Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 21-05-2026 | Tender Corrigendum | Other | 05-06-2026 |
| Sl. No. | Item Description |
| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GARRISON ENGINEER (AF) BANGALORE NAME OF WORK : REPAIR/REPLACEMENT TO SECURITY LIGHTS/STREET LIGHTS/HIGH MAST/CONNECTING PANELS AT SMQ,OTM AND REPAIR REPLACEMENT OF FITTING FIXTURES, RENEWAL OF EARTHINGS INCL ALLIED SERVIES OF INTERNAL ELEC OF VARIOUS BUILDING AT HQTC CA NO: GE(AF)/B/ OF 2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description of Item of Work Item Code / Make Quantity Unit Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT (in Words) |
| 2 | Taking down existing defective/unservicable street light fittings/security light fittings/Flood light fittings of any capacity,any description,any wattage, any type and in any position from poles/pipes/ walls of buildings of any height complete after disconnecting the electrical connection replacement of un-serviceable/damaged/ broken spare parts/ brackets etc, re-assembling the fittings and making the light fittings serviceable, fixing the fittings in same position, connecting to electric supply and its testing on installation complete all as specified and directed. |
| 3 | Taking down existing defective/unservicable post top lanterns/Gate lights /Garden lights fitting of any capacity,any description,any wattage, any type and in any position fixed at a height not more than 4 mtr from ground level complete after disconnecting the electrical connection replacement of un-serviceable/damaged/ broken spare parts,accessories etc, re-assembling the fittings and making the light fittings serviceable, fixing the fittings in same position, connecting to electric supply and its testing on installation complete all as specified and directed. |
| 4 | Lowering of and lifting of carriage of high mast lights fitting with wire rope motorised or manually existing defective/unservicable high mast lights fittings of any capacity,any description,any wattage, any type,any position and any height after disconnecting the electrical connection replacement of un-serviceable/damaged/ broken spare parts/ accessories etc,including servicing of High mast of any height and description , opening the mechanical hoisting / lowering assembly , steel wire bobbin , replacing the unservieable meshing gear, easying the steel rope movements, checking the locking mechanism , replacing of oil ,greasing complete and checking for smoothing operation of the mast, re-assembling the high mast lights fittings and making the high mast lights fittings serviceable, fixing the fittings in same position, connecting to electric supply and its testing on installation complete all as specified and directed. |
| 5 | S&F high energy efficient constant current electronic driver suitable for LED street light fitting 35 Watts, LED luminaires 240 Volt ,50Hz, AC single phase complete all as specified and directed, |
| 6 | S&F high energy efficient constant current electronic driver suitable for LED street light fitting 45 Watts, LED luminaires 240 Volt ,50Hz, AC single phase complete all as specified and directed. |
| 7 | S&F high energy effiicient constant current electronic driver suitable for LED street light fitting 90 Watts, LED luminaires 240 Volt ,50Hz, AC single phase complete all as specified and directed. |
| 8 | S&F high energy effiicient constant current electronic driver suitable for LED street light fitting/ Flood light fitting 100 Watts, LED luminaires 240 Volt ,50Hz, AC single phase complete all as specified and directed. |
| 9 | S&F high energy effiicient constant current electronic driver suitable for LED Flood light fitting 30 Watts, LED luminaires 240 Volt ,50Hz, AC single phase complete all as specified and directed. |
| 10 | S&F high energy effiicient constant current electronic driver suitable for LED Flood light fitting 50 Watts, LED luminaires 240 Volt ,50Hz, AC single phase complete all as specified and directed. |
| 11 | S&F high energy efficient constant current electronic driver suitable for LED Flood light fitting 60 Watts, LED luminaires 240 Volt ,50Hz, AC single phase complete all as specified and directed. |
| 12 | S&F high energy efficent constant current electronic driver suitable for LED Flood light fitting 200 Watts, LED luminaires 240 Volt ,50Hz, AC single phase complete all as specified and directed. |
| 13 | S&F opening the LED street light/Flood light fittings of capacity 30 watts to 60 watts ,any type and in any position,taking out the LED motherboard,checking the power LEDs, replacing the unserviceable motherboard,electronic driver, power LEDs and soldering or any item as per requirement and making the light fittings serviceable in any way and fixing the fittings in same position including testing, complete all as specified and directed. |
| 14 | S&F opening the LED street light/Flood light fittings of capacity 90 watts to 200 watts ,any type and in any position,taking out the LED motherboard,checking the power LEDs, replacing the unserviceable motherboard,electronic driver, power LEDs and soldering or any item as per requirement and making the light fittings serviceable in any way and fixing the fittings in same position including testing, complete all as specified and directed. |
| 15 | Dismantling the three phase motor upto 5 HP,440 Volt ,50Hz, AC of High mast lights fittings and taking out to workshop for re-winding,removing the burntout windings, re-winding the same with super enamelled copper wire of existing guage,varnishing and oven drying , and replacing any item as per requirement ,assembling the motor including testing, making the motor serviceable in any way and fixing the motor in same position complete all as specified and directed. |
| 16 | Disconnecting and taking out old rusted/ unserviceable light fitting bracket incl FI clamps of any description and in any position and S&F GI brackets made out of 50 mm dia light grade GI pipe 1.50 mtr long bent to shape and size as per site requirement for fixing of street light fitting on poles/ walls including Flat Iron clamps=02 Nos of size 30x5mm made to shape incl nuts,bolts & washers complete all as specified and directed. |
| 17 | Disconnecting and taking out old rusted pipe and M&L for 40 mm dia galvanized iron tube light grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc, including Flat Iron clamps=02 Nos of size 30x5mm, with nut bolt and washers complete all as specified & directed. |
| 18 | Disconnecting and taking out old rusted pipe and M&L for 50 mm dia galvanized iron tube light grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc, including Flat Iron clamps=02 Nos of size 30x5mm, with nut bolt and washers complete all as specified & directed. |
| 19 | Disconnecting and taking out old existing unserviceable PVC cable loop box and supplying and fixing with pole PVC cable loop box, size not less than 200 mm x 140 mm x 95 mm, out door type, IP 65 including 4 Nos aluminum bus bar of size 25mmx5mm mounted on porcelain insulators with one MCB SP 6 amps 230 volts connected to street light fitting sub main wire and using FI clampsof size 20mm x3 mm for fixing of PVC cable loop box with pole,including nuts,bolts & washers and connecting the cables to bus bars with using suitable size GI nut, bolts and washers and aluminum lugs etc and complete all as specified & directed. |
| 20 | Disconnecting and taking out old existing unserviceable PVC cable loop box and supplying and fixing with pole PVC cable loop box, size not less than 145 mm x 145 mm x 95 mm, out door type, IP 65 including porcelain insulated connectors for incoming and outgoing 4 core cables with one MCB SP 6 amps 230 volts connected to street light fitting sub main wire and using FI clampsof size 20mm x3 mm for fixing of PVC cable loop box with pole,including nuts,bolts & washers and connecting the cables to connectors with using suitable size GI nut, bolts and washers and aluminum lugs etc and complete all as specified & directed by Engineer-in-Charge. |
| 21 | S&F sub main wiring from street light fitting to junction box with two single core PVC insulated cable with copper conductor multistranded 1100 volts grade 1.5 sqmm in and including heavy grade PVC conduit and its accessories with fixing arrangements on pole surface, wall, ceiling etc including 1.5 sqmm PVC insulated multistranded copper earth continuity conductor and connecting to main earth dolly complete all as specified and directed.Note : One run of earth continuity conductor,one run of PVC conduit and two runs of copper conductor together taken as one length for measuring unit length. |
| 22 | S&F in repairs Single core PVC insulated,unsheathed, FRLS multistranded copper conductor 1100 volts grade cable of size 2.5 sqmm ,complete all as specified and directed. |
| 23 | S&F MCB SP, 6-32A, 240V,50Hz ,10kA, 'B' type, for street light fittings complete all as specified and directed. |
| 24 | S&F MCB SPN 32A, 240V,50Hz ,10kA, 'B' type,suitable for existing timer control board complete all as specified and directed. |
| 25 | S&F MCB TPN,63A, 415V,50Hz ,10kA, 'B' type,suitable for existing timer control board complete all as specified and directed. |
| 26 | S&F MCCB, 4 poles 415 Volts, 63 Amps, 16 kA, 50 Hz, AC, fixed thermal and fixed magnetic type including connecting up incoming/out going cables connection with suitable lugs and testing complete all as specified & directed. |
| 27 | S&F 3 pole Power Contactors 415 volt 50 Hz ML3 type 40 Amps AC3 rating with 2 NO +2NC Aux contacts, fixed in repairs,including taking out old existing unserviceable complete all as specified & directed.Make : L&T Cat No. SS 90721 or techno-commercially equivalent in Legrand/Schneider/Indo-asian |
| 28 | S&F 3 pole Power Contactors 415 volt 50 Hz ML 4 type 70 Amps AC3 rating with 2 NO +2NC Aux contacts, fixed in repairs,including taking out old existing unserviceable complete all as specified & directed. Make : L&T Cat No. SS 90910 or or techno-commercially equivalent in Legrand/Schneider/Indo-asian |
| 29 | S&F Digital Multi function time switch with programmable fuction with battery backup and current carring capacity 16 Amps with 1 changeover including takingout the unserviceable time switch, complete all as specified & directed by Engineer-in-Charge. Make : L&T 67DDT0 or techno-commercially equivalent in Legrand/Schneider/Indo-asian |
| 30 | S&F Street light panel box 32 Amps , 3 pole, 230 volts with contactor, Digital time switch ,24 hours timer , MCB TPN etc, including taking out the unserviceable street light panel box , complete all as specified & directed. Make : Indo Asian TL032DBO or techno-commercially equivalent in Legrand/Schneider/Havells |
| 31 | S&F LED flood light fitting 30 watts,240 Volt, single phase, AC, outdoor type,aluminium pressure die-cast housing with IP66 protection with 4 Kv in-built surge protection complete with driver,motherboard and LED including taking down unserviceable fitting, connecting and testing complete all as specified & directed. Make:Bajaj BJFL 30W LED or techno-commercially equivalent in Havells/Philips/Wipro. |
| 32 | S&F LED flood light fitting 50 watts,240 Volt, single phase, AC, outdoor type,aluminium pressure die-cast housing with IP66 protection with 4 Kv in-built surge protection complete with driver,motherboard and LED including taking down unserviceable fitting, connecting and testing complete all as specified & directed.Make: Bajaj BJFL 50W LED or techno-commercially equivalent in Havells/Philips/Wipro. |
| 33 | S&F LED flood light fitting 60 watts,240 Volt, single phase, AC, outdoor type,aluminium pressure die-cast housing with IP66 protection with 4 Kv in-built surge protection complete with driver,motherboard and LED including taking down unserviceable fitting, connecting and testing complete all as specified & directed. Make : Havells JETAALBAFLOODLIGHT60W or techno-commercially equivalent in /Philips/Wipro. |
| 34 | S&F LED flood light fitting 100 watts,240 Volt, single phase, AC, outdoor type, with pressure die-cast housing, toughened glass with IP66 protection with 4 Kv in-built and 10 Kv external surge protection complete with driver,motherboard and LED including taking down unserviceable fitting,connecting and testing complete all as specified & directed.Make : Bajaj PRAZE F 120L WH NB-A5 TG SD or techno-commercially equivalent in Havells/Philips/Wipro. |
| 35 | S&F LED flood light fitting 200 watts,240 Volt, single phase, AC, outdoor type, with superior polycarbonate optics pressure die-cast housing, with IP66 protection with 4 Kv in-built and 10 Kv external surge protection complete with driver,motherboard and LED including taking down unserviceable fitting,connecting and testing complete all as specified & directed.Make : Bajaj GLEAM F 220L WH SY PC SD V2 or techno-commercially equivalent in Havells/Philips/Wipro. |
| 36 | S&F LED street light fitting 35 watts,240 Volt, single phase, AC, outdoor type with pressure die-cast housing with IP66 protection,high performance polycarbonate optics, 4 Kv in-built surge protection with top opening driver cover complete with driver,motherboard and LED including taking down unserviceable fitting,connecting and testing complete all as specified & directed.Make : Bajaj ENXT P 42L WH PO PC SD MT or techno-commercially equivalent in Havells/Philips/Wipro. |
| 37 | S&F LED street light fitting 45 watts,240 Volt, single phase, AC, outdoor type with pressure die-cast housing with IP66 protection,high performance polycarbonate optics, 4 Kv in-built surge protection with top opening driver cover complete with driver,motherboard and LED including taking down unserviceable fitting,connecting and testing complete all as specified & directed.Make : Bajaj ENXT P 54L WH PO PC SD MT or techno-commercially equivalent in Havells/Philips/Wipro. |
| 38 | S&F LED street light fitting 90 watts,240 Volt, single phase, AC, outdoor type with pressure die-cast housing, toughened glass with IP66 protection with 4 Kv in-built and 10 Kv external surge protection complete with driver,motherboard and LED including taking down unserviceable fitting,connecting and testing complete all as specified & directed.Make : Bajaj ZELA P 108 L WH PO TG SD or techno-commercially equivalent in Havells/Philips/Wipro. |
| 39 | S&F LED street light fitting 100 watts,240 Volt, single phase, AC, outdoor type with pressure die-cast housing, toughened glass with IP66 protection with 4 Kv in-built and 10 Kv external surge protection complete with driver,motherboard and LED including taking down unserviceable fitting,connecting and testing complete all as specified & directed.Make : Bajaj ZELA P 120 L WH PO TG SD or techno-commercially equivalent in Havells/Philips/Wipro. |
| 40 | S&F LED post-top light fitting 25 watts made in die-cast aluminium bottom housing and spun aluminium top reflector with decorative clear acrylic diffuser and IP 65 protection with 25 watt LED bulb including taking down unserviceable fitting, complete all as specified & directed.Make : Bajaj BGCTN 25 W LED WH or techno-commercially equivalent make of Havells,CG. |
| 41 | S&F LED post-top light fitting 25 watts made in spherical shape polycarbonate opal and clear diffuser with IP 65/66 protection with 25 watt LED bulb including taking down unserviceable fitting, complete all as specified & directed.Make: Bajaj BLPTSP 25 W WW LED or techno-commercially equivalent make of Havells,CG. |
| 42 | S&F LED Bulbs 23 Watts, BEE star rated energy efficient Retrofit bulb, including taking down unserviceable lamp, complete all as specified & directed. |
| 43 | S&F LED Bulbs 10 Watts, BEE star rated energy efficient Retrofit bulb, including taking down unserviceable lamp, complete all as specified & directed. |
| 44 | Excavation in trenches not. exc. 1.5m wide and not exc. 1.5m deep and getting out in soft/loose soil complete all as specified and directed. |
| 45 | Returning, filling in,including spreading, levelling ,watering and well ramming in layers not exc 25cm thick in soft/loose soil complete all as specified and directed. |
| 46 | Removing surplus soil to a distance not exc 50m and depositing where directed at a level not exc. 1.5m above the starting point complete all as specified and directed. |
| 47 | M&L for sand cushioning to under ground cable with locally available dry sand for protection of cable 8cm thick before laying of cable and 15 cm thick after laying and stretching the cable below the bricks/PCC cover ,punning of sand using suitable T&P as per site requirement complete all as specified and directed.Note- Punned thickness of sand i.e 18 cm shall be considered for measurement purpose. |
| 48 | Supplying and laying un-reinforced precast concrets cable cover class LV, Type 1, flat, size 250x150x40 mm complete all as specified and directed. |
| 49 | M&L Plain cement concrete 1:4:8 type D-2( using 40mm graded crushed stone aggregate) as in foundation,filling and mass concrete in foundation of poles and stay assembly for bed concrete or as per site requirement complete all as specified and directed. |
| 50 | Taking out unserviceable cable any type/size from trenches,pole, road,duct etc including necessary joints,U/S fittings and pipes etc complete all as specified and directed. |
| 51 | Supply and laying in trenches /laid in floor/duct/drawn through conduit XLPE insulated,screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable 1100V grade with aluminum conductor of cross sectional area 10 sqmm 2 core complete all as specified and directed. |
| 52 | All as per item No-50.00 here-in-before but of size 10 sqmm 4 core. |
| 53 | All as per item No-50.00 here-in-before but of size 16 sqmm 4 core. |
| 54 | M&L for Earthing complete with galvanised steel earth electrode plate of size 600x600x6mm thick, buried directly in ground(earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.50m below normal ground level, connected to galvanised iron wire 4 mm dia as earth lead up to test point with suitable size GI nuts/bolts, washers,check nut and brazed properly up to main board,LT panel etc and adequate quantity of charcoal and salt 15 cm around the earth plate including earth pit in cement concrete 1:2:4 type B-1 using 20mm graded stone aggregates,40mm thick precast RCC cover in 1:2:4 reinforced with 8mm dia TMT bars 3 Nos both way including CI cover 10 mm thick with hinged and frame of angle iron 25x25x6mm with 6mm dia MS bar handle made to shape, excavation and earth work in any type of soil and including medium grade GI watering pipe 20mm bore with funnel and wire mesh and medium grade GI protection pipe 15 mm bore up to main board complete all as shown in electrical plate no 3 of MES schedule Part-I , connected to earthing testing point and testing on completion complete all as specified and directed. Note: (i) The unit rate includes 15 mm dia GI pipe up to 7.5m for protection of earth lead. (ii) The unit rate includesgalvanised iron wire 4 mm dia from earth electrode to test point up to 7.5 meter (iii) In case measured value of earth resistance of each earthing is recorded more than 3 ohms then the earthing shall be re done by the contractor without any extra cost to the Govt till desired result is obtained (iv) After completion of work earthing shall be tested by the contractor in presence of Engineer-in-Charge / JE E/M and proper record shall be maintained duly signed by all concerned. (v) Earth resistance tester shall be provided by the contractor. |
| 55 | S&F in repair Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4 mm dia galvanised iron or steel wire complete all as specified & directed. |
| 56 | M&L for Earthing complete with galvanised steel earth electrode plate of size 600x600x6mm thick, buried directly in ground(earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.50m below normal ground level, connected to galvanised iron strip of size 32 x 6 mm as earth lead up to test point with suitable size GI nuts/bolts, washers,check nut and brazed properly up to main board,LT panel etc and adequate quantity of charcoal and salt 15 cm around the earth plate including earth pit in cement concrete 1:2:4 type B-1 using 20mm graded stone aggregates,40mm thick precast RCC cover in 1:2:4 reinforced with 8mm dia TMT bars 3 Nos both way including CI cover 10 mm thick with hinged and frame of angle iron 25x25x6mm with 6mm dia MS bar handle made to shape, excavation and earth work in any type of soil and including medium grade GI watering pipe 20mm bore with funnel and wire mesh and medium grade GI protection pipe 40mm bore up to main board complete all as shown in electrical plate no 3 of MES schedule Part-I , connected to earthing testing point and testing on completion complete all as specified and directed. Note: (i) The unit rate includes 40 mm dia GI pipe up to 7.5m for protection of earth lead. (ii) The unit rate includesGI main earthing lead/strip of size 32x6 mm from earth electrode to test point up to 7.5 meter (iii) In case measured value of earth resistance of each earthing is recorded more than 3 ohms then the earthing shall be re done by the contractor without any extra cost to the Govt till desired result is obtained (iv) After completion of work earthing shall be tested by the contractor in presence of Engineer-in-Charge / JE E/M and proper record shall be maintained duly signed by all concerned. (v) Earth resistance tester shall be provided by the contractor. |
| 57 | S&F in repair Earth continuity conductor or main earthing lead or for lightening conductor fixed to wall on insulator 1 mtr distance or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required GI strip of size32 x 6 mm complete all as specified & directed. |
| 58 | M&L for Earthing complete with copper earth plate of size 600x600x3.15mm thick, buried directly in ground(earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.50m below normal ground level, connected to copper strip of size 20x3 mm as earth lead up to test point with suitable size copper coating nuts/bolts, washers,check nut and brazed properly up to main board,LT panel etc and adequate quantity of charcoal and salt 15 cm around the earth plate including earth pit in cement concrete 1:2:4 type B-1 using 20mm graded stone aggregates,40mm thick precast RCC cover in 1:2:4 reinforced with 8mm dia TMT bars 3 Nos both way including CI cover 10 mm thick with hinged and frame of angle iron 25x25x6mm with 6mm dia MS bar handle made to shape, excavation and earth work in any type of soil and including medium grade GI watering pipe 20mm bore with funnel and wire mesh and medium grade GI earth wire protection pipe 40mm bore up to main board complete all as shown in electrical plate no 3 of MES schedule Part-I , connected to earthing testing point and testing on completion complete all as specified and directed. Note: (i) The unit rate includes 40 mm dia GI pipe up to 7.5m for protection of earth lead. (ii) The unit rate includes copper main earthing lead/strip of size 20x3 mm from earth electrode to test point up to 7.5 meter (iii) In case measured value of earth resistance of each earthing is recorded more than 2 ohms then the earthing shall be re done by the contractor without any extra cost to the Govt till desired result is obtained .(iv) After completion of work earthing shall be tested by the contractor in presence of Engineer-in-Charge / JE E/M and proper record shall be maintained duly signed by all concerned. (v) Earth resistance tester shall be provided by the contractor. |
| 59 | S&F in repair Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required copper strip of size 20 x3 mm complete all as specified & directed. |
| 60 | S&F in repair Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required aluminium strip of size 20 x3.15 mm complete all as specified & directed. |
| 61 | S&F in repair Air termination, single pointed aluminium rod 12mm dia and 300mm long with existing Aluminium strip at any place complete all as specified & directed. |
| 62 | S&F Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified & directed. |
| 63 | M&L for Repair/Reconditioning of exisitng earth pit by removing carefully existing Earth PCC chambers and excavate the earth pit soil any type upto 3 feet length,3 feet width and 5 feet depth and adding 20 kg charcoal and 20 kg mixture of salt in alternate layers of 15 cm above the earth plate/electrode and moist the mixture using water , replacing of funnel with wire mesh,testing the earthing after reconditioning and earth resistance value must be within 2 Ohms, making good to distrubed surface complete all as specified & directed. Note: (i) The unit rate includes excavation, returning filling,removing ,20 kg charcoal and 20 kg mixture of salt,replacing of funnel with wire mesh and connected items etc. (ii) In case measured value of earth resistance of each earthing after Repair/Reconditiong is recorded more than 2 Ohms then the Repair/Reconditiong shall be re done by the contractor without any extra cost to the department till the desired result. |
| 64 | S&F Earth pit cover of size 480x480x330mm and 80 mm thick made out of plain cement concrete 1:2:4 type B-1 using 20mm graded stone aggregates for earth pit and 40mm thick precast RCC pit cover in 1:2:4 reinforced with 8mm dia TMT bars 3 Nos both way including CI cover 10 mm thick with hinged and frame of angle iron 25x25x6mm with 6mm dia MS bar handle made to shape with funnel and wire mesh complete all as specified & directed. |
| 65 | S&F in repair of Sheet metal enclosure for DB's double door VTPN 06 ways including 01 No MCCB 125 Amp 4 pole 16 KA to be used as incomer and outgoing as MCB single pole, deep drawn with 200 Amps rated copper bus bar 415 V, complete all as specified & directed. |
| 66 | S&F single pole and neutral sheet metal enclosure with a two pin and earth plug and socket complete with one single pole MCB of rating 32 Amps complete all as specified & directed. |
| 67 | S&F in repair triple pole and earth sheet metal enclosure with a three pin and earth plug and socket complete with one triple pole MCB of rating 63 Amps complete all as specified & directed. |
| 68 | M&L for sub main wiring with four single core 4 sqmm PVC insulated ,unsheathed , FRLS multistranded copper conductor 1100 volts grade cable in and including heavy grade PVC Casing & Capping ISI marked broken white or of cream colour with all accessories such as tee,bend,joint cover etc, screws, gutti / roul plugs PVC all as per site requirements including fixing on surface on stone walls / brick masonary walls /ceilings /floors etc with 4 sqmm PVC insulated,unsheathed, FRLS multistranded copper conductor 1100 volts grade cable as a continuous earth wire and connected to common earth dolly complete and making good to disturbed surfaces/wall with plaster & matching with the existing colour of wall/floor etc all as specified and colour coding of cables such as Phase- Red, Neutral-Black, and Earth-Green complete all as specified & directed.Note- Four runs of 4 sqmm single core cable and one run of 4 sqmm earth wire including PVC casing & capping together shall be measured as one unit. |
| 69 | M&L for sub main wiring with four single core 6 sqmm PVC insulated ,unsheathed , FRLS multistranded copper conductor 1100 volts grade cable in and including heavy grade PVC Casing & Capping ISI marked broken white or of cream colour with all accessories such as tee,bend,joint cover etc, screws, gutti / roul plugs PVC all as per site requirements including fixing on surface on stone walls / brick masonary walls /ceilings /floors etc with 6 sqmm PVC insulated,unsheathed, FRLS multistranded copper conductor 1100 volts grade cable as a continuous earth wire and connected to common earth dolly complete and making good to disturbed surfaces/wall with plaster & matching with the existing colour of wall/floor etc all as specified and colour coding of cables such as Phase- Red, Neutral-Black, and Earth-Green complete all as specified & directed. Note- Four runs of 6 sqmm single core cable and one run of 6 sqmm earth wire including PVC casing & capping together shall be measured as one unit. |
| 70 | M&L for sub main wiring with four single core 10 sqmm PVC insulated ,unsheathed , FRLS multistranded copper conductor 1100 volts grade cable in and including heavy grade PVC Casing & Capping ISI marked broken white or of cream colour with all accessories such as tee,bend,joint cover etc, screws, gutti / roul plugs PVC all as per site requirements including fixing on surface on stone walls / brick masonary walls /ceilings /floors etc with 10 sqmm PVC insulated,unsheathed, FRLS multistranded copper conductor 1100 volts grade cable as a continuous earth wire and connected to common earth dolly complete and making good to disturbed surfaces/wall with plaster & matching with the existing colour of wall/floor etc all as specified and colour coding of cables such as Phase- Red, Neutral-Black, and Earth-Green complete all as specified & directed. Note- Four runs of 10 sqmm single core cable and one run of 10 sqmm earth wire including PVC casing & capping together shall be measured as one unit. |
| 71 | S&F Modular white cover plate with frame, 1 module complete all as specified & directed. |
| 72 | S&F Modular white cover plate with frame, 3 module complete all as specified & directed. |
| 73 | S&F Modular white cover plate with frame, 4module complete all as specified & directed. |
| 74 | S&F Modular white cover plate with frame, 6 module complete all as specified & directed. |
| 75 | S&F Modular white cover plate with frame, 8 module complete all as specified & directed. |
| 76 | S&F in repair PVC Casing & Capping ISI marked broken white or of cream colour with all accessories such as tee,bend,joint cover etc, including fixing on walls/ Roof/ Ceilings or as per site requirement with proper all fixing arrangements of size 25 mm complete all as specified & directed. |
| 77 | S&F Modular white colour heavy duty plastic terminal boxes suitable for mounting of modular switch,socket,regulator ,1 module complete all as specified & directed. |
| 78 | S&F Modular white colour heavy duty plastic terminal boxes suitable for mounting of modular switch,socket,regulator ,2 module complete all as specified & directed. |
| 79 | S&F Modular white colour heavy duty plastic terminal boxes suitable for mounting of modular switch,socket,regulator ,3 module complete all as specified & directed. |
| 80 | S&F Modular white colour heavy duty plastic terminal boxes suitable for mounting of modular switch,socket,regulator ,4 module complete all as specified & directed. |
| 81 | S&F Modular white colour heavy duty plastic terminal boxes suitable for mounting of modular switch,socket,regulator ,6 module complete all as specified & directed. |
| 82 | S&F Modular white colour heavy duty plastic terminal boxes suitable for mounting of modular switch,socket,regulator ,8 module complete all as specified & directed. |
| 83 | S&F Modular white colour heavy duty plastic terminal boxes suitable for mounting of modular switch,socket,regulator ,10 module complete all as specified & directed. |
| 84 | S&F Modular white colour heavy duty plastic terminal boxes suitable for mounting of modular switch,socket,regulator ,12 module complete all as specified & directed. |
| 85 | S&F in Repair LED Bulbs 3 Watts, BEE star rated energy, efficient suitable for showcase light as per sample complete all as specified & directed. |
| 86 | S&F in Repair LED Bulbs 5 Watts, BEE star rated energy, efficient suitable for showcase light as per sample complete all as specified & directed. |
| 87 | S&F in Repair LED Bulbs 5 Watts,thread type BEE star rated energy, efficient suitable for jhumar light as per sample complete all as specified & directed. |
| 88 | S&F in Repair LED Bulbs 7 Watts, BEE star rated energy, efficient Retrofit bulb complete all as specified & directed. |
| 89 | S&F in Repair track mounted LED light fitting 10 watts 220 V, to provide focussed light complete all as specified & directed. |
| 90 | S&F in Repair LED spot light fitting 3 watt 220 V, round recessed mounted LED edge lit Slim downlight with die cast aluminium housing white powder coated complete all as specified & directed. |
| 91 | S&F in Repair LED spot light fitting 6 watt 220 V, round recessed mounted LED edge lit Slim downlight with die cast aluminium housing white powder coated complete all as specified & directed. |
| 92 | S&F in Repair LED spot light fitting 9 watt 220 V, round recessed mounted LED edge lit Slim downlight with die cast aluminium housing white powder coated complete all as specified & directed. |
| 93 | S&F in Repair LED spot light fitting 22 watt 220 V, round recessed mounted LED edge lit Slim downlight with die cast aluminium housing white powder coated complete all as specified & directed. |
| 94 | S&F Rigid PVC trunking white colour of 80 mm x 50mm with a long bodies & with flexible cover 65mm as per OEM, Legrand fixing on stone walls/ brick masonry walls/ceilings / floors etc. for running of all type of service/ miscellaneous cables complete with fitting such as joints/ Tee/ elbow / coupler etc, including taking down old PVC cable Trunking complete all as specified & directed.Make : Legrand, Cat No- 010452,( BODY) 010521 (COVER ) or techno-commercially equivalent in L&T/Schneider/Indo-asian |
| 95 | S&F flexible LED rope light of warm white colour with IP 65 of capacity 20 watt /Mtr including driver, adaptor and all accessories as per site requirement complete all as specified & directed.Make- Havells or techno-commercially equivalent in Philips,Bajaj,Wipro |
| 96 | S&F Decorative LED T type light fitting, 9/10 watt with three colour option(White, Warm white, Natural White) stainless steel, rust free fixture with driver, holders & LED lamp as per sample complete all as specified & directed. |
| 97 | S&F LED Light fitting, 4 feet 1x20 Watts, 220 volts, 3 in1 with three colour option (White, Warm white, Natural White) AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of size 1.5 sqmm from ceiling rose complete all as specified & directed. |
| 98 | S&F single core PVC insulated,unsheathed, FRLS multistranded copper conductor 1100 volts grade cable of size 2.5 sqmm , fixed in repairs, complete all as specified and directed. |
| 99 | S&F single core PVC insulated,unsheathed, FRLS multistranded copper conductor 1100 volts grade cable of size 1.5 sqmm , fixed in repairs, complete all as specified and directed. |
| 100 | S&F switch socket combination, 5 pin, 5 Amp,with box , 230 volt complete all as specified & directed. |
| 101 | S&F switch socket combination 2 in 1 6 pin 6/16 Amp with box 230 volt complete all as specified & directed. |
| 102 | S&F LED tube rod , 4 feet 20 Watts, 220 volts complete all as specified & directed. Total in Figures 0.0 23 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail