| 1 | Cat (A) -Items to be supply and fixing |
| 2 | Dismantling/taking down carefully existing conduit pipe and other accessories. All as specified and direction by E-I-C. |
| 3 | Supply and fixing wiring for circuits in 19mm steel conduit along with wiring accessories with 2X2.5 Sq.mm+1X1.5 Sq.mm as a earth wire (in each meter length) heavy duty 1100V grade, 50Hz AC PVC insulated, PVC sheathed multistranded copper conductor as per IS: 694-1990 make-Havells/Polycab/Indicab or Equivalent for carrying out wiring of circuit of any length form DB/Switch upto load point. All as specified and direction by E-I-C. |
| 4 | Supplying & Drawing of 2X2.5 Sq.mm + 1X1.5 Sq.mm as a earth wire (in each meter length) heavy duty 1100V grade, 50 Hz AC PVC insulated, PVC sheathed, multistranded copper conductor as per IS: 694-1990 make-Havells Polycab/Indicab or Equivalent for carrying out wiring of a circuit of any length from DB/switch upto load point. All as specified and direction by E-I-C. |
| 5 | Supply & drawing of 2X6 Sq.mm + 1X4 Sq.mm as a earth wire (in each meter length) heavy duty 1100v grade, 50 Hz AC PVC insulated, PVC sheathed, multistranded copper conductor as per IS:694-1990 make-Havells/Polycab/Indicab or Equivalent for carrying out wiring of a circuit of any length from DB/switch upto main switch. All as specified and direction by E-I-C. |
| 6 | Supply and fixing of Flame proof 4 WAY Junction box. Material aluminium dia costing LM6, 16A, 250V, four side wire entry through steel conduit having threaded 19 mm BSW with metallic blanking plug -04 Nos. all as per the direction of E-I-C. |
| 7 | Supply and fixing of Earth continuity conductor/earthing of 2 mm G. I. steel wire drawn along with conduit properly fix to the conduit with copper clips. All as specified and direction by E-I-C. |
| 8 | Supply, Fixing & Connection of sheet metal enclosure for DB, Double door, TPN 415 V, 04 Way, per phase complete fixed with (Make-L&T, ABB OR Equivalent) a) 4 pole MCB TPN, 63 A MCB, 10KA – 01 no. Make-L&T, ABB OR Equivalent (incomer)b) SP, 10A MCB, 10KA-12 no. Make – L&T, ABB or Equivalent. All as specified and direction by E-I-C. |
| 9 | Excavating for earth pit, n. exc. 1.5m wide and n. exc. 1.5m in depth n soft/loose soil and getting out etc. All as per specified & Direction by E-I-C. |
| 10 | Supply and fixing of Earthing complete with G. I. earth plate electrode 600x600x6mm thick buried directly in the ground vertically to a depth not less than 2.25 meter below normal ground level with top edge of the earth plate at a depth not less than 1.5 meter below ground level, connected to galvanised earth strip 25x4mm as earthing lead upto test point, all as specified and shown in electrical plate no. 3 of SSR part II and testing on completion etc. all as per the direction of E-I-C. |
| 11 | S & F of G. I. Steel tubes of medium grade of 32mm bore as per IS-1239/1990 for protection of earthing strip in earthing chamber etc. as per the direction of E-I-C. |
| 12 | Supply & fixing of G. I. steel tube of medium grade of 50mm bore for lighting protection rod purposed etc all as per the direction of E-I-C. |
| 13 | S&F of G. I. Steel tubes of medium grade of 20mm bore as per IS-1239/1990 for watering pipe in earthing chamber etc. as per the direction of E-I-C. |
| 14 | Supply & fixing air termination single point aluminium rod 12mm dia and 300mm long. All as per the direction of E-I-C. |
| 15 | Supply & fixing test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. Head screw. As per the direction of E-I-C. |
| 16 | Supply & fixing aluminium strip 25x3.15mm for roof conductors and down conductors above ground. As per the direction of E-I-C. |
| 17 | Supply & fixing of porcelain insulator for down conductor and roof conductor mesh. Por. Insulator suitable size for 25x3.15mm aluminium strip. As per the direction of E-I-C. |
| 18 | Supply & fixing Galvanised iron strip 25x4mm buried in ground. As per the direction of E-I-C. |
| 19 | Supply and fixing LED street light fitting 35 to 45 Watt 230 AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete. As per the direction of E-I-C. |
| 20 | Supply & fixing of LED FLP well glass luminaries with inbuilt LED 23 to 26 Watt, material cast aluminium alloy LM6, top wire entry though steel conduit having threaded 19mm BSW with metallic blanking plug – 02 Nos for side entry. Finish inside/outside light grey epoxy powder coating shade No. 631 as IS:5 earthing 1 inside & 2 outside earthing screws of M6 with 2 No. plain washer, stainless gasket “O” ring endless neoprene rubber gasket, Ms wire guard with white epoxy powder coating heat resistance glass. Make - Sudhir or equivalent (Note-FLP certificate from CIMFR Dhanbad to be provided by firm). All as specified and direction of E-I-C. |
| 21 | Returning, filling in including spreading, levelling and well ramming in layers of excavated soft loose soil in trenches etc., as per the direction of E-I-C. |
| 22 | M&L for provision of cement concrete earth pit chamber of type B-2 1:2:4 40mm graded aggregate etc. for i) Earth pit of size 0.5x0.5x0.5mt. having 10cm wall thick inside with cover of size 0.35x0.35x0.05mt. with 8mm rod 2 No. hinged inside.ii) Earth pits platform for size 1x1x0.10mt. outside & 0.3x0.3x0.250mt fixing of earth pit chamber inside and other civil work. Including necessary formwork. All as per the direction of E-I-C. |
| 23 | Cat (B) - Buy Back Items |
| 24 | Credit of old well glass fitting and other accessories. All as specified and direction by E-I-C. |
| 25 | Credit of old removed wiring material which consist of steel conduit and wire. All as specified and direction by E-I-C. Please Enable Macros to View BoQ information |