| 1 | BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: COMMANDER WORKS ENGINEER, UDHAMPUR Name of Work: COMPREHENSIVE MAINT OF OVERHEAD HT POWER TRANSMISSION SYSTEM AT CHETTRI, MAP ACCN, GOLF ENCLAVE AND OTHER LOCATIONS UNDER GE (UTILITIES) UDHAMPUR Contract No: CWE/U(U)- 22/2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Excavation in trenches in soft/loose soil not exceeding 1.5 mtr wide and exceeding 1.5 mtr depth and getting out complete all as specified and as directed by Engineer-in-Charge. |
| 3 | All as per item no 1 here-in-before but exc. 1.5 mtr depth and not exc. 3 mtr deep, complete all as specified and directed. |
| 4 | Returning, filling in, including spreading, leveling, watering and well ramming in layer not exceeding 25cm thick each complete all as specified and directed by Engineer-in-Charge |
| 5 | Removing excavated soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.50 meter above the starting point complete all as specified and directed by Engineer-in-Charge |
| 6 | M & L PCC 1:4:8 type D2 using 40 mm graded stone aggregate as in foundation, filling of mass concrete complete all as specified and as directed |
| 7 | M & L PCC 1:3:6 type C2 using 40 mm graded stone aggregate as in foundation, filling of mass concrete complete all as specified and as directed |
| 8 | M & L for PCC 1:2:4, type B-1, (using 20mm graded stone aggregate) as in coping including necessary use & waste of form work complete all as specified and directed. |
| 9 | Supply and laying 100 mm bore galvanised iron tubing, light grade with all fittings for passing of cables under ground complete all as specified and as directed. |
| 10 | Supply and laying 80 mm bore galvanised iron tubing, light grade with all fittings for passing of cables under ground complete all as specified and as directed. |
| 11 | Dismantling of old UNSVdamage/rusted PCC pole/steel tubular poles of any Size necessary disconnecting cables/over head condcutor and removing unserviceable pole from Site complete all as specified and directed. |
| 12 | Supply and erection of steel tubular swaged pole 12.00 metres long designation 410-SP-64 complete with cast iron base plate, finial taper plug, bolts, nuts and screws etc. complete all as specified and directed. [Note :- Earth work and concrete foundation shall be measured and paid seperately under relevant items of Sch 'A'). |
| 13 | Refixing of serviceable steel tubular pole of any type size and height obtained from item above at the location as directed by Engr-in-Charge. [Note :- Earth work and concrete foundation shall be measured and paid seperately under relevant items of Sch ' |
| 14 | Dismantling of cross-arms of MS channels or angle section etc and setting aside serviceable materials for reuse and removing unserviceable materials from site of work complete all as directed by Engineer-in-Charge. |
| 15 | M & L for Cross arm bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of two coats of aluminium paint over a coat of zinc chrome primer complete all as specified. |
| 16 | M&L for cutting/boring the existing bitumenous road/payment/footpath upto 0.75 mtr in depth, 0.45 mtr in width and getting out excavated material and making good the damaged portion after laying the pipe, returning filling in mass concrete PCC 1:2:4 type B2 upto 10 cm below the top of the road and WBM and black top carpeting with bitumen & aggregate, complete all as specified and directed by Engr-in-Charge.Note :-(i) M&L for laying of pipe shall be measured and paid separately. |
| 17 | Taking down U/S cable of size 95 sqmm 3 core to 185 Sqmm 3 core of any type and size from trench, duct, wall, road and panel complete with necessary disconnection of electrical line and making good the disturbed surface. |
| 18 | Supply, laying, jointing and testing in replacement of HT XLPE insulated ,screened,PVC bedded galvanised steel strip or wire armoured ,electric power cables(heavy duty) with aluminium conductor,11000 volts (earthed) , grade cross sectional area 95 sqmm 3 core for working voltage upto 11000 Volts, including cable lugs for providing connections as in repair complete all as specified and as directed. |
