Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Proposed Fire Fighting and Electrical Work at S.N.C.U. Building (51 Bedded) at Medical College Jhansi at District- Jhansi (U.P.) |
| 2 | FIRE FIGHTING WORK Supply & fixing of welding Heavy Quality Class 'C', MS pipe conforming to IS:1239 (part-1) for pipes up to 150 mm dia and IS: 3589-1991 for pipes above 150 mm including cutting, threading, welding, clamping fitting with elbow, socket nipple, clamping with MS angle iron supports and fasteners etc. also painting with red oxide and PO red enamel paint complete in all respects. 150 mm |
| 3 | 100 mm |
| 4 | Supply & fixing of welding Heavy Quality Class 'C', MS pipe conforming to IS:1239 (part-1) for pipes up to 150 mm dia and IS: 3589-1991 for pipes above 150 mm including cutting, threading, welding, clamping fitting with elbow, socket nipple, clamping with MS angle iron supports and fasteners etc. also painting with red oxide and PO red enamel paint complete in all respects. [ FOR SPRINKLER] 80 mm |
| 5 | 65 mm |
| 6 | 50 mm |
| 7 | 32 mm |
| 8 | 25 mm |
| 9 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories. Pendent Sprinkler/Sprinkler |
| 10 | Supplying Installation testing & Commissioing of Butterfly Value PN-16 slim seal standard lever operated type as per design standard IS:1395 or BS:5155 with required flanges, nut, bolts etc. Complete in all respects. 150 mm |
| 11 | 100 mm |
| 12 | 80 mm |
| 13 | Supplying Installation Commissioning of dual plate Non Return Value of following sizes PN-10 as per design standard IS:5312 or BS:1868 with companion flanges, nut, bolts etc. Complete in all respect. 150 mm |
| 14 | 100 mm |
| 15 | Supplying Installation testing & Commissioning of Manual Swing type Fire Hose Reel IS:444 complete with heavy duty reel, 19 mm dia 30 Mtr. Long. 2 ply polyster yarn braided rubber pressure hose, Red colored, SS jet nozzle 25 mm isolating value and all other necessary fixing accessories complete in all respect. |
| 16 | Supplying Installation testing & Commissioning of 25 mm Air Release valve gunmental having rubber ball and with 25 mm BSP threaded male inlet including necessary accessories and connections complete in all respect. |
| 17 | Supplying Installation Commissioning of 25 mm Ball valve PN-1 gunmental as per IS:778 including necessary accessories and connections. |
| 18 | Providing / Fixing of Fire Hose cabinet box made out of 18 gauge MS sheet including two coats of post office red paint over one coat of primer with 4 mm, thick glass door in front painted \\"FIRE\\" in red luminous paint. The size of the box should be 750 mm X 600 mm X 250 mm size capable of accommodating a pair of hose with coupling and nozzle. The box should be floor mounted type with railway coach lock arrangement and lever for opening the door after breaking the glass complete. |
| 19 | Supplying fixing of Fire hose, RRL hose jacketed with circular woven synthetic fibre conforming to IS:636.88 63 mm dia X15 Mtr. Long with S.S. heavy duty, 63 mm, Painr of male and female instantaneous couling having IS: 903 mark and duly S.S. wire wounded. |
| 20 | Supplying fixing of S.S. Branch pipe, short type with 63 mm male instantaneous intel, male threaded outlet, fitted with 15 mm bore nozzle having IS:903 mark. |
| 21 | Providing / Fixing of Fire Fighting Terrace pump set suitable for automatic operation consisting of the following as per the specification. a) Horizontally mounted, centrifugal type single stage fire pump having cast iron body, bronze impeller, stainless steel shaft and capable of delivering 450 LPM, 7.5 H.P against a total head of 52 mtrs. Complete with pressure gauge & gun metal cocks on delivery side including bypass arrangement. |
| 22 | Supplying Installation testing & Commissioning of vertical air vessel fabricated from 6 mm thick MS plate with dished ends 250 mm dia DN 1.2 m high common for fire and jockey pump complete with spring loaded safety valve. Test pressure 12 kv/Sq.mm) |
| 23 | Supplying Installation Commissioning of pressure Gauge ranging from 0 to 14 kg. per sq.mm ISI marked from approved manufactures complete in all respect. |
