| 1 | Design, Supply, Installation, Integration, Testing and Commissioning with programming and configuration of Modbus RTU to Modbus TCP/IP gateway for Power Management System (PMS-SCADA based) on premise with Wired Architecture using Company LAN for 10,000 tags with Data base, Reporting tool and minimum 5 users webview provision at a time. PMS software should have Customized Dashboard Reporting with Historical database and Dedicated display of Energy and PQ Dashboard and PMS software shall be complete in all respect with following Functionalities.1. Data Acquisition for metering devices, sensors, and other intelligent electric devices i.e., The PMS Software suitable for monitoring and control of Electrical Substations equipment’s comprising of VCB panels (Breakers, relays), Transformers, S/S LT Panels and Sub Panels (Control of incomer breakers, status monitoring of all switchgears), Power Quality Equipment’s. DG Synch, ATS, APFCR etc..2. Power Quality analysis (including harmonics, voltage sags/swells, transients and voltage and current sinusoids), Power Quality compliance reporting for international standards (IEC61000 4 30)3. Reports (100ms PQ Report, Energy Period over period Report, Energy usage by shift report, System configuration report, Hourly Usage Report, Data Export Report and any other customer requires) and Reports are easy to read and understand - they are fully customised reports with user-created templates4. PMS software should be SCADA-based for device communication, integration, data acquisition, data management, monitoring & control and Business Intelligence with License engineering software.5. PMS Software should be Customisable for SLD creation and SLD's are to be created for Overall Power Distribution and Individual Substation wise SLD of 6 No's i.e., can programme the system as per specific needs. The system has a customised SLD creation and Trends.6. PMS Software should be Real-time reporting: Real-time communication for monitoring, control and diagnostics and system should supports multiple protocols and drivers like Modbus TCP/IP, Modbus RTU, IEC 61850, Simatic S7, OPC-UA, MQTT.7. The system should provide a facility with alerts and acknowledgments.8. PMS software should have Fully customized Dashboards to Create own dashboard to monitor KPIs such as:• Energy consumption• Power factor• Maximum demand• Regenerative power• Harmonic distortion• Specific energy consumption etc.9. PMS software should have Compile energy monitoring for different loads to obtain holistic picture.• View instantaneous parameters like voltage, current and power factor at a single location, through aesthetic dial gauges.• Continuously monitor drive parameters, e g. power, energy, current, voltage, frequency etc.10. Instant alerts by email & SMS notifications.Make: L&T (L&K)/ Honeywell/ Schneider/ Siemens/Jhonson Control/Equivalent |
| 2 | Supply and Installation of Modbus RTU to Modbus TCP/IP gateway converters i.e. from D+ and D- to Ethernet wiring standard for the communication-capable products with RS485 port with EMS software and Gateway supports Modbus RTU, ASCII (Master/ Slave) with and without mapping.Make: L & K/ Honeywell/ Schneider/ Siemens/Jhonson Control/Equivalent |
| 3 | Supply and drawing of 0.5 sq.mm 2 core Shielded twisted pair data cable, copper with low impedance, capable to transmit the data of the energy meters serial port RS485 with PVC sheath to gateway converters including conduit on surface/ recessed steel/ PVC conduit, ties/clamps and including terminations etc as required.Make: Beldon/ Finecore/Varsha/ AT&T/Caliplast |
| 4 | PC SystemSupplying Installation Testing Commissioning of Client PC System comprising of PC Hardware with minimum 11th Gen Intel® I7 processor CPU x64 (or better), compatible with 8 core processors minimum 3.1 Ghz and 32GB RAM, Hard Drive Space of 256 GB SSD and 2TB HDD and DVD ROM, Video card and monitor (24 inch full LED) capable of 1920 x 1080 pixel resolution or better with Ethernet adapter (10/100/1000 Mbps with RJ-45 connector), USB Ports (2Nos), NIC (2 No's - 4 ports) with 2 GB or higher Graphics card HDMI ports with USB keyboard, USB Mouse three button and scrolling, . With licensed Windows 10 Pro/11, 64 bits software or higher, MS Office 2013 or better 64 bits software, Anti Virus Software and Adobe reader as per suitable for BMS/PMS System complete etc. as required.Make: Hewlett Packard/ Lenevo/ DellMonitor Make: Samsung/ Sony/LG/ Dell/HP |
| 5 | Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 23AWG Twisted Pair Data Cable in existing conduit on surface/recessed including ties/ clamps, terminations etc., Category 6 Unshielded Twisted Pair, 4 pair should be complied as per UL/ETL verification program for compliance with ANSI/TIA-568.2-D standard. Outer diameter should be in the range of 6.1mm nominal with Operating Temperature Range : -5° to +60°C, Bending Radius : < 4 X Cable Diameter at –5°C ± 1°C and Pulling Force : 11.5Kg etc. complete as required.Make: D Link/AMP/Molex/Legrand/Krone/R & M . |
| 6 | Supply and fixing of Cat 6 RJ-45 information outlets including Single face plate and fixing of 2 module GI/PVC box along with modular base & cover plate including terminations and ferruling. |
| 7 | Supplying and fixing of 25mm sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit asrequired.Makes : Sudhakar / Finolex / Modi / VIP/ Precision / Universal / Million Plast /Goldmedal / GM / DEC / Beljin |
| 8 | Supply and Installtion of 16 port or site suitable requirement basis of 10 / 100 / 1000 Gigabit unmanageable Ethernet switch.Make : TP Link / D link / Netfox |
| 9 | Supplying of external 4TB (Terabytes) capacity Hard Disk with upto 256MB/s Transfer Rate, 256 MB Cache, 7200 RPM Disk Speed, 3.5 inch form factor, SATA Interface, BSMI, ICES-003/NNB-003, CE, FCC, KC, Maghreb, RCM, UKCA, VCCI, CB-Scheme, TUV, UL Certifications.Make : WD / Seagate or equivalent as approved by Department |
| 10 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of upto 35 sq.mm or laying of OFC cable in HDPE pipe direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 11 | Supply and erection of L.T. 3phase Digital multifunction energy meter Class I RS 485 with LED display for measuring all the parameters (Voltage, Current, Frequency, Power factor, KW, KVA, KWH, KVA, KVAH, KVAR, Maximum Demand and THD(V&I) Events) on existing box panel board including making hole and making connections etc., complete.MAKE : CONZERVE / ELMEASURE / LK (L&T) / SEIMENS. |
| 12 | Supply and erection of LT current transformer with bar primary 100/5A to 1000 / 5A ratio in the existing panel including connections, terminal blocks etc., complete.MAKE : KAPPA/ Equivalent |
| 13 | Supplying and drawing 2 x 2.5 sq. mm sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC/flexible conduit including termination lugs and ties etc as required.Make: Finolex / RR kabel / Havells /APAR EBXL / KEI / LK / V-guard. |
| 14 | Supply and laying of 25mm SWR reinforced Flexible Conduit Pipe.Make: Precision or its equivalet. |
| 15 | Supplying and fixing 6 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of Single pole MCB with Din channel and terminal blocks in the existing panel complete with connections, testing and commissioning etc. as required.Make : Legrand-DX3 / Schneider-Acti9/ Siemens / LK Exora / BCH / Havells Stadx |
| 16 | Online UPS - Input supply: Single Phase, Output Supply : Single Phase. Supplying, installation, Testing & Commissioning of 3kVA capacity at full load (Unity Power Factor) ON LINE Uninterrupted Power Supply (UPS) system suitable for Single Phase input, Single Phase output AC Supply. The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. The UPS systems shall be Microprocessor based Digital Control, using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter with PWM (Pulse Width Modulation) Technology. The quality of design, manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >95% at 100% non-linear loads. Current total harmonic distortion (ITHD)/ total demand distortion (TDD) on the input grid shall be < 5% at 100 %load. (The required LC filters shall be included in UPS cost), extreme power factor kit to be include to limit the input pf to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ) however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC single phase 160-270V 50 Hz and delivering output AC supply true sine wave single phase 220/230/240 Volt, 50 Hz +/- 0.2Hz,Overload capacity of 120% for 10 mins and 150% for 1 minute. Operating temperature 0 to 40 deg C, Relative humidity 0-95% non condensing, noise level less than 60db at 1 meter distance, Protection for Under voltage, over voltage, abnormal output voltage, battery over charging, output over current, short circuit, battery deep discharge , 10 KV surge. Display for watt/VA,Amp and Voltage power parameters etc. UPS shall comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI) type UPS (as per standard IEC 62040-1, 2 & 3) . The UPS should be with IGBT Based Inverter Technology, Communication RS232/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge. Required battery racks, DC breaker of suitable rating and interconnecting copper conductor cable of suitable size and connectors and all required accoseries are inclusive in the cost. The UPS should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc Make: Numeric / Emerson / Fuji Electric/Schneider/ABB Please Enable Macros to View BoQ information |