| 19 | Supplying, laying, testing and connecting in replacement of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable of size 120 sqmm 3 core (heavy duty) with multistranded aluminum conductors, 11 KV grade,IS 7098 (Part-2) 2011 marked, suitable for HT 11 KV(E) system, laid in trenches / ducts / encased in GI, HDPE pipe / fixed to pole etc or against re-routing / diversion from residential buildings/ road/ footpath etc, including jointing & testing complete all as specified and directed by Engr In Charge. |
| 20 | Supplying, laying, testing and connecting in replacement of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable of size 150 sqmm 3 core (heavy duty) with multistranded aluminum conductors, 11 KV grade,IS 7098 (Part-2) 2011 marked, suitable for HT 11 KV(E) system, laid in trenches / ducts / encased in GI, HDPE pipe / fixed to pole etc or against re-routing / diversion from residential buildings/ road/ footpath etc, including jointing & testing complete all as specified and directed by Engr In Charge. |
| 21 | S & F HT 11000 volts Danger notice plate of size 25cm x 20cm made of 1.6mm thick mild steel plate, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size complete all as specified and directed. |
| 22 | Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm. complete all as specified and directed. |
| 23 | Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm. complete all as specified and directed. |
| 24 | Cable jointing kit for 11 KV (Earthed) grade cable for end termination heat shrink type joint outdoor type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm, complete all as specified and directed. |
| 25 | Cable jointing kit for 11 KV (Earthed) grade cable for end termination heat shrink type joint outdoor type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm, complete all as specified and directed. |
| 26 | Cable jointing kit for 11 KV (Earthed) grade cable for end termination heat shrink type joint indoor type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm, complete all as specified and directed. |
| 27 | Cable jointing kit for 11 KV (Earthed) grade cable for end termination heat shrink type joint indoor type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm, complete all as specified and directed. |
| 28 | Dismantling of overhead ACSR (Aluminium conductor steel reinforced) from existing electric pole and removing unserviceable ACSR from Site complete all as directed. |
| 29 | Supplying and fixing, Stretching, Securing, Connecting & testing of Aluminium Conductor Steel Reinforced (ACSR) of size Zebra/ Dog/Goat/ Panther/Wolf/mink for 11 KV to 33 KV over head lines complete including taking out old unserviceable conductor complete all as directed and specified by Engr In Charge. |
| 30 | Dismantling of existing GI earth/guard wire of any Size and removing unserviceable GI wire from Site complete all as specified and as directed. |
| 31 | Suplying and fixing as in replacement GI Stranded continous earth wire/ surge wire of 7/2.24 mm on 11 KV to 33 KV line at road crossing including of special Tools and plant , manpower required at site complete all as directed by Engr-in -charge.Note : -(i) Length of span is approx 60 to RM.(ii) Due care is to be given while replacement of earth wire that there should no damage to over head line conductor/pole. In case due to any negligence, damage is caused to be make good/renewal by the contractor from his own resources and nothing extra is admissible.(iii) All Safety to labourer must be adhered by the contractor during execution of work. |
| 32 | Dismantling of insulator of any type and Size from existing poles after opening nuts, bolts and removing from Site all as directed. |
| 33 | M & L for MS plate /sheet plain or chequered, 3.00 mm thick to 10 mm thick cut to pieces as required and fixed to MS frame work by means of Electric arc/gas welding all as directed and specified. |
| 34 | Material and Labour for synthetic insulation mat confirming to IS 15652/2006, 2.5 mm thick of size 2x1m suitable for 11 KV substation all as specified and as directed. |
| 35 | S&F double walled corrugated (DWC) pipe of size 120 mm including snap fit coupler conforming to IS14930 (Pt-II)/IS16205 Pt-II for protection of LT cable in under ground complete all as specified and directed. |
| 36 | Meterial and labour for emergency maintenance work of 11 KV to 33 KV overhead line during breakdown by deploying skilled labour and electricians at faulty site having Gang of minimum 6 persons and tansportation including hydraulic machine and other tools and plant reqired a site for fault rectification.Note:- Contrator of his rep shall come to the site of breakdown within one hour of notification of breakdown. In case the rep or contractor shall not come to the site of breakdown and start attending breakdown within 1.00 hour a penalty of Rs 1000 per fault per hour will be imposed over contactor and will be deduct from his dues. |
| 37 | All as per Item No.35 here-in before above but Gang of minimum 3 persons except hydraulic machine. |
| 38 | Supply and fixing in replacement, Disc insulators with hardware fittings, 33 KV Grade complete all as specified and directed. |
| 39 | Supply and fixing in replacement of pin insulator with hardware fittings 33 KV grade complete all as specified and directed. |
| 40 | Supply and fixing in replacement of damage triple tension disc insulators not less than 160 KN and hardware fitting and fixing in position including tighetning of bolts & nuts, complete after dismentling and lowering of damage conductor/disc insulator by taking tension of conductor on a separate arragement including opening & provinding of jumpers of 33 KV tension towers. complete all as specified and directed. |
| 41 | Supply and fixing for replacement of aluminium jumper of length upto 2.5 mtr made of ACSR conductor of type Zebra/Dog/Goat/Panther/Wolf /any type of conductor of 11/33 KV LINE complete all as specified and directed. |
| 42 | M&L for stretching/ tightning of loose ACSR conductor including fixing of conductor accessories such as clamp etc as per site condition of Zebra/ Dog/ Goat/ Panther/ Wolf/ etc/any type conductor of 11 KV to 33 KV lines. Note : Length of indl conductor shall be measured. |
| 43 | Supply, Installation, Testing & Commissioning Factory Made ( CPRI Approved/ Tested Manufacturer) Feeder Pillar Box of Size 1.2m x 1.2m x 0.8 meter (minimum) suitable for 11 KV HT Bus Bar Chamber 3 Way, Outdoor type, made out of 3.15mm CRCA Mild Steel Sheet, Powder coated, Dust and Vermin Proof with Rain Water Protection,Double Door type with Locking Arrangements with Provision of HT 11 KV Post Insulators, 03 No. Fixed Inside with suitable Size Copper Bus-bars not less 1250 Amps capacity, and 26 KA breaking capacity of all HT insulator mounting on HT spot insulator for Cable Connections, complete with HT creamic bushing and HT bushing road of suitable size and make arrangemennt the out going and incommer cable end joint should be seprately connected outside the inner busbar with proper locking arrange with nuts and bolts as directed. The HT panel having HT busbar tank should be seprated and connected through HT bushig and road and incoommer and outer connection of HT cable will be outside of the inner HT tank dully properly inclosed and 11 KV Danger Notice Board on all Sides, having all Steel Metal Works including Frame shall be with Anti-corrosive Coating with 07 Tank Process and Finally Epoxy Polyester Powder coating of Siemens Grey RAL-7035 Shade, Panel to be fixed at 450mm above Natural Ground Level on Brick Masonry Platform including Cement Concrete 1:2:4 (20mm graded stone aggregates) 100mm thick around the Area upto 1.50 Metre in all directions from the Panel all as ordered including Provision of Cattle Fencing with Open-able Gate (1.20 Metre to 1.50 Metre in Height) around the Area upto 1.50 Metre, complete all as specified and as directed. |
| 44 | Material and Labour for construction of platform for transformer 3 M(wide)x 3 m (long) & 1.5m (height) including moorum filling, earth work in brickwork any type of soil, brick work in CM (1:6) and PCC at top 10 cm thick (1:2:4) type B-1 and foundation with 1:4:8 type D-2, 25cm thick all as per drawing including plastering to exposed walls and white wash, providing MS channel on top of size 75x40x8mm of 1.5m length for rolling to transformer, including chain link fencing of wire mesh 150x100 size made out 4mm dia GI wire of height 1.5m fixed with the help of MS strip 25x6mm on and including MS angle iron 75x45x6mm thick 12 Nos post by the means of drilling holes at the distance of 30cm and fixed with the help of suitable nut, bolt and washer, the length of MS angle iron not less than 2.25m top of post bend to the shape of 60 degree including 03 Nos cuts for inserting barbed wire including 03 run of barbed wire and including provision of gate of size 1.5mx0.9m made out of MS angle iron 50x50x6mm and MS bar 12mm dia for meshing to the gate and locking arrangement complete all necessary for work, complete all as specified. |
