| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: MILITARY ENGINEERING SERVICES (GE (SOUTH) UDHAMPUR) NAME OF WORK : REWIRING OF ALL UNITS & VIP BLDGS AT COMD CAMP AND OTM ACCN AT COMD CAMP,NCSR, HQ 1 EW,10 EW, CMDC, 9 R & O, 135 (I) WKSP, ASCON NODE AND CERTAIN WORKS UNDER GE(SOUTH) UDHAMPUR Contract No: CA NO : GE/S(U)-35/2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Excavation in trenches in soft/loose soil not exceeding 1.5 M wide and not exceeding 1.5 Mtr deep and getting out including filling bottom surface to required level or slope for laying of pipes/ cables complete all as specified and directed. |
| 3 | Returning filling including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in any type of soil complete all as specified and as directed. |
| 4 | Removing excavated surplus soil not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and directed. |
| 5 | Taking down carefully, copper/ aluminum point wiring (light, fan, socket or power) complete including fitting such as switch, sockets, ceiling rose, pendants socket,fan regulators any type, rectangular board ,light fittings,terminal boxes etc removing materials for taking credit and making good disturbed surfaces of walls floors and ceiling complete all as specified and directed. |
| 6 | Taking down carefully copper/aluminium sub main wiring of size 2.5/4/6 sqmm from surface/concealed at any height and removing the materials from site and making good the disturbed surfaces of walls,floors roofs etc complete all as specified and directed. |
| 7 | Taking down Old/ Unserviceable MCCB/MCB DBs TPN / Main Switches by disconnection of electric connection including old unsv MCCBs,MCBs, isolators etc and making good to distrubed surface complete all as specified and directed. |
| 8 | Point wiring for one light/ fan/bell point controlled by one switch using 1.5 Sq mm FRLSH copper conductor cables (multistranded) PVC insulated and unsheathed in and including PVC concealed conduit pipe as per site requirement (size not less than 20mm dia), medium grade with Modular sunken boxes metal back plate for mounting modular type switches, sockets & regulators etc with cover plate modular type including supplying and laying PVC insulated and stranded unsheathed 1100 volts coppper conductor cable 1.5 Sq mm as earth wire connected to earth dolly including cutting of chases in wall /ceiling etc and making good the disturbed surfaces match to existing with cement mortar and putty white /colour wash complete all as directed .Make: Havells / Finolex / Polycab. |
| 9 | All as per item no 7 above but cable 2.5 sqmm FRLSH for one 3/5 pin 6 Amp socket outlet point on an independent board. |
| 10 | All as per item no 7 above but cable 2.5 sqmm FRLSH for one 3/5 pin 6 Amp socket outlet point on the same board with other switch. |
| 11 | All as per item no 7 above but for one bell/buzzer point controlled by one bell push single pole one way . |
| 12 | All as per item no 7 above but for Two way point control by Two two way 6 Amp switch. |
| 13 | All as per item no 7 above but for one 3/6 pin 16 amps socket outlet point on an independent board with cables of size 2.50 sqmm. |
| 14 | All as per item no 7 above but for one 3/6 pin 16 amps socket outlet point on an independent board with cables of size 4.0sqmm. |
| 15 | S&F for modular switch 6 Amps single pole one way 230 V, 50 Hz, AC , with outer cover complete all as specified and directed by Engr In charge. Make: Havellscrabtree/ Legrand/Schenider/L&T. |
| 16 | S&F for modular switch 16 Amps single pole one way 230 V, 50 Hz, AC , with outer cover complete all as specified and directed by Engr In charge. Make: Havellscrabtree/ Legrand/Schenider/L&T. |
| 17 | S&F for modular socket 3 Pin 6 Amps flush type 230 V, 50 Hz, AC , with outer/inner cover complete all as specified and directed by Engr In charge. Make: Havellscrabtree/ Legrand/Schenider/L&T. |
| 18 | S&F for modular socket combined 2-in-1, 6 Pin 6 & 16 Amps 230 V, 50 Hz, AC , flush type with outer/inner cover complete all as specified and directed by Engr In charge. Make: Havellscrabtree/ Legrand/Schenider/L&T. |
