| 1 | Re-electrification of SCT bhavan ground floor at FACT UC |
| 2 | Supply, erection, termination and servicing of single/double door 4 way, VTPN Three phase DB having the following specifications:1) 100A 4 pole MCCB incomer - 1 No 2) 63A Three pole MCB -2 Nos Remaining module spaces has to be covered with dummy. DB has to be flush mounted on to the wall. |
| 3 | Supply, erection, termination and servicing of single/double door 6 way, 415 Volts TPN power DB, having the following specifications:1) 63A 4 pole isolator-1 no2) 63A 30mA 4 pole RCCB-1 no3) 16A single pole B curve MCB- 18 nosDB has to be flush mounted on to the wall. |
| 4 | Supply, erection, termination and servicing of single/double door 12 way, 415 Volts TPN AC DB, having the following specifications:1) 63A 4 pole isolator-1 no2) 63A 30mA 4 pole RCCB-1 no3) 32A Double pole C curve MCB- 16 nosDB has to be flush mounted on to the wall. Remaining module spaces has to be closed by blanking plates |
| 5 | Supply, erection, termination and servicing of single/double door 16 way, 230 Volts SPN Emergency DB, having the following specifications:1) 40A 2 pole isolator-1 no2) 40A 30mA 2 pole RCCB-1 no3) 10A single pole B curve MCB- 12 nosDB has to be flush mounted on to the wall |
| 6 | Point wiring over/through beam/wall / column / ceiling /cable trays with individual control for light / fan/ bell/ 6A modular plug sockets separately mounted , using FRLS flexible copper wires of 1.5 sq.mm for phase, neutral and earth connection through PVC conduit of minimum size of 20mm with ISI marking, as per relevant drawings or instructions from FACT engineer. Scope of work include preparation and fixing of PVC conduits,modular switch boards, switches, cover plates,dummy plates etc, fixing ceiling roses on suitable junction boxes, modular step type regulators for fans(as required), drawing flexible copper wires of 1.5 sq.mm, connecting, testing and commissioning. The PVC conduit fixing shall either be open or concealed. The cutting of wall and replastering for concealed conduit fixing is mentioned as separate schedule of work. All the switch boards must be fixed concealed, unless asked to fix on surface. If required, holes through wall need to be made for conduit passing. For a point wiring,pipe length of 10 metres shall be considered as one point and pipe length above 10m and less than 20m shall be considered as one and half points and if additional power sockets are provided in same Switch Boards that shall be considered as half point. Sockets shall be shutter type. All the materials required for wiring such as copper flexible wires, PVC conduits, metallic modular switch boards, modular switches, cover plate, dummy plates, PVC box for fixing ceiling rose, PVC Junction boxes(2/3/4 way) etc. shall be in the scope of contractor. Ivory color PVC conduit shall be used for open conduit wiring. If any wiring need to be concealed that portion may be executed with black/ivory color PVC conduits. Suitable lengths of PVC flexible hose shall be used for point wiring above false ceiling as per the requirement. |
| 7 | Looping of point wiring upto 6m for PVC conduit point wiring over/through beam/wall / column / ceiling/ cable trays for lights,using FRLS flexible copper wires of 1.5 sq.mm for phase, neutral and earth connection through PVC conduit of minimum size of 20mm with ISI marking, as per relevant drawings or instructions from FACT engineer. Scope of work include preparation and fixing of PVC conduits, fixing ceiling roses on suitable junction boxes, drawing flexible copper wires, connecting, testing and commissioning. The PVC conduit fixing shall either be open or concealed. The cutting of wall and replastering for concealed conduit fixing is mentioned as separate schedule of work. All the switch boards must be fixed concealed, unless asked to fix on surface. All the materials required for wiring such as copper flexible wires, PVC conduits, PVC box for fixing ceiling rose, PVC Junction boxes(2/3/4 way) etc. shall be in the scope of contractor. Ivory color PVC conduit shall be used for open conduit wiring. If any wiring need to be concealed that portion may be executed with black/ivory color PVC conduits. Suitable lengths of PVC flexible hose shall be used for point wiring above false ceiling as per the requirement.For looping point wiring, pipe length upto 6 metres shall be considered as one loop point. |
| 8 | PVC conduit point wiring from DB to switch board or between switchboard to switch board looping along/through beam/wall / column / ceiling/cable trays using 2.5 sq. mm FRLS flexible copper wires for phase, neutral and earth through PVC conduit of minimum size 20mm with ISI marking, as per relevant drawings or instruction from FACT engineer.Scope of work include preparation and fixing of suitable junction boxes if required, drawing flexible copper wires of 2.5 sq.mm, connecting, testing and commissioning are under the scope of contractor.The work shall include preparation and fixing of PVC conduits, drawing wires as required, fixing suitable junction boxes etc., wire termination, testing and commissioning. The PVC conduit fixing shall either be open or concealed. The cutting of wall and replastering for conduit concealing is mentioned as separate schedule of work. If required, holes through wall need to be made for conduit passing. Ivory color PVC conduit shall be used for open conduits. If any wiring need to be concealed that portion may be executed with black/ivory color PVC conduits. For a point wiring, 10 metres shall be considered as one point and pipe length greater than 10 metres shall be considered as one and a half point, upto 20m. All the materials required for wiring such as copper flexible wires, PVC junction boxes(2/3/4 way), etc. shall be in the scope of the contractor. |
| 9 | Point wiring over/through beam/wall / column / ceiling with individual control for 25 A modular plug socket for Air conditioners by using 25A DP modular switch. Individual plug socket shall be placed near Air Conditioner and switch shall be at standard height from ground. Wiring shall be using 4 sq.mm FRLS multi strand flexible copper wire for phase, neutral and earth connections, through PVC conduit of minimum size of 20mm with ISI marking. The work shall include preparation and fixing of conduits and drawing wires through 20mm PVC pipe from DB to modular switch and to socket as required, preparation and fixing of modular switch boards, switches, plug sockets, cover plates, dummy plates, suitable junction boxes etc., wire termination, testing and commissioning. The PVC conduit fixing shall either be open or concealed. The cutting of wall and replastering for concealed conduit fixing is mentioned as separate schedule of work. All the switch boards must be fixed concealed, unless asked to fix on surface.For a point wiring, 10 metres shall be considered as one point and Pipe length above 10m shall be considered as one and half points, upto 20m. All the materials for this Work including PVC conduits, copper flexible wires, 25 A Plug socket, 25 A DP switch etc. shall be in the Scope of the contractor. |
| 10 | Supply of 25 A modular plug socket and 25A DP modular switch, same as item used in schedule no.08 |
| 11 | Point wiring over/through beam/wall / column / ceiling with individual control for 16 A modular plug sockets with SP switch. Individual plug socket with switch. Wiring shall be using 2.5 sq.mm FRLS multi strand flexible copper wire for phase, neutral and earth connections, through PVC conduits of minimum size 20 mm with ISI mark. The work shall include preparation and fixing of PVC conduits, wiring along wall and drawing wires as required,preparation and fixing of modular switch boards, switches, plug sockets, cover plates, dummy plates, suitable junction boxes etc., wire termination, testing and commissioning. Sockets shall be 6/16A type. The PVC conduit fixing shall either be open or concealed. The cutting of wall and replastering for concealing conduit fixing is mentioned as separate schedule of work. All the switch boards must be fixed concealed, unless asked to fix on surface. If required, holes through wall need to be made for conduit passing. Ivory color PVC conduit shall be used for open conduits. If any wiring need to be concealed that portion may be executed with black/ivory color PVC conduits. For a point wiring, 10 metres shall be considered as one point and Pipe length above 10m shall be considered as one and half points, upto 20m. |
| 12 | Supply of 4Cx25 sq.mm XLPE Aluminium armoured Cable |
| 13 | Supply of 4Cx16 sq.mm XLPE Aluminium armoured Cable |
| 14 | Supply of 4Cx35 sq.mm XLPE Aluminium armoured Cable |
| 15 | Laying and clamping of cable of size 4Cx16 sq.mm to 4Cx35 sq.mm XLPE Aluminium armoured Cable. Scope of work includes :1) Laying cable through MS cable trays/walls/trenches/GI pipes by properly clamping the cable at distance not exceedding 50 cm with aluminium clamps/ GI metal saddles.2) Holes through walls should be made by the contractor if required.All the materials including clamps, fasteners etc. required for this work are under the scope of contractor. |
| 16 | Glanding and termination of Aluminium armoured cables of size 4CX 16 sq.mm using single/double compression glands. All the materials including cable, glands of required sizes, lugs, fasteners etc. required for this work is under the scope of contractor. |
| 17 | Glanding and termination of Aluminium armoured cables of size 4CX 25 sq.mm using single/double compression glands. All the materials including cable, glands of required sizes, lugs, fasteners etc. required for this work is under the scope of contractor. |
| 18 | Glanding and termination of Aluminium armoured cables of size 4CX 35 sq.mm using single/double compression glands. All the materials including cable, glands of required sizes, lugs, fasteners etc. required for this work is under the scope of contractor. |
| 19 | Supply, fixing and servicing of recess mounting LED downlighter including all accessories and having the following specifications: Power supply: 220-240V, 1 ph, 50Hz, round/square shape, Cool day light colour, Wattage: 30±2 W, >85 Lm/Watt |
| 20 | Supply of recess mounting LED downlighter including all accessories as spares for the work specified in Schedule No- 18, along with mounting bracket. |
| 21 | Supply, fixing and servicing of surface mounting LED light including all accessories and having the following specifications: Power supply: 220-240V, 1 ph, 50Hz, round/square shape, Cool day light colour, Wattage: 30W, >85 Lm/Watt |
| 22 | Supply of surface mounting LED light including all accessories as spares for the work specified in Schedule No- 20, along with mounting bracket. |
| 23 | Supply, fixing and servicing of surface mounting LED light including all accessories and having the following specifications: Power supply: 220-240V, 1 ph, 50Hz, round/square shape, Cool day light colour, Wattage: 3-6W |
| 24 | Supply of surface mounting LED light including all accessories as spares for the work specified in Schedule No- 22, along with mounting bracket if available for the model. |
| 25 | Supply, fixing and servicng of recess mounted profile lighting. The scope of work includes fixing of aluminium profiles(min 25mm width) after cutting false ceilings/supports/blanking plates if required, supply and installing LED strip lights (cool white/warm/neutral white), drivers (as per the requirement) and diffusers of reputed make without any dark points, wiring, connection and commissioning of the profile light. All the required materials including blanking plates, aluminium profiles, drivers, diffusers, LED strips, connectors etc shall be supplied by the contractor. The LED strip supplied shall have minimum 240 LEDs/meter and shall have OEM warranty/guarantee of minimum 1 year. |
| 26 | Supply of identical LED strips used for executing profile lighting as in schedule no.24 |
| 27 | Supply, Fixing and servicing of exhaust fan of sweep 225mm of metal body . All accessories and fasteners required for the completion of work are in the scope of contractor. |
| 28 | Supply, installation and servicing of 400mm remote controlled BLDC wall fan with suitable clamps/fasteners. Supply of all materials required for the work shall be under the scope of the contractor. The service value of wall fan shall be higher Than 5.5 CMM/Watts.(Refer BEE Guide lines for service value and Star Ratings) |
| 29 | Cutting into walls for executing concealed PVC conduit wiring and replastering after the work. All the tools & materials for this work shall be under the scope of the contractor |
| 30 | Open/conceiled fixing of 25mm ISI marked PVC conduit through wall. The work include chipping through wall, fixing of PVC conduit and replastering back to normal or clamping though wall/ceilings etc.All the items required for the works like PVC conduits, PVC junction boxes with inspection cover (if required), clamps etc. are under the scope of contractor |
| 31 | Supply of 5 nos spare LED drivers for each type of LED light fittings mentioned in schedules 18 and 20. |
| 32 | Supply and concealed fixing of 6 modular metallic box with frame and plate suitable for fixing modular type RJ11 telephone sockets. |
| 33 | Supply of RJ11 telephone socket with shutter. |
| 34 | Supply of dummy plates for modular box mentioned in schedule 31 |
| 35 | Supply of 20 nos of 6A switches, 10 nos 6A sockets, 5 nos 16A switches, 5 nos 16A sockets and 5 nos of fan regulators of the same make and model used for the point wiring |
| 36 | Core cutting through wall of diameter 2.5 to 4 inch. The required machinery for core cutting shall be brought by the contractor. Please Enable Macros to View BoQ information |