| 1 | Supply only XLPE insulated armoured cable (heavy duty) electric cable with aluminium stranded conductor 1100 volts grade of following size after taking down complete all as specified and directed by Engr-in-charge and directed as follows : |
| 2 | 10 Sqmm x 2 Core |
| 3 | 16 Sqmm x 4 Core |
| 4 | Supply, installing, testing and commissioning factory made LT ( 415 Volts, 50 Hz , 3-phase, 4 wire supply ) CPRI approved and tested Street Light TIme switch Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system. The panel shall be dust and vermin proof, protection class ( IP-54 ) and made of 3.15 mm thick CRCA mild steel sheet and mild steel angle iron frame work ( made out of 40 mm X 40 mm X 6 mm thick ), front opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035 embedded in ground with and including bocks of PCC 1:2:4 type B1 of block size 30x30x30 cm, Make of Panel Board:- Adlec/ Schneider / Universal Switch Gear Control/ Tricolite.The scope of work also comprising of the following:- |
| 5 | INSTRUMENTS:-(i) Red, Yellow, Blue Phase indicating light LED type- 01 Set.(ii) Control MCB 6 A SP C Series - 1 Set.INCOMING:-(i) MCB 63 Amps, 4 Pole, 10 KA, 50 Hz, 415 Volts-01 No. Make: L&T/ Havells / Legrand(ii) Power Contactor 3 Pole, 32 Amps. 50 Hz, 220 Volts- 01 No. Make: L&T/ Havells/ ABB or equivalent.(iii) Automatic astronomical Timer Switch with battery backup of 100 hours, Programmable every 4 Hours current capacity 16 Amps 240/415 Volts, 50 Hz- 01 No. Make: L&T/ Havells or equivalent.(iv) Auto Manual Selector Switch 6 A SP- 01 No. Make: L&T/Schneider/Kaycee.(v) RED Phase indicating light LED type- 01 No.. Make: L&T/Vishnu/ Schneider/ C&S.(vi) Outgoing Terminal 4 Way - 1 Set. Make: Master/FTC/Connectwell.Panel wiring for control circuit with copper flexible 1.5 Sq mm & power wiring 10 Sqmm flexible.Note: In Case of failure, manual system should also be provided. |
| 6 | The panel manufacturer should have following Govt. Approved Certificates: 1. Panel should be according to IEC-61439. CPRI Certification Degree of Protection IP-54 (IS/IEC : 61439 (Part-1), 2011 & IS/IEC : 61439 (Part-2) 2011)2. Tempreature Rise (IS/IEC : 61439-1, 2011 & IS/IEC : 61439-2 2011)3. CPRI Short Circuit IEC-61439-1 & 2 withstand strenght should be 70kArms for 1.0 Sec with intial peak of 154kApk4. CPRI Certification IEC-61439-1 & 2 Rated current for short circuit not less than 6300 A with rated insulation voltage 660V5. ISO 9001 CERTIFIED |
| 7 | Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC platform incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge. |
| 8 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required upto 35 sqmm complete all as specified and as directed by Engr-in-charge. |
| 9 | Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required for following: |
| 10 | 16 Sqmm x 2 Core |
| 11 | 16 Sqmm x 4 Core |
| 12 | Arranging fault locating machine to locate the fault in underground electric power cable of any length & any type of 1.1 KV grade HT/ LT cables & pin point the fault, it also include testing of the cable after locating fault and cutting the cable at Fault to fix the joint including excavation and earth wotrk in any type of soil complete Note : Cable joint shall be measured and paid separately under respective of Sch 'A' (ii) If fault is not rectifed within 24 hours after receivng message , the contractor shall be charged penalty for Rs 500/- per Hours & the same has been deducred from his account during RAR |
| 13 | Supply & fixing in repair of moulded case circuit breaker four pole 100 amps 16 KA Capacity 415V 50 Hz with adjustable thermal and magnetic relay incl replacement of lugs & disconnecting and taking out the old unservicable MCCB from panel/DBs/ etc complete all as specified and directed by Engr-in-charge and directed. |
| 14 | M&L for painting of Galvanised iron type pole for post top Lattern after Cleaning and scraping with wire brush complete with two coat of aluminium paint over a coat of red oxide primer and applying one coat of cement base paint on PCC coping complete all as directed br engineer in charge. |
| 15 | S&F in repair of Inverter LED Street Light, PDC housing, IP66, Inbuilt Battery back-up- Auto ON/OFF/DIMMING (pre-programmable) fitting 60 Watt Highly efficient made of pressure die cast aluminium housing with lens & toughened glass including taking down of old unservicable conventional security light fitting and fixing material ie MS clamp, Nut and bolt,anchor fastner washer etc complete all as directed with following specification of Model :- LED SL INVER HLSLD-ML04-60-CWL-INV-RTC-R of Haloix or equivalent in PS.Wattage: 60W ± 10%Color Temperature: 5700K (Cool White)Housing & Protection: Aluminum PDC with IP66 (dust/water) and IK05/07 impact resistanceBattery Backup: Integrated Li-ion battery with 4 hours max backup (Initial lumen reduces to 40% in battery mode)Operating Voltage: 140V-270V AC (with 5KV surge protection)Control Mechanism: RTC timer-based auto on/off with pre-programmable dimming |
| 16 | S&F in repair of LED Street light fitting 90 Watt Highly efficient made of pressure die cast aluminium housing with lens & toughened glass including taking down of old unservicable conventional security light fitting and fixing material ie MS clamp, Nut and bolt,anchor fastner washer etc complete all as directed . |
| 17 | S & F LED flood light luminaires 200 watts, 230 volts AC, out door type with pressure die cast housing resistant to impact and corrosion, glare free complete with lamp, driver complete all as specified. |
| 18 | S&F in repair thermoplastic cable junction box with metric knock out for cable entry of size 200x160x98mm with 4 Nos of 200A aluminium busbar mounted on insulators, terminal and provision of din rail for fixing of MCB 10A capacity including fixing with clamp 30x5mm iron flate, nuts, bolts and washer complete including providing of steel conduit of dia 32mm bore of length 1.60 mtr including earth work for taking out of cable,old unsv junction box and fixing complete all as specified and directed. |
| 19 | Supply drawing, connecting and testing of 3 core, 1.5 Sqmm PVC insulated and PVC round sheathed copper conductor (flexible ) industrial cable, 1100 Volts conforming to IS 694 in steel tubular poles from KIOSK box to street light fitting including providing suitable copper lugs all as specified and directed by Engr-in-charge. |
| 20 | Taking down of Existing any type of street light/ Bolard/ Posttop laltern/flood Light/ Building securityLight / high mast light etc fittings from street poles/roof top of any type capacity for carrying out necessary repair and re-fixing the same light after necessary repairing, wiring, cutting and taping through connection wire Complete all as specified and directed by Engineer-in-Charge. |
| 21 | M & L Painting of steel tubiler swaged poles of height up to 10 mtr with two coat of aluminium paint and cleaning, scrubing incl junction box. Marking of Pole No by Trained Painter etc complete as specified and directed by engineer-in-charge. |
| 22 | Dismantling of metallic pole of Length Above 8.0 Meter and upto 10.0 Meter from on Location using all manpower and necssaery T & P and refixing the same includung erection of metallic pole in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. |
| 23 | S&F in repair GI braket for fixing of street light fitting atleast 1.5 mtr long to be fixed in wall while constructing the wall and it has to be bend to install the bldg security light fitting including necessary cutting, welding and MS fastner, clamp to the light and painting the bracket by good quality paint as directed by Engr-in-Charge. Please Enable Macros to View BoQ information |