| 1 | Total amount of Sch 'A' Part-I (Section-I) ( Bldg Work) Note : This schedule is not pre priced by MES and the pre priced rate indicated as \\"Rs. 0.00\\" under Col.5 signifies this fact only |
| 2 | Design, Fabrication, Erection and construction of building (Stilt + 6 ) configuration for Married Accommodation as per architectural Drawings and structural drawings designed by the bidder based on input data as provided in the tender documents and as per specification including as per note given below:- Note:- (A) Super structure in steel strcture as per IS 800 and IS 1893-2016 with limit state method using LGSF member confirming to IS standard with RCC foundation Shallow or deep foundation based on the safe bearing capacity (SBC) of the soil as and the structure load as per design criteria specified. (B) Reinforced Cement Concrete - M-30 Design mix and Reinforcement steel of grade Fe-500D/550D TMT bars. (C) Floor/ Deck slab shall be of GI profiled sheet of thickness as per design with RCC laid over it as per IS 11384. (D) Internal and external wall except for bathroom and toilet Area as shwon in shall be of minimum 140 mm thick composed of LGSF member with surface as specified. Space between surface shall be filled with Rockwool insulation of minimum 50 mm thickness of density 48 kg/cum. Bathroom and Toilet shall in PCC Block as shwon. (E) Firefighting cum over head tank of capacity as shown shall be design, construct and finished in GRP as per IS 14399- 1&2 (F) The detailed design and construction shall also include design of internal water supply scheme and sanitary plumbing scheme and supply and fixing of fitting and fixture as specified. (G) The design and construction shall cater for provision of services such as internal electric supply,water supply, sanitary plumbing works, internal heating etc.(H) Confirmatory SBC test as per IS Provisions.(J) Finish of Building as per Schedule of Finish. any missing details of finish shall be as per manufacturuer guidelines and as approved by GE(K) Wall of liftwell however, shall be in 230mm thcik in RCC/ Steel Frame confirming to requirement of relevant IS code and manufacturer for Lift. |
| 3 | Construction of Pump House Building in single storey in RCC frame as per drawings, complete all as specified and as directed by Engr-in-charge |
| 4 | Construction of UG Sump of 50000 ltr capacity sump in RCC as per Drawing No CEAF/STD-34/2002, complete all as specified and as directed by Engr-in-charge |
| 5 | Total amount of Schedule 'A' PART-I (BUILDING WORK) |
| 6 | Total amount of Sch 'A' PART-II (SEC-I) (INTERNAL ELECTRIC SUPPLY WORKS) |
| 7 | Total amount of Sch 'A' Part-II (Section-II) (INTERNAL ELECTRIC SUPPLY WORKS) Note : This schedule is not pre priced by MES and the pre priced rate indicated as \\"Rs. 0.00\\" under Col.5 signifies this fact only |
| 8 | S&F LED Building security Light fitting 25 watt, for opearting voltage between 110V to 320V system efficiency not less than 120 lumen / watt, PF-0.95 minimum, IP66 protection, 5700CCT(K), CRI between 80-85, confirming to LM79 and LM 80 standards or as per IS-16104:2012 and IS-16106:2012, for estimated life span of minimum 50,000 hrs consisting of high / low voltage cut off, maintenance free isolated Electronic driver circuits, Low THD, PMMA grade high quality Transmittance lens, Epoxy powder coated Die Cast Aluminium housing with LED street optics LENS for uniform light distribution, weather proof gasket for lamp & driver compartment, Heat resistance toughened UV stabilized glass fitted in cast aluminium housing with SS screws, complete all as specified and directed by Engineer-in-Charge |
| 9 | Supply and fixing MCB Single Pole 10Amps rating 240V, 10KA 'C' curve miniature circuit breaker complete with connection testing and commissioning complete all as specified and directed by Engineer-in-Charge. |
| 10 | Supply and fixing MCB Single Pole 6 Amps rating 240V, 10KA 'C' curve miniature circuit breaker complete with connection testing and commissioning complete all as specified and directed by Engineer-in-Charge |
| 11 | Supply and fixing MCB Single Pole 16 Amps rating 240V, 10KA 'C' curve miniature circuit breaker complete with connection testing and commissioning complete all as specified and directed by Engineer-in-Charge |
| 12 | Supply and fixing RCBO for earth leakage, overload & short-circuit protection double pole 32A, 100 mA, AC 240 volt, 10 kA, C - curve comforming to IS-12640-2 & IEC 61009-1 complete with connection testing and commissioning complete all as specified and directed by Engineer-in-Charge Please Enable Macros to View BoQ information |
| 13 | Supply and fixing RCBO for earth leakage, overload & short-circuit protection double pole 32A, 100 mA, AC 240 volt, 10 kA, C - curve comforming to IS-12640-2 & IEC 61009-1 complete with connection testing and commissioning complete all as specified and directed by Engineer-in-Charge Please Enable Macros to View BoQ information |