| 1 | Dismantling interconnection between equipments using ACSR Moose/ Kundah/ wolf Single conductor at both ends with compressed/ bolted ends including uncoiling and cutting of conductor as per the direction of departmentalofficers. |
| 2 | Dismantling of 1 set of 3 pole EHT 110/66kV Circuit breaker from the already erected structure of above 1.5m height , including dismantling the structure,leading with an initial lead of 50m to storage place carefully keeping at vertically not allowing tilting from verticalposition more than the specified angles, keeping lines and levels as per the direction of the departmental officers, including all labour charges, hire charges of tools & tackles etc. |
| 3 | Providing interconnection between equipments using ACSR Moose/ Kundah/ wolf Single conductor at both ends with compressed/ bolted ends including uncoiling and cutting of conductor as per the direction of departmental officers. |
| 4 | Unpacking carefully and leading leading with an initial lead of 50 m, one set of 3 pole EHT110/66KV Circuit Breaker from the place of storage, including support structure , mechanism box compressor, pipe lines etc. to site , cleaning and erecting on foundation using suitable lifting tools, after disassembling necessary parts if required, to lines and levels and assembling all the parts ,connecting mechanism etc. in complete shape and making ready for commissioning as per the direction of departmental officers |
| 5 | Laying of departmentally supplied GI strip/Copper stripof suitable size including cleaning and neatly bending of strips ,cutting, removing of metal/earth in the yard and burying earth strip to the required depth re-doing the yard metalling as per the direction of the departmental officers. |
| 6 | Welding overlapping joints of 50x6mm GI strip with 50mm long, 6mm thick welding on all three sides after doing 2 Nos. bolted joints at the centre as specified after cleaning the surface. Charges includes hire charges of DC arc welding set, current charges, cost of low hydrogen content DC arc welding electrodes( No.E7018) cost of anti corrosive paint etc.complete. |
| 7 | Welding one end of the bended GI strip of size 50x6mm with the riser of the already laid earth mat, welding 150mm in length, 6mm thick on both sides & end of the strip & other end of the strip with yard structure at 2 points 50mm apart each welding points having 50mm length and 6mm thick on both sides & end of the strip including the charges for connecting the strip with structure using bolted joints as per the directions of the department officers. Charges includes hire charges of DC arc welding set, current charges, cost of low hydrogen content DC arc welding electrodes(No.E7018) cost of anti corrosive paint etc. complete |
| 8 | Welding one end of the GI strip 50x6mm with the structure with a welding length of 50mm & 6mm thickness on both sides & end of the strip and connecting other end with bolts & nuts if required including hire charges of DC arc welding set, current charges, cost of low hydrogen DC arc welding electrodes (No.E7018) cost of anti corrosive paint etc.complete. |
| 9 | Termination of cables in panel by using cable glands of fixing the cable rigidly by any means as per direction of departmental staff at site charges include for providing necessary suitable hole in the gland plate etc. for 20/19 core 2.5sqmm cable/12 core 4 sqmm cable (using gland of size 28-32mm) |
| 10 | Termination of cables in panel by using cable glands of fixing the cable rigidly by any means as per direction of departmental staff at site charges include for providing necessary suitable hole in the gland plate etc. for 12/7/6 core 2.5 sqmm cable (using gland of size 25mm). |
| 11 | Doing termination of all sizes of PVC insulated copper control cable 2.5 mm²,pealing, providing number and letter ferrules in the wire, stripping ends, crimping with suitable lugs and connecting to the terminals in the panel board and marshalling kiosk etc., neatly and carefully including cost of copper sockets and ferrules as per the direction of Departmental Officers at site |
| 12 | Preparing wiring schedule per transformer / feeder bay of 110 or 66kV with details of type of cable, core and colour, ferrule No. and terminal no of quipments/panels including giving full details in A4 sheet with computer print providing outer border line and sheet no etc. and supplying in the shape of book with special binding etc. and assisting the departmental officers at the time of relay testing and commissioning |
| 13 | Picking up and removing 40mm stone aggregate spread in the yard and stacking at a suitable place in standard heaps for reuse as per the direction of department staff |
| 14 | Collecting the spread sand/6mm stone aggregates from the yard and stacking the same in standard heaps at suitable places up to a lead of 50 m for reuse as per the direction of the departmental staff at the site |
| 15 | Demolishing R.C.C. work manually / by mechanical means including stacking of steel bars and disposal of unserviceable material with in 50 metres lead as per direction of Engineer -in-Charge |
| 16 | Earth work in excavation by mechanical means (Hydraulic excavator )/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.Ordinary rock |
| 17 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:3:6 ( 1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) |
| 18 | Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete |
| 19 | Extra for scrapping,cleaning and straightening reinforcement from R.C.C. or R.B work. |
| 20 | Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo -Mechanically Treated bars of grade Fe-500D or more |
| 21 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement All work up to plinth level:1:1:5:3 (1 cement 1.5 coarse sand :3 graded stone aggregate 20 mm nominal size |
| 22 | 12 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand) |
| 23 | Spreading Sand/6 mm stone aggregate stacked at Substation compound in levels of 10 cm thick, lead upto 50 m as per the direction of departmental officers in charge |
| 24 | Spreading 40 mm metal stacked at the Substation compound in levels of 15 cm thick, lead upto 50 m as per the direction of departmental officers in charge |
| 25 | Close timbering in trenches including strutting, shoring and packing cavities (wherever required) complete (Measurements to be taken of the face area timbered).Depth not exceeding 1.5m |
| 26 | Extra for cutting reinforcement bars manually/ by mechanical means in R.C.C. or R.B. work ( Payment shall be made on the cross sectional area of R.C.C.or R.B work) as per direction of Engineer-in-charge |
| 27 | Quoted Amount of BOQ1 in figures |
| 28 | GST Rate in percentage Please Enable Macros to View BoQ information |