| 24 | Supplying fixing of Cast iron body 63 mm dia male instantaneous intel coupling with housing cabinet (500X400X400 for 2 way and 600X400 for 4 way) cap and chain for fire brigade correction conforming to IS:904 and making connection with fire fighting pipe or underground water tank completing the work in all respect as per the directions of the Engineer-in-charge. (FIRE BRIGADE CONNECTION) Four way connection (4 way) |
| 25 | Providing/Fixing of cubical type floor mounted Fire pump control panel fabricated from 16 G M.S. sheet duly powder coated finish of approved shade and comprising of: a) One 63 amp. TP-NL M.C.C.B. with rotary handle of beacking capacity 35 KV. b) One Volt meter (0-500 V) with selector swich. c) One set including lamps. |
| 26 | Supplying and laying of Insulated PVC sheathed, Steel Aromed, Copper Aluminium Conductor, 1100V grade Powder Cable. The cable shall be laid in tray / in trenches/on wall/ floor etc. As required (Approx quantities only) 2 crore x 1.5 sq.mm Cu Cable |
| 27 | 3.5 crore X 25 sq.mm AL Cable |
| 28 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. 150 sq. mm 3-1/2 core |
| 29 | 50 sq. mm 3-1/2 core |
| 30 | 35 sq. mm 3-1/2 core |
| 31 | 10 sq. mm 4 core |
| 32 | Supplying and fixing of Self Glow Exit signage for stairs and exists size 100 x 300 |
| 33 | Fire man axe |
| 34 | Pressure Switch |
| 35 | Supply & fixing of Single way landing/Hydrant / Yard Hydrant valve 63 mm dia.gun metal instantanuous with female coupling with chain etc. complete. |
| 36 | Surface dressing of road with Painting between using 2.25 kg. of bitumen per sq.mt with 1.65 cum of stone chipping, 13.2 mm nominal size/100 sq.mt of road surface including corolidation. (Although this job the fore will be given to civil contractor/Required Tank and pump house as per direction fo Fire Department. |
| 37 | Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325 M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required Suitable cement concrete foundation duly plastered with anti vibration pads. 2280 lpm at 70 m Head |
| 38 | Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump) Horizontal type, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520 Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required Suitable cement concrete foundation duly plastered and with anti vibration pads. 2280 lpm at 70 m Head. |
| 39 | Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325. M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. 180 lpm at 70 m Head. |
| 40 | Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter-connection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection classIP 42 as required :INCOMING400A, 50kA 4 Pole MCCB, Ics=100% lcu rating Digital Voltmeter 0-500V with selector switch Ammeter (0-400 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 500AmpsOUTGOING( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) JOCKEY PUMP63 A, 50kA TPN MCCB, Ics=100% lcu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. DIESEL ENGINE CONTROLControl for diesel engine comprising -Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engineSYSTEM CONTROLLERDesigning, Supply, Installation, esting and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification |
| 41 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fitting and base support for tank. |
| 42 | SITC Automatic priming arrangement for all fire pumps including necessary pipe, fitting, water level controller, 1 HP pump, auto starter gate valve NRV's etc complete. |
| 43 | Cost of minor repair / repainting or necessary works after installation of fire figting works. Making Holes with core cutting as per specified dia & depth including stacking of dismantled materials as directed by Engineer-in-charge with in a distance of 60 meters. 25 mm dia (9\\") |
| 44 | 32 mm dia (9\\") |
| 45 | 50 mm dia (9\\") |
| 46 | 80 mm dia (9\\") |
| 47 | 100 mm dia (9\\") |
| 48 | 150 mm dia (9\\") |
| 49 | Grounting of holes with plaster & painting with matching color as per specified dia & depth including cost of materials complete in all respects as directed by Engineer-in-charge. 25 mm dia |
| 50 | 32 mm dia |
| 51 | 50 mm dia |
| 52 | 80 mm dia |
| 53 | 100 mm dia |
| 54 | 150 mm dia |
| 55 | Drilling & Grounting of holes with DE-Walt Pure 150- Pro Chemical as per specified dia & depth including cost of materials complete in all respects as directed by Engineer-in-charge. 16 mm dia (9\\") |
| 56 | FIRE ALARM SYSTEM Supplying Installation Commissioning Intelligent Addressable 2 loop fire alarm control panel is able to connect 250 devices (Detector or Module) per loop in any combination with 20% spare address for detector in each loop should have min. 854 char LCD multi-line QVGA LCD display complete with inbuilt additional seven customized pregrammable function switch for direct activation of any device or control along with three programmable LED's indication along with 9A power supply inbuilt min three Notification appliance circuit with sufficient power supply to drive sounder cum strobe unit along with inbuilt 50 AH UL listed battery charger along with required SMF batteries for 24 hours in normal condition. |
| 57 | Supplying Installation testing & Commissioning Intelligent Addressable photoele smoke detector with base as per specification with true alarm photo sensing technology selectable sensitivity from 0.2% to 3.7% / Ft, obscuration support digital communication and magnetically operated functional test. |
| 58 | Supplying Installation testing & Commissioning Intelligent Addressable type heat Dectector along with base as per specification rate of rise temperature range is at 8.3 dgree c/ 11.1 dgree c per min and fixed temperature sensing is independent of rate of rise sensing to operate at 57.2 dgree c/68 dgree c support digital communication and magnetically operated functional test. |
| 59 | Supplying, installation, testing & commissioning response indicator on surface/recess MS box having two LEDs metallic cover complete with all connections etc, as required. |
| 60 | Supplying Installation testing & Commissioning of Intelligent Addressable Manual Call points-double action Break Glass cum pull station suitable for wall/column mounting. |
| 61 | Supplying Installation testing & Commissioning of Intelligent Addressable Hooter cum multi carriar strobe, Unit as per specifications and customization of intensity selection as 15, 30, 75 or 110 cd of strobe unit is possible by panel. Sounder sum strobe will be driven by supervised 24 V DC input and will give 70 db output at 3 m strobe unite will be synchronized 1 Hz strobe flash rate for better evacuation in complete facility. |
| 62 | Supplying Installation testing & Commissioning Intelligent Addressable single Addressable Control Relay Module-Form \\"C\\" contact type. |
| 63 | Supply laying testing & Commissioning of 2 corex 1.5 sr.mm single standard copper conductor, PVX insulated armoured cable. |
| 64 | Class A Fire Form extinguisher |
| 65 | Class B Fire Form extinguisher |
| 66 | Supply and burying of 600mm x 600 mmx6mm G.I. plate, vertically for earthing with its top atleast 3 mts. below ground level complete with 20mm G.I.pipe and funnel for watering and two earthing leads of No.8to10SWG G.I.wire in 15mm diaG.I. pipe upto switch board (from apron to switch board the cost of G.I. pipe and G.I. wire will be extra) 30cm. square C.I. frame with hinged cover, masonary housing, alternate layers/of charcoal/ coke and salt at least 150mm thick alround etc. complete in all respects. |
| 67 | Supplying & Laying of 25mmx5mm G.I. Strip on surface for earthing purpose as required complete in all respects. |
| 68 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 69 | INTERNAL ELECTRICAL WORK Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.Group C |
| 70 | Wiring for group controlled (looped) light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed midium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C |
| 71 | Supply & wiring of submains with 2 nos. 2.5 sq.mm & with 1 no. earth wire of 1.5 sq.mm FR PVC insulated 1100 V grade single core multistrand copper conductor cable in PVC conduit pipe partly concealed including supply of all material, labourand T&P etc. required for proper completion of the work as directed by Engineer I/C. |
| 72 | Supply and wiring of submain with two number 4 sqmm . FR PVC insulated 1100 V grade multistranded single core copper conductor cable in 20mm dia heavy duty (2mm thick ) PVC conduit partly concealed in wall and partly laid in slab along with reinforcement befor concreting with one number 2.5 Sqmm FR PVC Multistand copper earth contunity wire including colour wash etc. complete in all respects. |
| 73 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 74 | Supply and wiring of submain with 4 number 10 sqmm . FR PVC insulated 1100 V grade multistranded single core copper conductor cable in 32 mm dia heavy duty (2mm thick ) PVC conduit partly concealed in wall and partly laid in slab along with reinforcement befor concreting with two number 10 SWG copper earth contunity wire including colour wash etc. complete in all respects. |
| 75 | Wiring for circuit / submain wiring alongwith earth wire with the following sizes for FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class pvc conduit as required. 2X1.5 sq. mm+1X1.5 sq. mm earth wire |
| 76 | 2X2.5 sq. mm+1X1.5 sq. mm earth wire |
| 77 | 2X10 sq. mm+1X6 sq. mm earth wire |
| 78 | 4X10 sq. mm+2X6 sq. mm earth wire |
| 79 | S/F of hexagonal fan box with hexagonal side of approx 80mm in length fabricated from 16SWG MS. Sheet incorporating 10mm dia, M.S. round bar duly bent for supporting fan hanger dully painted with red oxide and screwing arrangement with wiring conduit laid in the R.C.C roof before concreting along with supply of all materials,labour. T& Petc. required for proper completion of the work. |
| 80 | Supplying and fixing Two Module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 81 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes |
| 82 | Supply & fixing of single wall bracket on matching M.D.F.E.G. board base etc. complete in all required. Cat. AAA |
| 83 | Supplying and fixing brass batten/angle holder including connection etc. as required. |
| 84 | Supply and fixing of recess mounting square 45 Watt LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set complete in all respect |
| 85 | Supply and fixing of recess mounting round 10 Watt LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set complete in all respect |
| 86 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/MIW) minimum 6.00, Air delivery minimum 210 Cum/Min, 350 RPM (tolerance as per IS : 374-2019), THO less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required |
| 87 | Supply & erection of A.C 230/250 Volts,50 Hz exhaust fans including providing m.S bolts,mounting frame and other acessories including connections etc.complete as required 300mm sweep as per directionof E/I Makebajaj,Cromption or Equivalent. |
| 88 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 89 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 90 | Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. For 4 way, Double door TPN MCBDB |
| 91 | For 6 way, Double door TPN MCBDB |
| 92 | Supply and fixing of power plug with 15 Amp./250 Volt flush type universal switch and 5 pin 15 A/250 V flush type universal socket switch on concealed M.S. box including supply of all material, labour T&P etc. required for proper completion of work. |
| 93 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 94 | Supply and burying of 600mm x 600 mmx6mm G.I. plate, vertically for earthing with its top atleast 3 mts. below ground level complete with 20mm G.I.pipe and funnel for watering and two earthing leads of No.8to10SWG G.I.wire in 15mm diaG.I. pipe upto switch board (from apron to switch board the cost of G.I. pipe and G.I. wire will be extra) 30cm. square C.I. frame with hinged cover, masonary housing, alternate layers/of charcoal/ coke and salt at least 150mm thick alround etc. complete in all respects. |
| 95 | Supplying & Laying of 25mmx5mm G.I. Strip on surface for earthing purpose as required complete in all respects. |
| 96 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 97 | Supply, installation, testing and commissioning of electrical pane, modular type, front accessible only, free floor standing confirming to Minimum IP:43 degree of protection. The panel sheet structure shall undergo seven tank pre-treatment process before painting. The sheet steel shall be all of 2.2mm thick CRCA sheet. All the openable compartments of the panel shall be completely shrouded and provided with padlocking arrangement on all compartments including bus bar and cable alley chambers. The panel height shall not exceed 2200mm and the maximum operating height for any switchgear shall not be more than 1700mm. The panel shall be provided with minimum 75mm base channel frame fabricated from ISMC sections. All bus bar links in the panel shall be