| 19 | Point wiring for one light/ fan/bell point controlled by one switch using 1.5 Sq mm FRLSH copper conductor cables (multistanded) PVC insulated and unseathed in Wiring with Copper conductor cables in PVC casing & caping as per site requirement , medium grade with sunken boxes & PVC back plate for mounting all type switches, sockets & regulators etc with front plate including supplying and laying PVC insulated unsheathed 1100 volts coppper conductor cable 1.5 Sq mm as earth wire stranded and conected to earth dolly as specified.Note:- Cutting and making same the wall patchs after laying the wire and conduit using putty, white wash and distamper. The surface should be made smooth using putty and should match exactly with the existing wall finish.Make: Havells / Finolex / Polycab/SCI. |
| 20 | All as per srl item No 18 but for 3 pin 6 Amps socket outlet independent board including PVC insulated PVC unsheathed 2.5 sq mm earth wire and connected to earth dolly. |
| 21 | All as per srl item No 18 but for 3 pin 6 Amps socket outlet on the same board including PVC insulated PVC unsheathed 1.5 sq mm earth wire and connected to earth dolly. |
| 22 | All as per srl item No 18 but for One light point controlled by two 2-way switches,with cables 1.5 sq. mm size earth wire and connected to earth dolly. |
| 23 | All as per Srl item No 18 but for 3 Pin 16 Amps socket outlet independent board with cable 2.5 Sq mm including copper PVC insulated PVC unsheathed 2.5 sq mm earth wire standard and connected to earth dolly. |
| 24 | S&F piano switch 6 Amps single pole one way 230 V, 50 Hz, AC , complete all as specified and directed by Engr In charge. Make: Havells/ Legrand/Schenider/L&T. |
| 25 | S&F piano switch 16 Amps single pole one way 230 V, 50 Hz, AC , complete all as specified and directed by Engr In charge. Make: Havells/ Legrand/Schenider/L&T. |
| 26 | S&F for Socket outlet 2 in 1, 3/5 pin, 6A, 230 V, 50 Hz, AC , complete all as specified and directed by Engr In charge. Make: Havells/ Legrand/Schenider/L&T. |
| 27 | S&F for Socket outlet 2 in 1, 3/5 pin, 16A, 230 V, 50 Hz, AC , complete all as specified and directed by Engr In charge. Make: Havells/ Legrand/Schenider/L&T. |
| 28 | S & F Bell push flush type 6 amp 230 V, 50 Hz, AC , complete all as specified and directed by Engr In charge. Make: Havells/ Legrand/Schenider/L&T. |
| 29 | M &L Ceiling rose, surface bakelite 65x 50mm three terminals fixed on PVC Round Blockcomplete all as specified and directed by Engr In charge. Make: Havells/ Legrand/Schenider/L&T. |
| 30 | S & F calling Bell ding dong 230 volts single pole 50Hz complete all as specified and directed by Engr In charge.Make: Havells/ Legrand/Schenider/L&T. |
| 31 | S&F electronic step type fan regulator 100 watt 230 volts 50Hz 1/2 module C/S deluxe type complete all as specified and directed. Make: Havells/ Legrand/Schenider/L&T. |
| 32 | S&F Sub main wiring with two single core PVC insulated with copper conductor cable stranded of size 10 Sqmm in PVC concealed conduit /casing capping 25mm dia including PVC insulated copper conductor cable 10 Sq mm as earth lead all as specified. Including taking down old sub main wire. Make: Havells / Finolex / Polycab. |
| 33 | S&F Sub main wiring with two single core PVC insulated with copper conductor cable stranded of size 6 Sqmm in PVC concealed conduit /casing capping 25mm dia including PVC insulated copper conductor cable 6 Sq mm as earth lead all as specified. Including taking down old sub main wire. Make: Havells / Finolex / Polycab. |
| 34 | S&F Sub main wiring with two single core PVC insulated with copper conductor cable stranded of size 4 Sqmm in PVC concealed conduit/casing capping 25mm dia including PVC insulated copper conductor cable 4 Sq mm as earth lead all as specified. Including taking down old sub main wire. Make: Havells / Finolex / Polycab. |
| 35 | S&F Sub main wiring with two single core PVC insulated with copper conductor cable stranded of size 2.5 Sqmm in PVC concealed conduit/casing capping 25mm dia including PVC insulated copper conductor cable 2.5 Sq mm as earth lead all as specified. Including taking down old sub main wire. Make: Havells / Finolex / Polycab. |
| 36 | S&F Sheet metal enclosure double door type for MCCB TPN DB upto 125 Amps, 4 way vertical type 415 volts with suitable rated busbar and neutral link including MCCB 125 Amps 25 KA , chases wall for fixing DB and making good distributed wall surfaces to match with existing specification complete all as specified and directed. Make:- Havells / Schenider/ Legrand. |
| 37 | S&F Sheet metal enclosure double door type for DBs (when MCB to be used) Single pole & neutral 12 way 240 volts with 200 Amps rated busbar and neutral link including chases wall for fixing DB and making good distributed wall surfaces to match with existing specification complete all as specified and directed. Make:- Havells / Schenider/ Legrand. |
| 38 | S&F Sheet metal enclosure double door type for DBs (when MCB to be used) Single pole & neutral 8 way 240 volts with 200 Amps rated busbar and neutral link including chases wall for fixing DB and making good distributed wall surfaces to match with existing specification complete all as specified and directed. Make:- Havells / Schenider/ Legrand. |
| 39 | S & F in replacement MCCB Three Pole & Neutral capacity of 100 amps 415 volts rupturing capacity 16 KA complete all as specified and directed. Make:- Havells / Schenider/ Legrand. |
| 40 | S & F in replacement MCB Single pole and neutral 240 volt any rating from 40 amps\\"C\\" series, with rupturing capacity 10 KA ,inculding providing thimble for out going cable complete all as specified and directed. Make:- Havells / Schenider/ Legrand. |
| 41 | S & F in replacement MCB single pole 240 volt any rating from 6 to 32 amps \\"C\\" series, with rupturing capacity 10 KA ,inculding providing thimble for out going cable complete all as specified and directed. Make:- Havells / Schenider/ Legrand. |
| 42 | S & F in replacement MCB single pole and neutral 240 volt any rating from 63 Amps \\"C\\" series, with rupturing capacity 10 KA ,including providing thimble for out going cable complete all as specified and directed. Make:- Havells / Schenider/ Legrand. |
| 43 | S & F in replacement of Modular MCB protected socket AC power board complete with one single pole MCB 240 Volts 20 Amps including comlete all as directed by Engr-in-cahrge. Make:- Havells |
| 44 | S & F in replacement Sheet metal enclosure single pole and neutral with a two pin and earth plug and socket complete with one single pole MCB 240 Volts 20 Amps including taking down of old one complete all as directed by Engr-in-charge. Make:- Havells / Schenider/ Legrand. |
| 45 | M&L PVC insulated (unsheathed) 03 core multistranded cable copper conductor FRLSH suitable upto 1.5 Sqmm suitable upto 1100volts. |
| 46 | M&L PVC insulated (unsheathed) 02 core multistranded cable copper conductor FRLSH suitable upto 2.5 Sqmm suitable upto 1100volts. |
| 47 | M&L PVC insulated (unsheathed) single core multistranded cable copper conductor FRLSH suitable upto 1.5 Sqmm suitable upto 1100volts. |
| 48 | M&L PVC insulated (unsheathed) single core multistranded cable copper conductor FRLSH suitable upto 2.5 Sqmm suitable upto 1100volts. |
| 49 | M&L PVC insulated (unsheathed) Double core aluminum cable conductor suitable upto 10 Sqmm x 2 core suitable upto 1100volts. |
| 50 | S & F in repairs PVC Casing Caping of Size upto 25 mm and 12 mm including all connected accessories (Nail, Tee, Elbow etc). |
| 51 | Switch - socket combination 5 Amps, 5 pin multipurpose with PVC Box, 4 holes complete all as specified and directed. |
| 52 | Switch - socket combination 15 Amps, 6 pin multipurpose with PVC Box, 4 Holes complete all as specified and directed. |
| 53 | S & F in repairs LED lights fitting 1x 5W, 230V, white/ warm white Endura Linear Neo surface and wall mounted LED Batten with & Integrated electronic driver with THD<10% connecting up with flexible copper conductor cable of suitable size from ceiling rose complete.Make : Phillips/ Havells/syska/Bajaj |
| 54 | S & F in repairs LED lights fitting 1x 10W, 230V,AC white/ warm Endura Linear Neo surface and wall mounted LED Batten with & Integrated electronic driver with THD<10% connecting up with flexible copper conductor cable of suitable size from ceiling rose complete.Make : Phillips/ Havells/syska/Bajaj |
| 55 | Switch - socket combination 5 Amps, 5 pin multipurpose with holes complete all as specified and directed. |
| 56 | Switch - socket combination 15 Amps, 6 pin multipurpose with Holes complete all as specified and directed. |
| 57 | Modular plate 1/2 module including taking down old u/s one. Make: Havellscrabtree/ Legrand/Schenider/L&T. |
| 58 | Modular plate 3 module including taking down old u/s one complete all as specified and as directed. Make: Havellscrabtree/ Legrand/Schenider/L&T. |
| 59 | Modular plate 4 module including taking down old u/s one complete all as specified and as directed. Make: Havellscrabtree/ Legrand/Schenider/ L&T. |
| 60 | Modular plate 6 module including taking down old u/s one complete all as specified and as directed. Make: Havellscrabtree/ Legrand/Schenider/ L&T. |
| 61 | Modular plate 8 module including taking down old u/s one all as specified and as directed. Make: Havellscrabtree/ Legrand/Schenider/L&T. |
| 62 | Hylam sheet Polycarbonate electric switch board sheet of size 9x11 inch complete all as specified and as directed. |
| 63 | Hylam Sheet Polycarbonate electric switch board sheet of size 9x5 inch complete all as specified and as directed. |
| 64 | Hylam Sheet Polycarbonate electric switch board sheet of size 8x8 complete all as specified and as directed. |
| 65 | Hylam Sheet Polycarbonate electric switch board sheet of size 4x6 complete all as specified and as directed. |
| 66 | PVC Box 2 way/ 4 way complete all as specified and directed. |
| 67 | Modular mild steel sheet sunken boxes metal back plate of 3 module for mounting modular type switches, sockets & regulators etc complete all as specified and as directed. |
| 68 | Modular mild steel sheet sunken boxes metal back plate of 4/6/12 module for mounting modular type switches, sockets & regulators etc complete all as specified and as directed. |
| 69 | S&F decorative LED Picture light of 6/12W wall mounting fixture luminaire complete all as specified and directed by Engineer-in-Charge. Make : Phillips/ Havells/Bajaj. |
| 70 | S & F in repairs LED lights fitting 1x 20W, 230V,white/ warm Endura Linear Neo surface and wall mounted LED Batten with & Integrated electronic driver with THD<10%, holder including LED tube light connecting up with flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed. Make : Phillips/ Havells/syska/Bajaj |
| 71 | S & F in repairs LED light fitting 1x9W/1X10Wbulkhead luminaires including LED light driver holder connecting up with flexible copper conductor cable of suitablesize complete all as specified and as directed. Make : Phillips/ Havells/syska/Bajaj |
| 72 | S & F in repairs LED building security light fitting 30 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp,clamps,suitable bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete.Make : Phillips/ Havells/syska/Bajaj. |
| 73 | S & F in repairs LED decorative down light fitting/recess mounted round type white/ warm white with high out put diffuser 15/18/22 watt all as required at site 220 V AC with driver holder and LED lamp including connecting up with flexible copper conductor cable of suitable size complete all as specified.Make : Phillips/ Havells/syska/Bajaj |
| 74 | Supply and fixing LED luminaire 600 mm x 600 mm, 36 watt, 220–240 Volts AC, 50 Hz recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete with all accessories as specified below :- Input Voltage: 220–240 Volts AC, 50 HzType: Edge-lit / Back-lit LED panel, slim designLuminous Efficacy: Minimum 100 lumens per wattColour Temperature (CCT): Cool White (6500K) / Neutral White (4000K)/ Warm White (3000K) as specifiedDriver: Inbuilt constant current LED driver, BIS approvedBody: Powder coated CRCA sheet / Aluminium housingDiffuser: High transmission opal acrylic / polycarbonate diffuserProtection: IP20 or betterMake: Philips /Havells / CromptonNote:- Quoated rate includes cutting of false ceiling if required, making good damages, connection with existing wiring, earthing, testing and commissioning complete in all respects. |
| 75 | Supply and fixing LED luminaire 600 mm x 600 mm, 60 watt, 220 V AC 220–240 Volts AC, 50 Hz recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete with all accessories as specified below :- Type: Edge-lit / Back-lit LED panel, slim designLuminous Efficacy: Minimum 100 lumens per wattColour Temperature (CCT): Cool White (6500K) / Neutral White (4000K)/ Warm White (3000K) as specifiedDriver: Inbuilt constant current LED driver, BIS approvedBody: Powder coated CRCA sheet / Aluminium housingDiffuser: High transmission opal acrylic / polycarbonate diffuserProtection: IP20 or betterMake: Philips / Havells / CromptonNote:- Quoated rate includes cutting of false ceiling if required, making good damages, connection with existing wiring, earthing, testing and commissioning complete in all respects. |
| 76 | S & F in repairs LED lights fitting 1x 3W, 230V, Red/Green Light surface/Recess mounted LED light (For Engagement Light) with Integrated electronic driver ,THD<10% connecting up with flexible copper conductor cable of suitable size incl modular boxes/Hylam Sheet for mounting light complete all as specified and directed by Engr-In-Charge. Make : Phillips/ Havells/syska/Bajaj/Orient |
| 77 | S & F in repairs LED wall mounting Decorative wall light fixture CITY 3 made up of Polycarbonate, suitable for 9 W retrofit LeD Lamp B22 base with driver holder and LED lamp including connecting up with flexible copper conductor cable of suitable size complete.Make : Phillips/ Havells/syska/Bajaj |
| 78 | S & F in repairs LED Decorative, STYLO wall mounting, champagne gold finish fixture with plastic body suitable for 9 W LeD lamp B22 base.with driver holder and LED lamp including connecting up with flexible copper conductor cable of suitable size complete.Make : Phillips/ Havells/syska/Bajaj |
| 79 | S&F decorative LED bed light wall mounting fixture luminaire complete all as specified and directed by Engineer-in-Charge.Make : Phillips/ Havells/Bajaj. |
| 80 | S&F decorative LED Focus light wall mounting fixture luminaire complete all as specified and directed by Engineer-in-Charge.Make : Phillips/ Havells/Bajaj. |
| 81 | S&F decorative rope light (LED Strip) warm/white colour fixture with driver/ starter luminaire complete all as specified and directed by Engineer-in-Charge.Make : Phillips/ Havells/Bajaj. |
| 82 | S & F calling Bell Wireless(Cordless) type other than ding dong sound 230 volts single pole 50Hz, including battery(set of two) complete all as specified and directed by Engr In charge. |
| 83 | Supply, installation, testing and commissioning of 40 Watt LED gate light fitting 220–240 Volts AC, 50 Hz, suitable for outdoor use at main gate / entrance area, complete with all accessories as specified below:Rated Wattage: 40 WattsType: LED outdoor wall mounted / bracket mounted light fittingLuminous Efficacy: Minimum 100 lumens per wattColour Temperature (CCT): Cool White (6500K) / Neutral White (4000K) as specifiedBody: Die-cast aluminium housing with powder coated finishDiffuser: Toughened glass / high impact polycarbonateProtection: IP65 or better (weatherproof outdoor type)Surge Protection: Minimum 2.5 kV internal Mounting: Suitable for wall / gate pillar mountingLife Span: Minimum 50,000 burning hours Warranty: Minimum 2 yearsMake: Philips / Wipro / Havells /Crompton / BajajIncluding fixing on gate pillar/wall with suitable MS bracket if required, connection with existing wiring, earthing, testing and commissioning complete all as specified and as directed. |
| 84 | S & F in repairs LED lights fitting 1x 20W, 230V,AC white/ warm white decorative box type with driver, Powder coated aluminium extruded body with integrated electronic driver with THD<10%,including connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed Make-Crompton Trimline Neu Cat Part No CCS-103-20-65-SL-DP-NWH OR Techno commercial Equivalent make in Philips/Bajaj/syska |
| 85 | S & F LED Lamp 12W,which gets automatically switched ON during Power cut and Run effectively up to 4 Hours, Lumens Capacity-900lm ,PF-0.9(min) ,colour temp 6500K,CRI>80,IP 20 base-B22 type Make- Bajaj LEDZ Inverter Lamp 9W or techno commercial equivalent make in Syska/Havells. |
| 86 | S & F LED lights fitting 1x 20W, 230V,AC white/warm white decorative box type with driver,which gets automatically switched ON during Power cut and Run effectively up to 3 Hours, Lumens Capacity-2000lm ,PF-0.9(min) ,colour temp 6500K,CRI>80,IP 20 light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed by Engr-In-Charge. Make- Havells Pride Plus Inverter Batten cat Part No LHEXACP7FN1W020 or techno commercial equivalent make in Syska/Bajaj |
| 87 | Supply and fix 3 pin 16 Amp Plug top with indicator lamp all as specified and directed |
| 88 | Supply and fixing staff mini calling bell indicator with light 10 way controller box for offices/VIP bldgs complete all as specified and directed. |
| 89 | Supply, laying and testing of Service cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4 core all as specified and directed by Engr-In-charge. |
| 90 | S&F Robustly designed IP65/IK10 Bollard garden light 15W, Innovative design with uniformly lit diffuser at the upper portion acts a beacon of path guidence in a landscape environment light to be fixed on cement conctrete in bed in foundations filling and mass contrete and making electrical connection with copper cable all as specified . Make: Philips cat part no. BCP150 LED150/NW PSU 220-240V 7043 equivalent in Havells/Crompton |
| 91 | S & F Street light Bracket complete made of GI pipe of suitable size, medium grade 1 m long bent to shape as per site requirement along with MS flat iron clamps with nuts, bolts, washers including grouting the same with wall , all as specified and directed by Engr- in Charge. |
| 92 | S & F in repairs LED Flood light fitting of 120 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp,clamps,suitable bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and as directed. Make : Phillips/ Havells/syska/Bajaj. |
| 93 | Supply, fixing and testing of meter box board made out of 2 mm thick MS sheet of size not less than 600 x 600 x 150 mm duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, wall mounted/ semi grouted in wall with locking arrangement and provision of tapping for incoming and outgoing electric connections with suitable size of lugs complete all as specified and directed comprising of the following(Make: LT panel shall be manufactured by one make mentioned in the List of makes under PS) :- (i) Aluminium bus bar chamber TPN of 200 amps rating (Set of four strip). (ii) MCCB four pole 415 volts AC 50 Hz, 63 amps rating breaking capacity 10 KA fixed magnetic and adjustable thermal release - 01 No. (iii) MCB two pole 415 volts AC 50 Hz, 40 amps rating breaking capacity 10 KA fixed magnetic and adjustable thermal release - 04 No. (iv) fixing and connection of existing energy meter - 04 nos(v) Earthing terminals - 02 Nos(vi) MCB SP 20A 10 KA C series - 01 Nos |
| 94 | M & L for Earthing complete with GI earth plate electrodes 600 mmx600 mm x6 mm thick buried directly in ground earth plate not less than 2.25 m deep below normal ground level with top edge of the plate not less than 1.5 m below normal ground level connected to and including galvanized steel earth lead wire 4.00 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron and steel including PCC pit in PCC 1:2:4 type B-1using 20 mm graded crushed stone aggregate, RCC frame with 40mm thick RCC cover reinforced with 8mm dia MS bars, 20mm bore light grade GI watering pipe with funnel, charcoal & Salt and 1 Bags of Benzonite powder weighs 25Kg. including excavation and earth work in any type of soil complete all as shown in electrical plate No 3 connected to main control board all as specified and testing on completion.NOTE: On completion of earthing contractor should check earthing results and submit the test report to Engr-in-charge. The test result should be less than 2 ohm, if desired results are not obtained then earthing shall be redone by the contractor at his own cost. |
| 95 | S&F Double Walled corrugated DWC Pipe of size 40 mm including snap fit coupler Pt-II for protection of LT Cable in underground complete all as specified and as directed. |
| 96 | Supply and fixing GI tubing light grade 40 mm dia along the wall/ in trenches/ in duct / in culvert /road crossing and including provisioning of suitable mild steel flat iron clamps and bolts, nuts and double washers etc for holding of GI pipe alongwith poles all as specified and as directed. Total in Figures 0.0 0.0 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |