| 1 | Excavation in trenches in hard/dense soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying of cables and foundation of poles etc. and getting out, complete all as specified and directed. |
| 2 | All as per item No-1 here-in-before but depth exceeding 1.5 Sqm but n.exc 3.0m, complete all as specified and directed. |
| 3 | Returning, filling in trenches (soil), including spreading, leveling and well ramming in layers not exceeding 25 cm thick, complete all as specified and directed. |
| 4 | Removal of surplus excavated soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5metre above the starting point, complete all as specified and directed. |
| 5 | M&L for sand cushioning to U/G cable in layers of 23 cm thick (8 Cm before laying the cable and 15 Cm thick after laying the cable) in trenches complete all as specified and directed. Note :- Only Puned down volume shall be measured. |
| 6 | Supply and laying un-reinforced precast concrete cable cover, class HV, Type I, flat size 300 mm x 180 mm x 40 mm laid dry for protection of UG cable complete all as specified and directed |
| 7 | Dismantling / Taking out unserviceable HT cables for replacement of any size from any position i.e ground / walls / poles / culverts etc complete with protection pipe all as specified and directed . (Note : Earth work shall be measured and paid separately) |
| 8 | Supply, laying , jointing and testing (in replacement) of HT XLPE cable 120 Sqmm 3 core, 11000 volt screened, PVC bedded \\"Earthed grade\\" insulated bedded, galvanised steel (Heavy duty) strip armoured with aluminium conductor 11 KV pressure earth system laid in pipe /ducts/trenches, under floor and road or fixed to wall etc complete cross-sectional area of cable 120 sqmm 3 core, all as specified and directed . |
| 9 | Supply, laying , jointing and testing (in replacement)of HT XLPE cable 95 Sqmm 3 core, 11000 volt screened, PVC 'E' grade insulated bedded, galvanised steel (Heavy duty) strip armoured with aluminium conductor 11 KV pressure earth system laid in pipe /ducts/trenches, under floor and road or fixed to wall etc complete cross-sectional area of cable 95 sqmm 3 core, all as specified and directed |
| 10 | Supply, laying , jointing and testing (in replacement)of HT XLPE cable 300 Sqmm 3 core, 11000 volt screened, PVC 'E' grade insulated bedded, galvanised steel (Heavy duty) strip armoured with aluminium conductor 11 KV pressure earth system laid in pipe /ducts/trenches, under floor and road or fixed to wall etc complete cross-sectional area of cable 300 sqmm 3 core, all as specified and directed |
| 11 | Material & labour for taking out the existing defective 3 core 95 sqmm to 300 sqmm HT cable from trenchs inclduing cable cover from ploes/ drains/ under roads and relaying the cable after rectifying the defects, complete all as specified and directed.Note :- Necessary earth work shall be measured and paid separately. |
| 12 | M & L in replacement of GI tubing light grade for passing through cables under the floor ,along the wall or along the pole of 100 mm bore and fixed to the poles/walls with suitable size of MS clamps and nut and botls/washers etc including taking down old GI tubing complete all as specified. |
| 13 | M & L in replacement of GI tubing light grade for passing through cables under the floor ,along the wall or along the pole of 150 mm bore and fixed to the poles/walls with suitable size of MS clamps and nut and botls/washers etc including taking down old GI tubing complete all as specified. |
| 14 | M&L in replacement of lightning arrester 11000 volts non linear resister, line discharge class-2, nominal discharge 10 KA and high discharge 65 KA assembly complete suitable for 11 KV including all clamps, nuts, bolts and washers and connecting to earth with 4 mm dia GI wire all as specified and directed. |
| 15 | M&L in replacement of outdoor end terminal joints cold shrinkable Suitable for HT 11000V (Earthed), XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 3 core 120 Sqmm to 185 Sqmm size cable all as specified and directed. |
| 16 | M&L in replacement of outdoor end terminal joints cold shrinkable Suitable for HT 11000V (Earthed), XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 3 core 95 Sqmm size cable all as specified and directed. |
| 17 | M&L in replacement of indoor end terminal joints cold shrinkable Suitable for HT 11000V (Earthed), XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 3 core 120 Sqmm to 185 Sqmm size cable all as specified and directed. |
| 18 | M&L in replacement of indoor end terminal joints cold shrinkable Suitable for HT 11000V (Earthed), XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 3 core 95 Sqmm size cable all as specified and directed. |
| 19 | M&L in replacement of outdoor end terminal joints Heat shrinkable Suitable for HT 11000V (Earthed), XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 3 core 120 Sqmm to 185 Sqmm size cable all as specified and directed. |
| 20 | M&L in replacement of outdoor end terminal joints Heat shrinkable Suitable for HT 11000V (Earthed), XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 3 core 95 Sqmm size cable all as specified and directed. |
| 21 | M&L in replacement of indoor end terminal joints Heat shrinkable Suitable for HT 11000V (Earthed), XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 3 core 120 Sqmm to 185 Sqmm size cable all as specified and directed. |
| 22 | M&L in replacement of indoor end terminal joints Heat shrinkable Suitable for HT 11000V (Earthed), XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 3 core 95 Sqmm size cable all as specified and directed. |
| 23 | M&L in replacement of straight through joints cold shrinkable Suitable for HT 11000V, XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 3 core 95 Sqmm size cableall as specified and directed. |
| 24 | M&L in replacement of straight through joints cold shrinkable Suitable for HT 11000V, XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 3 core 120 Sqmm to 185 Sqmm size cable all as specified and directed. |
| 25 | M&L in replacement of straight through joints heat shrinkable Suitable for HT 11000V, XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 3 core 220 Sqmm to 300 Sqmm size cable all as specified and directed. |
| 26 | M&L in replacement of end termination joints heat shrinkable Suitable for HT 11000V, XLPE insulated armoured Heavy duty under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable of cross sectional area 3 core 220 Sqmm to 300 Sqmm size cable all as specified and directed. |
| 27 | M&L in replacement of HT Cable route indicator, made up of cast iron suitable size complete all as specified and directed. |
| 28 | S&F in replacement of steel tubular swaged pole type 410 SP 55 (11 Mtr Long) complete with cast iron base plate/final taper plug, bolt, nuts and washers including excavation earth work in any type of soil, PCC 1:4:8 type D-2 using 40mm graded stone aggregate as in plinth block ,PCC copping, including aluminium painting over a coat of red oxide primer on external surface including writing pole numbers with black lettering on white background and making black & yellow strips upto 1.5 mtr height complete as specified and directed by engr-in-charge. |
| 29 | S & F Pin type insulator porcelain,vitreous,white,brown or green including one galvanised spindle, two galvanised iron washer and one galvanised iron nut 150 mm height , 150 mm dia for 11 KV grade complete incl dismantling old u/s all as specified and as directed |
| 30 | S & F Disc type insulator porcelain,vitreous,145 mm high and 255 mm dia ball and socket type white, brown or green insulator single disc assembly for tension with tension clamps for conductors working pressure 11000 V complete incl dismantling old u/s all as specified and as directed |
| 31 | Dismantling and Taking out Transformer from its position from any location under GE(AF) Leh for repair/rewinding of capacity 63 to 400 KVA , 11/0.433 KV capacity disconnecting /opening HV, LV Electrical connections, earthing connections along with following other works.(a) Transporation of transformer to workshop and back to site by making necessary arrangements of T&P (crane, recovery, vehicle, tripoid to be arranged by firm) as directed.(b) Opening of transformer top cover by extraction ,removing of serviceable - unserviceable nuts bolts and washers etc in presence of Engr -in -Charge. (c) Draining out of old transformer oil.(d) Lifting primary coil (HT) and secondary coil (LT) , and display all the parts without damaging any portion for inspection of Engr -in -Charge.(e) Reassembeling the transformer complete with all existing serviceable parts, and new parts as ordered.(f) Reinstall the Transformer at site in position as directed after repair connecting HV, LV electrical connections, earthing connections and testing to entire satisfaction on load . |
| 32 | M&L for opening, checking and testing of trasformer of capacity 63/400 KVA in HT copper rewinding coil of required size with super enameled superior quality copper wire and insulation material of suitable size and specification, complete with insulation, varnishing, vaccum impregnation and baking of coil assembly etc, after rewinding including taking out carefully burnt unserviceable copper winding of coils complete all as specified and directed. |
| 33 | M&L for opening, checking and testing of trasformer of capacity 63/400KVA & voltage stablizer of capacity 10 KVA to 320 KVA in LT copper rewinding coil of required size with super enameled superior quality copper wire and insulation material of suitable size and specification, complete with insulation, varnishing, vaccum impregnation and baking of coil assembly etc, after rewinding including taking out carefully burnt unserviceable copper winding of coils complete all as specified and directed. |
| 34 | M&L for dehydration and filtration of existing transformer oil of capacity ranging from 63 KVA to 400 KVA capacity, 11 KV, on site at different locations with filtration machine and heating system in order to achieve Di-electri strength of oil 40-45 KV minimum 3.0 mm gap, if its di-electric strength below 40 KV di-electric strength, oil shall be replaced with new oil complete all as specified and as directed. (Note : (a) New oil for toping or replacement shall be measured and paid separately under appropriate item of this schedule. (b)The unit of payment under this term shall be per liter of oil meant for all process to the entire completion of jobs). |
| 35 | Supply of Transformer oil superior quality, ISI marked in 200 Liter sealed drum for filling up, topping up/replacement up to desired level of transformer oil capacity and in voltage stablizer complete all as specified and directed. (Note : Dielectric strength of oil should not be less than 50 KV complete all as specified and directed.) |
| 36 | Supply and replacing silica gel in crystal form of breather assembly of transformer capacity upto 400 KVA at installed site complete all as specified and directed. |
| 37 | Supply and fix in repair LT bushing complete with gasket, for transformers of capacity 63 KVA to 400 KVA all as specified and directed. |
| 38 | Supply and fix in repair HT bushing complete with gasket, for transformers of capacity 63 KVA to 400 KVA all as specified and directed. |
| 39 | S&F in replacement of top cork sheet / gasket as per existing size, shape and specification for capacity 63 to 400 KVA ,11/0.433 KV transformer complete all as specified and directed |
| 40 | S&F in replacement of breather assembly as per existing size, shape and specification for capacity 63 to 400 KVA , Transformer complete all as specified and directed |
| 41 | M & L for preparing old painted surfaces by scrapping and removing old paints, rust etc from steel tubular poles (above the planting depth and PCC coping of 11.0 Metre length pole ) and Mild Steel cross arms, cable protection pipe,brackets etc and applying one coat of synthetic enamel paint alternate yellow & black strips painting as per recommendation by Engr-in-Charge and remaining portion of pole and cross arms,cable protection pipe,brackets etc treated with one coats of Aluminium paint incl writing pole no with white paint on black back ground complete all as specified and as directed |
| 42 | Labour for Servicing/Repairing of Transformer 11 KV/433V of capacity 63 KVA to 400 KVA by disconnecting of LT and HT side cable carefully from Transformer and checking of 4 Nos LT bushing and 3 Nos of HT bushing including necessary tools and plant for removal of carbon deposits and attending leakage problem with oil seal and all gaskets and re assembling complete all as specified and as directed by Engr-in-charge.Note :- New Transformer oil and spare parts shall be measured and paid separately under the relevant item of schedule as supply only excluding oil seal |
| 43 | M & L for detect HT 11 KV cable fault for various size of cable with technician around the clock at Tech Area , Domestic Area , MRS at all Insp Org area and other locations under GE (AF) Leh detect the cable fault including necessary repair, joint the faulty cable with new straight through joint kit, after jointing, testing, and charging of HT cable complete all as specified and as directed by Engr-in-charge. Note:- Cable joint of required size shall be measured and paid separately under relevant item of this BOQ. |
| 44 | Material and labour for carrying out adjustment/ servicing of 11 KV indoor type VCB, by adjustment/ servicing of spring operated control mechanism assembly with checking and adjustment of stops, opening springs and shock absorber, loading of the closing spring when circuit breaker close/ open, tripping of the circuit breaker, clearance of the dragging hook and trip coil/ close coil, tightning of all connections, oiling/ greasing all moving parts with recomended lubricant for smooth functioning from local and remote panel complete all as directed . |
| 45 | M&L for earthing complete with galvanized steel earth plate electrode 600 x 600x 6 mm thick buried in ground vertically to a depth n.less than 2.25 mtr below normal ground level connected to galvanized steel strip 32 x 6 mm earth lead by means of bolts, nuts and washers made of galavanised iron or steel earth strip protected by 40 mm bore light grade GI pipe and connected for body earthing of feeder pillar box complete incl PCC work, pit cover slab of size 300x300x50 mm with handle, 20 mm dia GI pipe medium grade for watering, charcoal and slat in alternate layers incl necessary earth pole and excavation in hard/dense soil and removal etc incl testing complete including taking down old u/s earthing all as specified and directed. |
| 46 | M&L for cleaning of MES electric supply installations/campus/complaint cell area by surface dressing or trimming of natural ground to remove small inequalities (including removing vegetation/ shrubs/brush wood/under growth) and carrying away the rubbish to a distance of not exc 50 mtr away complete for the various sub stations. |
| 47 | Material and labour for 40mm coarse aggregates filling in sub stations/ Transformers & HT 2/4 pole area with proper leveling complete all as specified and directed by Engineer in charge |
| 48 | Demolition of cement concrete (unreinforced) in ground floor and paving n. exc 15 cm thickness (below or above ground level) complete all as specified and as directed. |
| 49 | M & L for providing PCC plith of 1:3:6 type C-2 (using 40mm graded stone aggregate) as in foundation and mass concrete complete all as specified and directed by Engr-In- Charge. |
| 50 | M & L Rendering cement plaster of ration 1:4, 10mm thick on fair faces of brick work or concrete surfaces complete. |
| 51 | S&F in repair for Wire netting of galvanised steel wire 1.40 mm dia fixed with tinned tacks of wire staples of size 25 mm x 25 mm complete including necessary welding work all as specified and directed |
| 52 | S&F in repair of MS joist channel, angle or Tee section MS tubes, flats square bars (Fe 410-W Gde E-250 Quality A) etc fixed indepently or framed or without connecting plates, (cut to ordinary lengths i.e. within 20mm of the length indicated) trusses or any type framing etc complete all as specified and directed. |
| 53 | Dismantling ACSR conductors from the disturbed span including line spacer etc complete all as specified and as directed |
| 54 | S & F Aiuminium conductor steel reinforced (ACSR) (sizes as ordered) with permisible sags and providing jumper etc fixing on electric poles and binding to insulators with Aluminium binding wireas (weasel) in over head conductors including stringing, tightning etc complete all as specified and as directed.Note : Cost of binding wire is deemed to be included in the quoted unite rate |
| 55 | Disconnecting the voltage stabilizer of capacity upto 10 KVA to 20 KVA, 3 Phase 415 V, from electric circuit, strip opening of the same for repair work and replacement of worn out parts including wiring & interconnections, Reassembling of the voltage stabilizer after carrying out the repair work and testing the same after repair and replacement of electronic relays, control circuit, indicator lamp , auto manual switch and other connected item complete all as specified and as directed by Engineer-in-charge.(Note: Spares required/replaced will be measured and paid separately under the respective sch of item, if required.) |
| 56 | Disconnecting the voltage stabilizer of capacity upto 50 KVA to 100 KVA, 3 Phase 415 V capacity, single phase dry type from electric circuit, strip opening of the same for repair work and replacement of worn out parts including wiring & inter connections, Reassembling of the voltage stabilizer after carrying out the repair work and testing the same after repair and replacement of electronic relays, control circuit, indicator lamp , auto manual switch and other connected item complete all as specified and as directed by Engineer-in-charge.Note:- (Spares required/replaced will be measured and paid separately under the respective sch of item, if required.) |
| 57 | Disconnecting the voltage stabilizer of capacity upto 101 KVA to 320 KVA 3 Phase 415 V capacity, single phase dry type from electric circuit, strip opening of the same for repair work and replacement of worn out parts including wiring & interconnections, Reassembling of the voltage stabilizer after carrying out the repair work and testing the same after repair and replacement of electronic relays, control circuit, indicator lamp , auto manual switch and other connected item complete all as specified and as directed by Engineer-in-charge. |
| 58 | Supply and fixing in repair auto transformer (Dimmer) of input voltage single phase 90 to 270 volts and output voltage single phase 230 volts for power 10 KVA to 50 KVA complete all as specified and directed by Engineer-in-charge. |
| 59 | Supply and fixing in repair auto transformer(Dimmer) of input voltage single phase 90 to 270 volts and output voltage single phase 230 volts suitable for power 51 to 100 KVA Voltage stabilizer complete all as specified and directed by Engineer-in-charge. |
| 60 | Supply and fixing in repair auto transformer(Dimmer) of input voltage single phase 90 to 270 volts and output voltage single phase 230 volts suitable for power 100 to 320 KVA Voltage stabilizer complete all as specified and directed by Engineer-in-charge. |
| 61 | Supply and fixing in repair servo motor of capacity 3 kg suitable upto 50 KVA 3 Phase 415 V complete all as specified and as directed by Engineer-in-charge |
| 62 | Supply and fixing in repair servo motor of capacity 5 kg suitable upto 51 KVA to 100 KVA, 3 Phase 415 V complete all as specified and as directed by Engineer-in-charge |
| 63 | Supply and fixing in repair servo motor of capacity 10 kg upto 101 KVA to 320 KVA 3 Phase 415 V capacity complete all as specified and directed by Engineer-in-charge. |
| 64 | Supply and fixing in repair control circuit for power 10 KVA to 320 KVA voltage stablizer complete including soldering the same with existing circuit complete all as specified and directed by Engineer-in-charge. |
| 65 | Supply, installation, commissioning and testing of totally enclosed outdoor type HT Busbar Panel cubical type dust and vermin proof equal angle iron mounted type (IP-65 degree of protection) made out of 3.15 mm thick CRCA sheet. The panel having both side opening door with locking arrangement (HT bus bar door lock should be easy openable, duly painted with two coats of synthetic enamel paint powder coated, mounted on iron angle frame made out of 50 X 50X 6 mm frame with 4 No's of legs size not less than 50 cms (bottom portion of the panel wrt normal ground level) fixed with nut bolts of suitable size, grouted by using foundation 1:2:4 type C1 with 20 mm graded stone aggregates complete incl taking down old unsv bus bar panel and including the following :-Busbar Details ;- Rated voltage :- 11 KV.Enclosure Details :-Installation of HT Busbar - Outdoor Type (Angle Iron Legs mounted). HT Busbar Panel Dimention (L x W x H) - 1200mm x 900mm x 750mm Busbar Details ;-Busbar Material - Copper, Busbar strips arrangemets - Vertically fixed.Buabar insulation Materail - Bare.Busbar Size :- Busbar Width - 100 mm, Busbar Thickness - 10 mm, Number of Busbar - 03Busbar Length per Phase - 500 mm, duly drilled holes for connections and mounted on epoxy resin cast HT support insulators for busbar support. |
| 66 | Note : Schedule of credit for Rs. 1,27,994.00 to be deducted on acceptance of bid. Please Enable Macros to View BoQ information |