| 45 | Taking down/Dismantling of old unserviceable/corroded ACSR Conductor of any size from existing over head lines completed and supply, lay and fix aerial bunched cable 11KV grade stranded and compact aluminium phase conductor of size 3x95 sqmm + 1x70 sqmm (bare messenger) with Aluminium alloy as per IS-8130-1984 ans ISD 398(Part-4)-1979. The phase conductor shall be insulated with XLPE (Sioplas) compound Aluminium as per IS-14255-1995 & IS-7098(Part-2)-1985 including all fittings such as anchor clamp, suspension clamp, line connector, service clamp, Including End joints insulator piercing connectors, for taps from bare line etc. complete all as specified and as directed. |
| 46 | Taking down/Dismantling of old unserviceable/corroded ACSR Conductor of any size from existing over head lines completed and supply, lay and fix aerial bunched cable 11KV grade stranded and compact aluminium phase conductor of size 3x120 sqmm + 1x95 sqmm (bare messenger) with Aluminium alloy as per IS-8130-1984 ans ISD 398(Part-4)-1979. The phase conductor shall be insulated with XLPE (Sioplas) compound Aluminium as per IS-14255-1995 & IS-7098(Part-2)-1985 including all fittings such as anchor clamp, suspension clamp, line connector, service clamp, Including End joints insulator piercing connectors, for taps from bare line etc. complete all as specified and as directed. |
| 47 | Scrapping , cleaning and preparation of old surfaces of steel tubular pole (11 mtr long) including painting channel, angel, clamp, nuts and bolts washer etc steel fitting complete and M&L for painting with one coat for aluminium paint after preparation of the steel surfaces by painting with two coat for aluminium paint after preparation of the steel surfaces and as complete all as specified and directed. directed |
| 48 | Scrapping , cleaning and preparation of old surfaces of of HT 4 pole structure of any type and size (Steel tubular pole) including all steel/MS fitting and fixture complete and M&L for painting with two coat for aluminium paint after preparation of the steel surfaces and then applied strap with two coats black & white paint in strip alternatively all round the poles from the bottom of the pole for indication of the poles. Height of the strap shall be 30 cm and number of strap shall be 05 Nos and writing Sub Stn No/feeder name with white luminaire paint of letter size 75 mm complete and complete all as directed. |
| 49 | Scrapping , cleaning and preparation of old surfaces of of HT 2/3 pole structure of any type and size (Steel tubular pole) including all steel/MS fitting and fixture complete and M&L for painting with two coat for aluminium paint after preparation of the steel surfaces and then applied strap with two coats black & white paint in strip alternatively all round the poles from the bottom of the pole for indication of the poles. Height of the strap shall be 30 cm and number of strap shall be 05 Nos and writing Sub Stn No/feeder name with white luminaire paint of letter size 75 mm complete and complete all as directed. |
| 50 | Mateial and labour for applied strap with two coats black and white paint in strap alternatevely all round the poles from the bottom of the pole for indication of the poles. Height of the strap shall be 30 cm and number of strap shall be 05 Nos. complete all as specified and directed. |
| 51 | Material and labour for writing pole No with sub stn No on pole with applied two coat of black paint and writing the pole No and Sub Stn No with white luminaire paint of letter size 75 mm complete and all as specified and directed. |
| 52 | Trimming and cutting of tree branches (not more than 50 mm girth) coming across 11 KV/33 KV HT over head line clearing the line around 2m single/both sides and disposal of branches from site not less than 250m from site complete all as directed by Engr-in-Charge.Note :-(i) Length of span is approx 60 to 100 RM.(ii) Due care is to be given while trimming/cutting the tree branches that there should no damage to over head line conductor/pole. In case due to any negligence, damage is caused to be make good/ renewal by the contractor from his own resources and nothing extra is admissible.(iii) All safety to labourer must be adhered by the contractor during trimming and cutting of tree branches.(iv) The above quoted rate is included for T & P, hydaulic machine etc. Total in Figures 0.0 0.0 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |