 Pole, 415 Vols, 50 Hz, with Panel Mounted rotating handle, including dismantling old unserviceable change over switch by disconnection all incoming and outgoing electrical connection from existing indoor LT Panel complete all as specified and directed. |
| 35 | All as per item No- 16 but of capacity 250 A, 4 Pole, 415 Vols, |
| 36 | All as per item No- 16 but of capacity 125 A, 4 Pole, 415 Vols, |
| 37 | All as per item No- 16 but of capacity 100 A, 4 Pole, 415 Vols, |
| 38 | M&L in replacement of unserviceable Bus-bar chamber made out of sheet metal enclosure 200 Amps power coated independent for five connections, copper busbar suitable for 200 amps current rating mounted on wall, including disconnecting all incoming and out going electrical connections complete all as specified and directed. Make: : HAvells Cat No. IHBC020006 or equivalent in Legrand/Simens/C&S/ABB |
| 39 | Supply and fix in replacement of MCCB / MCB distribution board, Vertical TPN, 4 way, 415 V, 3 phase, AC with MCCB as incomer and MCBs as outgoing in sheet steel powder painted enclosure double door type with minimum IP 43 degree of protection with built in copper bus bar, neutral link and earth link complete including cutting the wall surfaces for flush mounting of DB and making good with cement plaster, putty and paint to match with the existing surface including taking down existing unserviceable MCB DB of any description complete all as specified and directed. Note: MCCB / MCBs shall be measured and paid separately. |
| 40 | Supply and fix MCCB 160A, 16 KA, 4 Pole, 415 V, 50 Hz with fixed thermal magnetic release fixed in Vertical TPN complete all as specified and directed. |
| 41 | S & F in replacement of U/S MCB Four Pole 63 Amp, 415 Volt, 'c' curve including necessary connection complete all as specified and directed. |
| 42 | S & F in replacement of U/S MCB SP 6 to 32 Amp, 415 Volt,'c' curve including necessary connection complete all as specified and directed. |
| 43 | M&L for Painting of single LT steel tubular pole including. cleaning and scrapping the old surface and then applying two coat of aluminium synthetic enamel paint over a coat of red oxide primer on all steel structure mounted on pole viz. Cross Arms , Clamps, bolts, nuts, brackets etc. and including painting of pole/ structure ith two coat of synthetic black & yellow enamel paint strip 300 mm wide alternative from bottom to upward of LT pole up to height of 1.5 mtr above the embedded portion of GL and writing pole number balance portion of pole shall be painted with two coats of Aluminium enamel paint over a coat of red oxide primer, complete the following as specified and directed :-Notes: - (i) Pole will be cleaned with steel brush to remove old unserviceable paint or scrapped complete surface.(ii) All poles will be numbered all as directed at site.(iii) If painting of poles not properly and not satisfied by JE/Engr-in-charge shall not be paid to contractor or otherwise repaint without extra cost. |
| 44 | Supply and fix in replacement PVC / DK Thermoplastic cable junction boxes IP 65 with metric knockouts for cable entry, weather proof suitable for outdoor installation for Gate light and Post top lantern, fixed on wall with screw & rawal plug and on GI Pipe wth suitable size MS clamp and Nut-bolts,washer of size outer dimension 170x170x105 mm complete including one connector block three terminals and PVC cable gland 02 Nos for incoming and outgoing cables with provn of 01 nos single pole MCBs 10-32 amps inside the box including taking out/down existing unserviceable junction box of any description complete all as specified and directed Make : Syntex model No-GSJB 1414 or any equivalent moden in Naptune/Hensel. |
| 45 | Supply, Fix and testing end termination jointing kit suitable for 1100V, 16-50 sqmm x 3.5/4 core XLPE cable heat shrinkable joint complete with jointing material & assessories complete all as specified and directed |
| 46 | All as per item no -27 but of size 70 sqmm to 120 sqmm. |
| 47 | All as per item no -27 but of size 185 sqmm to 400 sqmm. |
| 48 | Supply and spreading graded stone aggregate of size 40 mm at electrical outdoor installation yard 11 KV Substations / Near DP / FP structures etc including leveling of uneven surface, removing vegetation, grass etc complete all as specified and directed by Engr-in-charge. |
| 49 | Supply and fix LED security light fitting 70 watts ( Smart street Lighting ) New generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover having top opening seperate driver compartment with IP66 protection an automated lighting fixture that uses integrated sensor to deduct motion or changes in light level brightness upto 50% and once deducted the motion its comes to 100% for few minute then again comes down upto 50% brightness and illuminaying an area only when necessary with high efficiency long life LEDs with In-built electronic driver complete housed in pressure die-cast aluminium housing covered with polycarbonate cover with IP66 degree of protection including GI pipe bracket made up of 40/50mm dia medium grade GI pipe of length 1.50m bent to required shape and fixing on wall/Pole with suitable MS clamps (02 Nos) made up of 40mmx5mm MS flat, nuts, bolts and washers and provision of 3 core PVC insulated and PVC sheathed twisted three core flexible copper wire of 1.0 sqmm from LED fitting connector to GI bracket outlet complete all as specified and directed.Make : Make : Havells (ENDURA SUNBEAM SENSOR LIGHT) Model No - ENDURASUNBEAMSL70WLED757SASYTOPCSENSO or equivalent model & make of Bajaj / Philips / crompton / Wipro / Halonix / Shakti |
| 50 | Supply and fixing of cable jointing kit 11 KV (earthed) grade cable for indoor Terminal with long sleeves (Heat shinkable) type joint complete with jointing material and all accessories for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm complete all as specified and directed. |
| 51 | Supply and fixing of cable jointing kit 11 KV (earthed) grade cable for Out door Termination (heat shrinkable) type joint complete with jointing material and all accessories for 3 core XLPE armoured aluminium conductor cable of size 120Sqmm to 185 Sqmm complete all as specified and directed. |
| 52 | All as per Item No - 33 above but of size 3 core 95 Sqmm. |
| 53 | Material and labour in replacement of unserviceable can type resin filled (Alpx3) capacitors with built-in terminal connectors on top and mounting stud on the bottom heavy duty 440 V Un all as per existing type suitable for APFC panels, 3 phase, 415 V, 50 Hz sysytem of any capapcity. make : Legrand/Epcos/Universal 25 KVAr |
| 54 | Material and labour in replacement of unserviceable can type resin filled (Alpx3) capacitors with built-in terminal connectors on top and mounting stud on the bottom heavy duty 440 V Un all as per existing type suitable for APFC panels, 3 phase, 415 V, 50 Hz sysytem of any capapcity. make : Legrand/Epcos/Universal 15 KVAr |
| 55 | Material and labour in replacement of unserviceable can type resin filled (Alpx3) capacitors with built-in terminal connectors on top and mounting stud on the bottom heavy duty 440 V Un all as per existing type suitable for APFC panels, 3 phase, 415 V, 50 Hz sysytem of any capapcity. make : Legrand/Epcos/Universal 10 KVAr |
| 56 | Material and labour in replacement of unserviceable can type resin filled (Alpx3) capacitors with built-in terminal connectors on top and mounting stud on the bottom heavy duty 440 V Un all as per existing type suitable for APFC panels, 3 phase, 415 V, 50 Hz sysytem of any capapcity. make : Legrand/Epcos/Universal 5 KVAr |
| 57 | Material and labour for replacement of existing old unserviceable alluminium tube terminals (Thimbles) of size 150 sqmm to 300 sqmm complete all as specified and as directed. |
| 58 | All as per Item no-39 above but of size 95 sqmm to 120 sqmm. |
| 59 | All as per Item no-39 above but of size 50 sqmm to 70 sqmm. |
| 60 | All as per Item no-39 above but of size 35 sqmm to 50 sqmm. |
| 61 | All as per Item no-39 above but of size 25 sqmm |
| 62 | All as per Item no-39 above but of size 6 sqmm to 16 sqmm. |
| 63 | Fabrication, supply, installation, testing and commissioning electrical cubical control panel board ( KIOSK TYPE ) Double door, CPRI approved an ISO 9001 factory assembled made out door pedestal type feeder pillar box wheather and vermin proof fabricated of 3.0mm CRCA MS sheet of Suitable size,3 phase 4 wire 415 Volt ac 50 Hz complete duly painted with powder coating complete with locking arrangement, earthing terminals with suitable rating aluminium strips for incoming/outgoing MCCB's including and Mounting measuring instrument such as Volt meter, Ammeter, Selector switchs, CT's -03 Set, Phase indicator lamps with holder , toggle switches and MCBs etc including incoming and outgoing cables connections with suitable cable glands and end termination including grouting of feeder pillar box 60 cm above ground level by providing 105 cm long angle iron size 50x50x6mm welded onall four corner embedded in PCC (1:2:4) using 20mm graded upto 45cm complete all as specified and directed. ( Feeder piller box shall be consisting the following)(a) 4 Nos electrolytic aluminium bus bars high conductivity aluminium alloy proper insulated of 1 ½ times of the incoming capacity with provision of extension and mounting on porcelain support (b) MCCB FP 400 amps, 36 KA, 415 volts, 50Hz (Adjustable type) = 01 No (Incoming)(c) MCCB FP 160 amps, 25 KA , 415 volts, 50Hz (Adjustable type) - 04 Nos (Outgoing) (d) MCCB FP 125 amps, 16KA , 415 volts, 50Hz (Adjustable type) - 02 Nos (Outgoing) (e) Digital Panel mounted Amp meter 96 mm square type complete with selector switch complete with suitable size of CT's - 01 Set(f) Digital Panel mounted Volt meter 96 mm square type complete with selector switch - 01 Nos (g) Insulated Aluminium bus bars of suitable size shall be provided from the main bus bar to the out going MCCBs.(h) RYB indicating lamp, LED type - 01 sets.(i) Cost of PCC for foundation is deemed to be included in quoted rate by the contractor.(j) Drawing shall be approved by GE before placing the order. |
| 64 | Fabrication, supply, installation, testing and commissioning electrical cubical control panel board ( KIOSK TYPE ) Double door, CPRI approved an ISO 9001 factory assembled made out door pedestal type feeder pillar box wheather and vermin proof fabricated of 3.0mm CRCA MS sheet of Suitable size,3 phase 4 wire 415 Volt ac 50 Hz complete duly painted with powder coating complete with locking arrangement, earthing terminals with suitable rating aluminium strips for incoming/outgoing MCCB's including and Mounting measuring instrument such as Volt meter, Ammeter, Selector switchs, CT's -03 Set, Phase indicator lamps with holder , toggle switches and MCBs etc including incoming and outgoing cables connections with suitable cable glands and end termination including grouting of feeder pillar box 60 cm above ground level by providing 105 cm long angle iron size 50x50x6mm welded onall four corner embedded in PCC (1:2:4) using 20mm graded upto 45cm complete all as specified and directed. ( Feeder piller box shall be consisting the following)(a) 4 Nos electrolytic aluminium bus bars high conductivity aluminium alloy proper insulated of 1 ½ times of the incoming capacity with provision of extension and mounting on porcelain support (b) MCCB FP 400 amps, 36 KA, 415 volts, 50Hz (Adjustable type) = 01 No (Incoming)(c) MCCB FP 250 amps, 25 KA , 415 volts, 50Hz (Adjustable type) - 03 Nos (Outgoing) (d) MCCB FP 160 amps, 16KA , 415 volts, 50Hz (Adjustable type) - 02 Nos (Outgoing) (e) Digital Panel mounted Amp meter 96 mm square type complete with selector switch complete with suitable size of CT's - 01 Set(f) Digital Panel mounted Volt meter 96 mm square type complete with selector switch - 01 Nos (g) Insulated Aluminium bus bars of suitable size shall be provided from the main bus bar to the out going MCCBs.(h) RYB indicating lamp, LED type - 01 sets.(i) Cost of PCC for foundation is deemed to be included in quoted rate by the contractor.(j) Drawing shall be approved by GE before placing the order. |
| 65 | Fabrication, supply, installation, testing and commissioning electrical cubical control panel board ( KIOSK TYPE ) Double door, CPRI approved an ISO 9001 factory assembled made out door pedestal type feeder pillar box wheather and vermin proof fabricated of 3.0mm CRCA MS sheet of Suitable size,3 phase 4 wire 415 Volt ac 50 Hz complete duly painted with powder coating complete with locking arrangement, earthing terminals with suitable rating aluminium strips for incoming/outgoing MCCB's including and Mounting measuring instrument such as Volt meter, Ammeter, Selector switchs, CT's -03 Set, Phase indicator lamps with holder , toggle switches and MCBs etc including incoming and outgoing cables connections with suitable cable glands and end termination including grouting of feeder pillar box 60 cm above ground level by providing 105 cm long angle iron size 50x50x6mm welded onall four corner embedded in PCC (1:2:4) using 20mm graded upto 45cm complete all as specified and directed. ( Feeder piller box shall be consisting the following)(a) 4 Nos electrolytic aluminium bus bars high conductivity aluminium alloy proper insulated of 1 ½ times of the incoming capacity with provision of extension and mounting on porcelain support (b) MCCB FP 400 amps, 36 KA, 415 volts, 50Hz (Adjustable type) = 01 No (Incoming)(c) MCCB FP 200 amps, 25 KA , 415 volts, 50Hz (Adjustable type) - 02 Nos (Outgoing) (d) Digital Panel mounted Amp meter 96 mm square type complete with selector switch complete with suitable size of CT's - 01 Set(f) Digital Panel mounted Volt meter 96 mm square type complete with selector switch - 01 Nos (g) Insulated Aluminium bus bars of suitable size shall be provided from the main bus bar to the out going MCCBs.(h) RYB indicating lamp, LED type - 01 sets.(i) Cost of PCC for foundation is deemed to be included in quoted rate by the contractor.(j) Drawing shall be approved by GE before placing the order. |
| 66 | Fabrication, supply, installation, testing and commissioning electrical cubical control panel board ( KIOSK TYPE ) Double door, CPRI approved an ISO 9001 factory assembled made out door pedestal type feeder pillar box wheather and vermin proof fabricated of 3.0mm CRCA MS sheet of Suitable size,3 phase 4 wire 415 Volt ac 50 Hz complete duly painted with powder coating complete with locking arrangement, earthing terminals with suitable rating aluminium strips for incoming/outgoing MCCB's including and Mounting measuring instrument such as Volt meter, Ammeter, Selector switchs, CT's -03 Set, Phase indicator lamps with holder , toggle switches and MCBs etc including incoming and outgoing cables connections with suitable cable glands and end termination including grouting of feeder pillar box 60 cm above ground level by providing 105 cm long angle iron size 50x50x6mm welded onall four corner embedded in PCC (1:2:4) using 20mm graded upto 45cm complete all as specified and directed. ( Feeder piller box shall be consisting the following)(a) 4 Nos electrolytic aluminium bus bars high conductivity aluminium alloy proper insulated of 1 ½ times of the incoming capacity with provision of extension and mounting on porcelain support (b) MCCB FP 630 amps, 50 KA, 415 volts, 50Hz (Adjustable type) = 01 No (Incoming)(c) MCCB FP 125 amps, 25 KA , 415 volts, 50Hz (Adjustable type) - 04 Nos (Outgoing) (d) Digital Panel mounted Amp meter 96 mm square type complete with selector switch complete with suitable size of CT's - 01 Set(f) Digital Panel mounted Volt meter 96 mm square type complete with selector switch - 01 Nos (g) Insulated Aluminium bus bars of suitable size shall be provided from the main bus bar to the out going MCCBs.(h) RYB indicating lamp, LED type - 01 sets.(i) Cost of PCC for foundation is deemed to be included in quoted rate by the contractor.(j) Drawing shall be approved by GE before placing the order. |
| 67 | Supplying, installation. Connecting electrically & commissioning and testing of Outdoor type free standing type (IP -42) automatic power factor correction system with both auto and manual options type Inlet Var APFC Panel with MD-XL capacitors and MCCB as incomer factory made Non compartmentalised single unit 440 Volts 50 Hz. 3 phase 100 KVAR (Multiple of 5 KVAR) Complete all as specified and as directed including the following(a) Double Metallized paper with polypropylene film cylinderical, type MD-XL capacitor bank of rated voltage 525 volts with detuned Reactor of de tuning factor (P) 7% and suitable output of 100 KVAr at 440 Volts confirming to IS -13340, 13341. & IEC-60831 -1+2(b) Capacitor duly contactor with Damping Resistors appropriate rating for capacitor switching confirming to IEC-60070 & IS 13947(c) Automatic power factor controller relay micro processor based for switching ON & OFF of capacitors and suitable to display of voltage, current, active power, Reactive power, Apparent power. Display of power factor, THD Voltage, THD current, alarm indication for defective steps, low power factor and excess temperature. The relay has volt free c/o contact, Automatic detection and usage of optimum capacitors(i) Capable of 4 - Quadrant operation, and any phase offset requirement.(ii) Swithching programms LIFO, Combi filter, manual mode.(iii) Build in under and over voltage release with auto reset.(iv) Large Voltage input band of 90 Volt to 550 Volt, 45-65 Hz.(v) Current measuring 10 mA-5A, Suitable for CT x/1A and x/5A.(vi) Commissioning without additional settings and programming.(vii) Three decimal power factor reading(d) Multifunction meter having digital volt meter and ammeter of range as required and recommended by manufacturer within built selector switch and CTs of appropriate ratio with percentage load bar graph (Model EM 6459) equivalent. |
| 68 | (e) MCB \\"D\\", 3 Pole, 415 Volts Curve type with rupturing cap 10 kA of appropriate rating for protection of individual capacitor bank conf to IS 8828, IEC 898. (f) Incoming TPN MCCB. 250 Amps, Ics 100% Icu 25 KA, 4 Pole(g) Ventilating fans of required size to dissipiate the heat liberated by capacitor units complete with automatic switching ON and OFF of fans depending the temperature of the panel (h) Emergency stop push button to disconnect the unit in case of emergency.(j) Indicator LED type for phase indication and capacitor banks ON and OFF indication (k) All accessories prewired with suitable size copper conductor cable insulated with fibre glass insulation to withstand high temperature, housed in cubical panel (CPRI Approved) made out of 3. 15 mm thick MS sheet factory made duly powder coated front and rear door openable with locking arrangement complete with foundation as required or recommended by manufacturer. Total in Figures 0.0 23 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |