| 1 | HI - WALL SPLIT SYSTEMS - Supply,installation, testing and commissioning of Air Cooled HI Wall split type Air conditioners complete with Indoor unit (IDU), Out door unit (ODU), i/c R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cut off and50 hz ,1 phase AC Supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll /rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS694 or IS 9968 temperature sensing control IS/ International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per IS :1391 Part II 2023. The system shall be able to operate up to 50 Degree C (out door ambient temperature). The indoor outdoor must be Blue Fin coated. The unit price included with 3mtr Copper piping with insulation, drain Pipe and copper Power cable. The indoor should have 4 way swing . 5 Star Inverter Type - Cooling only (Category II Make :- LG/ O General/ Daikin) - 1.0 TR with 5 Star BEE Rating (LG-AS-Q14ENZE/ O General-ASGG12CGWA-B/ Daikin-FTKU35XV16) |
| 2 | 1.5 TR with 5 Star BEE Rating (LG-AS-Q20JWZE/ O General-ASGG18CGWA-B/ Daikin-FTKU50XV16) |
| 3 | 2.0 TR with 5 Star BEE Rating (O General-ASGG24CGWA-B/ Daikin-FTKM60XV16) |
| 4 | REFRIGRANT PIPING-- Supply,installation of hard/soft copper refregrant piping of size 5/8 inch and 1/4 inch for suction and liquid line with 3 corex4 sqmm FRLS Copper control cable alongwith 25 mm Factory laminated GC Cloth weather proof closed cell nitrile insulation ,complete with fitting of bends and other nesessary material to complete the job. 1 TR to 3 TR high wall split A.C |
| 5 | FRAME WORK-- Supply,installation & fabrication of MS base frame for both indoor and outdoor unit and other nesessary material to complete the job.1 TR to 3 TR high wall split A.C |
| 6 | DRAIN PIPING- Supply,installation & fabrication of Insulated drain water piping from indoor to nearestdrain point separate to all and other nesessary material to complete the job. 25mm nom. Dia pipe |
| 7 | Supply and fixing of 5kVA Voltage stabilizer (Make-V-Guard/Microtek) |
| 8 | Supply and fixing of 4pole MCCB in cubicle pannel board - S/F of 100AMP 25KA MCCB of Hager/Legrand/C&S Make with MS box including both side connections with all complete |
| 9 | Supply and fixing of copper bus bar with suitable sheet metal enclosure on MS angle frame with proper grouting on wall including all connections. - 100Amp TPN bus bar-300 X 32 X 3mm size |
| 10 | Recessed submain wiring alongwith earth wire with the following sizes of PVC insulated single core multistrand copper conductor ISI marked conforming to IS-694/1990 in 20mm dia non metallic heavy duty flexible conduit 1.6 mm in surface /recessed PVC conduit as required (make of wire -Finolex/L&T/Anchor/Havells/V-Guard/KEI/RHINO) - 2 X 4sq.mm +1 X 1.5sqmm. |
| 11 | TPN DISTRUBUTION BOARD - Supplying and fixing of following mentioned way, three pole/single pole and neutral, sheet steel,double door MCB distribution board, 415 volts/240 volts shall be as per IEC 61439-3,integrated door earthing system offering additional safety to the user,High quality polyurethane Gasket,the box and cover shall be fabricated to withstand IK09,the DB should be properly pre-treated with 7 tank process and duly powder coated, phosphatized with powder coated finish, on surface/recess, complete with terminal blocks,with suitable size FR PVC insulated copper conducter up to terminal blocks, tinned copper busbar, neutral busbar, earth bar, din bar. Make-LEGRAND-Ekinox3 DB/ Siemens-Betaguard/ Schneider- Acti 9/ABB Itus as per direction of Engg.-in-Charge. The Distribution boards should be Replacement Warranty will be 3 years - 4 Way(8+12) Way TPN MCB DD DB Horizontal Type as per IEC 61439-3 suitable for Flush mounting and Surface mounting with 100A Copper Bus Bar for each phase, with neutral Bus bar, Earth Bar & Cable ties for cable management, prefitted masking sheet, IP43-IK09 with metal door Warranty on DB is 3 years (FOR LIGHT,UPS DB,PDB) |
| 12 | Supplying and fixing 6 amps to 32 amps rating, 240 volts, C series, single poles MCB of Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 . the existing MCB DB complete with connections as per direction of Engg.-in-Charge. The MCB should be Replacement Warranty will be 1 years. |
| 13 | Supplying and fixing 63Amps 4P 415 volts MCB 415 volts, C series,10KA breaking capacity, Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB with connections as per direction of Engg.-in-Charge..Warranty on MCB is 3 years. |
| 14 | Supplying of one number PVC insulated armoured and PVC sheathed XLPE property AL. conductor power cable of 1.1 KV grade Make- Finolex/Polycab/HAVELLS/RR KABLE/KEI/Gloster of following size cables as per direction of Engg.-in-Charge. - 3.5core x 50 sq mm Please Enable Macros to View BoQ information |