solid bus bars with coloured PVC shrinkable sleeves, no wires will be acceptable. Continuous earth bus shall run alround the panel with earthing studs provided at minimum 2 places. The control wiring shall be carried out with minimum 1.5/2.5 sqmm copper wires and adequate number of NO/NC, potential free contacts incorporated for remote operation of the starters. Proper sized cable termination gland plates shall be provided on cable alleys and knockouts for same shall be provided during fabrication stage itself. The panel shall be provided with a thermostatically controlled heating arrangement (200 W) to take care of high humidity conditions. A 5A socket service outlet (single phase) shall be provided in one of the compartments as ervice outlet in the panel. Panel shall be so designed at to have minimum 20% spare feeders/space. Panel shall undergo epoxy powder coated paint, colour as per IS:5 requirement. All cable terminations shall be from top. The complete panel shall be fuse less type, for control circuits 2A/6A MCB's to be used. All bus bars shall be of aluminium, electrolytic grade only. Maximum design density shall not exceed 1 Amps/Sqmm. All bus bars shall be insulated with coloured heat shrinkable PVC sleeved. All bus bar supports shall be non hygroscopic DMC/SMC supports. The panel shall be manufactured in conformance to requirements of local electrical inspector and it shall be contractors responsibility to get initial approval of drawings and also final approval of complete electrical works related to this section. |
| 98 | Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 99 | Supply and laying of aluminium conducter PVC insulated armoured served sheathed cables 1100 volts grate at a depth of below ground lvl over a cusion of 75 mm thick sand alround and protected with burnt on side and on top ,On surface the cable run shall be fixed on M.S clamps etc. of suitable size or as directed by E/I complete in all respects,The armouring of the cable shall be properly connected with the earth conductor by clamps atc. (i) 10 Sq. mm 2core |
| 100 | (ii) 35 Sq. mm 3.5 core |
| 101 | (ii) 400 Sq. mm 3.5 core |
| 102 | Supplying Installation of Wall Fan |
| 103 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 Way , Double Door |
| 104 | 12 Way , Double Door |
| 105 | Invertor Wiring in wiring Point for light/ Fan/ Plug with 1.5 mm Cu Wire |
| 106 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For Computer Power). |
| 107 | Supplying and installing ,testing & commissioning 400 Amp 4 Pole ATS - (Automatic Transfer switch) |
| 108 | SUPPLY & FIXING OF D.G. SET |
| 109 | SUPPLY & FIXING OF UPS SYSTEM |
| 110 | SUPPLY & FIXING OF THREE PHASE 200 KVA SERVO VOLTAGE STABILIZE |
| 111 | SUPPLY & FIXING OF SMOKE EXHAUST SYSTEM |
| 112 | PUMP HOUSE Excavation in foundation in ordinary soil (loam clay or sand) including lift upto 1.50 meter and lead upto 30 meter and including filling, watering and ramming of excavated earth into the trenches or into the space between the building and sides of foundation trenches or into the plinth and removal and disposal of sur-plus earth as directed by the Engineer incharge up to a distance of 30 meters from the foundation trenches. |
| 113 | Providing and laying in cement concrete 1:4:8 (1 cement : 4 coarse sand :8 graded Stone aggregate 40 mm nominal size) and curing complete,including cost of form- work, in foundation and floors. |
| 114 | Local Sand filling in plinth including supply of necessary quantity of sand from a distance not exceeding 8 km. from the site of work & including watering, dressing etc. Rate include cost of all materials, labour and T&P etc. required for proper completion of the work. |
| 115 | Providing and injecting chemical emulsion for pre constructional antitermite treatment and creating a chemical barrier under and alround the column pits wall trenches basement excavation top surface if plinth filling junction of wall and floor, along the the external perimeter of binding expansion joints, surrounding of pipes and conduits etc, complete. (plinth area of the building at ground floor only shall be measured as per I.S.6313 (PartII 1981) Alderine emulsifiable concentrate or any other approved material such as Heptrachlor or Chlordane will be used. The rate of application of chemical emulsion shall be as follows : (1) Treatment for masonary & foundation 5 liters per sqm. (2) Back fill in immediate contact with foundation 7.5 liters/sqm (3) Treatment of top surface of plinth filling 5 liters/sqm (4) Treatment junction of wall and the floor 7.5 liters /sqm (5) Treatment of soil along external perimeter of building 7.5 liters/sqm (6) Treatment of soil under apron along external perimter 5 liters/sqm. (As per manufacturer's standard dilution) |
| 116 | R.C.C. work with cement approved coarse sand and 20 mm. guage approved stone grit im the proportion of 1:1.5:3 in lintels of doors and windows excluding supply of reinforcement and its fixing and binding the same with 24 BWG binding wire and including necessary centering and shuttering etc.and also including supply of all materials, labour and tools and plants etc, required for proper completion of the works. strength of the concrete shall not beless than M-20. |
| 117 | Same as Item No. 4 but R.C.C. work in slab (M-20). |
| 118 | Same as Item No. 4 but R.C.C. work in beam (M-20). |
| 119 | Same as Item No. 4 but R.C.C. work in foundation (M-20). |
| 120 | Same as Item No. 4 but R.C.C. work in column (M-20). |
| 121 | Class M-150 brick work in 1:6 cement coarse sand (of 2.25 fineness modulus) mortar in foundation & plinth including supply of all materials, labour, tools and plants etc. required for proper completion of the work. |
| 122 | M-150 Brick work in super-structure (1:6 cement coarse sand above plinth level up to floor two level (up to two storeys) including necessary cutting and moulding of brick work as required and also including honeycombed brick work in thickness of wall more than 12cms. |
| 123 | Same as in item above but in 1:3 cement and coarse sand mortar in superstructure for wall thickness 12 cms & below brick work M-150. |
| 124 | Applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7 kg per square metre on damp proof course after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil. |
| 125 | Providing and laying \\"brick coba\\" 12mm thick laid with M-150 class brick bat coba 7.50cm thick with gap of 15mm to each other, over 20 mm thick base of cement mortar 1:4 cement and coarse sand mixed with water proofing compound spreading cement slurry mixed with acrelic cement concrete water proofing compound filled gaps of coba & top of coba mortar mixed with water proofing compound in 1:4 cement and coarse sand mortar finised smooth & top mashed false square 30 cm x 30 cm and side wall parapet shall be mono tythic plaster wall up to 30 cm higher and junction and corner shall be rounded by brick ballast cement and coarse sand masonany Coba with top finised plaster mixed with acetic water proofing compound @ 2% by weight & including s/o all material, labour, T& P etc complete for proper completion of work. |
| 126 | Mild steel or iron work of small sizes and sections such as holding down bolts, hold fast tierods,gratings etc. ( when not included in an over all rates) wrought to required from including supply of steel and its wastage including cost of bolts, nuts if required for and welding, grinding and making holes as required completion of work fabrication of holes doors, chaukhats nosing. Providing & fixing of hold fast for chaukhats of doors and windows. |
| 127 | Providing & fixing of door / windows grill. |
| 128 | Z-Section steel windows |
| 129 | ISMB 200 Section |
| 130 | P/F FE-500 STEEL work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 131 | Fixing of Door, windows / ventilators chaukhats in position.Window chaukhats |
| 132 | 15 mm cement plaster on rough side of single or half brick wall of mix: 1:4 (1 cement: 4 coarse sand) |
| 133 | 12 mm cement plaster in single coat on fair side of single or half brick wall for interior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 6 course sand of 2.25 F.M. |
| 134 | 12 mm cement plaster in single coat on rough side of single or half brick wall for exterior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 6 course sand |
| 135 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand :4 graded stone aggregate 12-20mm nominal size laid in one layer neat cement (40 mm thick floor). |
| 136 | 18mm thick cement plaster in dado or skirting in 1:2 consisting of one part of cement and 2 parts of approved coarse sand laid in panels, finished with 3mm floating coat of neat cement or cement and marble dust in ratio of 5:1 including supply of all materials, labour and T & P etc required for proper completion of the work. |
| 137 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors 40 mm wide and 4 mm thick. |
| 138 | Painting or varnishing work in small areas or new wood work with one coat upto one square metre of ready mixed priming paint and one coat of approed superior quality ready mixed paint or varnish including supply of all materials, labour, Tools & plants etc. required for proper completion of the work. Paint to be used should fonfirm the ISI no. 103-1950 (M.S. works) |
| 139 | Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of required shade and colour all complete to achieve even shade and colour : New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC content less than 50 gram/litre. |
| 140 | Finishing wall with water proof cement paint of approved make and quality on new wood with two coat to give an even shade including supply of all materials, labour, tools and plant etc. required for proper completion of the work. (Three Coat) |
| 141 | Providing & fixing glass panes with putty and glazing clips in steel doors, windows, clerestory windows, all complete with : 4.0 mm thick glass panes |
| 142 | Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 -part 1 and M.S. top cover of required thickness for rolling shutters. 80x1.25 mm M.S. laths with 1.25 mm thick top cover |
| 143 | Providing and fixing ball bearing for rolling shutters. |
| 144 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : Slab & chhajja |
| 145 | Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 146 | Foundations, footings, bases of columns, etc. for mass concrete. |
| 147 | Columns,Pillars, Piers, Abutments, Posts and Struts. |
| 148 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 149 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 150 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 151 | Supply and Fixing of LED Tube Light with batten suitable for up to 1X22 watt LED tube light fitting complete including tube on surface complete in all respect. |
| 152 | S/F of hexagonal fan box with hexagonal side of approx 80mm in length fabricated from 16SWGM.S. sheet incorporating 10mm dia, M.S. round barduly bent for supporting fan hanger dully painted withred oxide and screwing arrangement with wiring conduit laid in the R.C.C. roof before concreting along with supply of all materials, labour T & P etc., for proper completion of work. |
| 153 | 100 K.L. CAPACITY U.G. TANK Excavation of foundation in ordinary soil (loam clay or sand) including lift upto 1.50 meter and lead upto 30 meter and including filling, watering and ramming of excavated earth into the trenches or into the space between the building and sides of foundation trenches or into the plinth and removal and disposal of sur-plus earth as directed by the Engineer incharge up to a distance of 30 meters from the foundation trenches. From Lvl. 0.00 Mt. to 1.50 mt |
| 154 | Providing and laying in cement concrete 1:4:8 (1 cement :4 coarse sand :8 graded Stone aggregate 40 mm nominal size) and curing complete,including cost of form- work, in foundation and floors. |
| 155 | R.C.C. work with cement approved coarse sand and 20 mm. guage approved stone grit in Slabs excluding supply of reinforcement and its fixing and binding the same with 24 BWG binding wire and including necessary centering and shuttering etc.and also including supply of all materials, labour and tools and plants etc, required for proper completion of the works. strength of the concrete shall not beless than M-25. |
| 156 | As in item above but in R.C.C. Raft foundation and footing with approved stone ballast. M-25 |
| 157 | As in item above but in Column with approved stone ballast. M-25 |
| 158 | P/F FE-500 STEEL work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 159 | 12 mm cement plaster in single coat on rough side of single or half brick wall for interior plastering up to floor two level including internal rounded angles not exceeding 80 mm in girth and finshed even and smooth. (1) 1 cement : 4 Coarse sand |
| 160 | Cement concrete flooring 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 12-20mm nominal size laid in one layer neat cement (40 mm thick floor). |
| 161 | Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : (a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. This layer will be allowed to air cure for 4 hours. (b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry. |
| 162 | Providing M.S. foot rest including fixing with 20x20x10 cm. cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 gradded aggregate of nominal size 20mm ) as per standard design with 20x20mm sq bars. |
| 163 | 560 mm diameter C.I. cover (heavy duty) the weight of the cover to be not less than 108 kg |
| 164 | Foundations, footings, bases of columns, etc. for mass concrete. |
| 165 | Columns,Pillars, Piers, Abutments, Posts and Struts. |
| 166 | Suspended floors, roofs, landings, balconies and access platform. |
| 167 | TUBEWELL Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer -in-charge, upto 90 metre depth below ground level. All Types of Soil 350 mm dia |
| 168 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer -in-charge, beyond 90 metre & upto 150 metre depth below ground level. Rocky strata including Boulders 350 mm dia |
| 169 | Supplying, assembling, lowering and fixing in vertical position in bore well, ERW (Electric Resistance Welded) FE 410 mild steel screwed and socketed/plain ended casing pipes of required dia, conforming to IS: 4270, of reputed & approved make, including painted with outside surface with two coats of anticorrosive paint of approved brand and manufacture, including required hire & labour charges, fittings & accessories, all complete, for all depths, as per direction of Engineer-in-charge. 150 mm nominal size dia having minimum wall thickness 5.00 mm |
| 170 | Supplying, assembling, lowering and fixing in vertical position in bore well, ERW (Electric Resistance Welded) FE 410 plain slotted (having slot of size 1.6/3.2 mm) mild steel threaded and socketed/ plain bevel ended pipe (type A) of required dia, conforming to IS: 8110, of reputed and approved make, having wall thickness not less than 5.40 mm, including painted with outside surface with two coats of anticorrosive bitumestic paint of approved brand and manufacture, including hire & labour charges, fittings & accessories, all complete, for all depths, as per direction of Engineer -in-charge. 200 mm nominal size dia |
| 171 | Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. Around Pipe (3.14*0.15*0.15*120.00) |
| 172 | Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge. (3.14*3.50*3.50*0.30) |
| 173 | Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by \\"V\\" notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tube well, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge. |
| 174 | Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for bore well of: 150 mm dia |
| 175 | Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tube well as per IS: 2800 (part I), including necessary bolts & nuts of required size complete. 150 mm dia |
| 176 | Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tube well as per IS:2800 (part I). 150 mm dia |
| 177 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. 80 mm dia nominal bore |
| 178 | Supply and fixing of finolex of copper cable ISI marked submersible cable of size 1 x 3 x 4 sq mm |
| 179 | Supply of Submersible pump with control panel, support wire etc. complete 7.5 HP (KSB / EQ.) |
| 180 | ARRANGEMENT OF SIGNAGE IN HOSPITAL FOR SAFE EXIT Providing & erecting direction & place identification & other fire related informations for emergency retro- reflectorised sign as per IRC-67 made of high intensity grade sheeting. The retro reflective sheeting type-IV shall be tested for 3 year outdoor weathering test in Indian conditions as per IRC 67:2012 & proof of the same in form of government report shall be uploaded while quoting tender vide clause 801.3 fixed over aluminium sheeting, 2mm thick with area exceeding 0.9 sqm. Supproted on a mild steel single angle iron post 75x75x6 mm, 2 nos firmly fixed to the ground by means of property designed foundation with M-15 grade cement concrete 45x45x60 cm below ground level as per approved drawing complete. |
| 181 | GST Extra as per applicable Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail