| 1 | Total amount of the \\"Rate Schedule\\" sheet SCHEDULE OF QUANTITY AND RATE FOR CONSTRUCTION OF HT LINE, LT LINE & SUB-STATION FOR RELEASING OF NEW SERVICE CONNECTION UNDER EDSD, MOHANPUR UNDER EDD, MOHANPUR WITH SUPPLY AND FIXING OF DECENTRALIZED MATERIALAGAINST E-TENDER SPECIFICATION NO.22/EDCRDDUN/2026-27 Name of The Bidder's Firm: 0.0 Sl. No. Description of Work Unit Qty Rate Amount Part [A] (Supply Portion) |
| 2 | 11KV XLPE HS Cable J/K 3X70/120 mm sq I/D |
| 3 | 11KV XLPE HS Cable J/K 3X70/120 mm sq O/D |
| 4 | Alu.toAlu. Connector ABCable 16 Sqr.mm to 16 Sqr.mm. |
| 5 | Alu.toAlu. Connector ABCable 95 Sqr.mm to 95 Sqr.mm. |
| 6 | Connecting Cable AB Cable to Dist. Box 1X16 Sqr.mm |
| 7 | Connecting Cable AB Cable to Dist. Box 1X25 Sqr.mm |
| 8 | Danger Board with Clamp Made of flat 25X3 mm with N&B |
| 9 | Dead End Clamp with Eye Hook ABCable ST Pole SP-10 |
| 10 | Dead End Clamp with Eye Hook ABCable ST Pole SP-21 |
| 11 | Dead End Clamp with Eye Hook ABCable ST Pole SP-23 |
| 12 | Dead End Clamp with Eye Hook ABCable ST Pole SP-33 |
| 13 | Dead End Clamp with Eye Hook ABCable ST Pole SP-55 |
| 14 | Dead End Clamp with Eye Hook AB cable PCC pole |
| 15 | Distribution Box with N&B ABCable 3Ph 8-Way |
| 16 | Earth Wire Clamp with N&B PCC Pole 8.5M.Long(MS flat 50X6mm) |
| 17 | Earth Wire Clamp with N&B ST Pole SP-10 (MS flat 50X6mm) |
| 18 | Earth Wire Clamp with N&B ST Pole SP-21 (MS flat 50X6mm) |
| 19 | Earth Wire Clamp with N&B ST Pole SP-23 (MS flat 50X6mm) |
| 20 | Earth Wire Clamp with N&B ST Pole SP-33 (MS flat 50X6mm) |
| 21 | Earth Wire Clamp with N&B ST pole 1sP-55 (Ms flat 50x6mm) |
| 22 | F-Clamp for 11KV PCC pole Line made of flat 65X6mm with N&B |
| 23 | LT Clamp with N&B PCC Pole 8.5Mtr.Long (MS flat 50X6mm) |
| 24 | LT Clamp with N&B ST Pole SP-10 (MS flat 50X6mm) |
| 25 | LT Clamp with N&B ST Pole SP-21 (MS flat 50X6mm) |
| 26 | LT Clamp with N&B ST Pole SP-23 (MS flat 50X6mm) |
| 27 | LT Clamp with N&B ST Pole SP-33 (MS flat 50X6mm) |
| 28 | LT Clamp with N&B ST Pole SP-55 (MS flat 50X6mm) |
| 29 | Lug Alu Alloy Al. Lug 120 mm sq |
| 30 | Lug Alu Alloy Al. Lug 70 mm sq |
| 31 | Lug Alu Alloy AI Lug 95mm Sq |
| 32 | MS flat PCC Pole 8.5M (50X6mm) with N&B |
| 33 | PP&Clamp with N&B PCC Pole 8.5Mtr Long (MS flat 50X6mm) |
| 34 | PP&Clamp with N&B ST Pole SP-21 (MS flat 50X6mm) |
| 35 | PP&Clamp with N&B ST Pole SP-23 (MS flat 50X6mm) |
| 36 | PP&Clamp with N&B ST Pole SP-33 (MS flat 50X6mm) |
| 37 | PP & Clamp with N&B ST pole SP-55 (Ms flat 50x6mm) |
| 38 | Shackle Insulator 100X115 mm with N&B |
| 39 | Shackle Insulator 100X115 mm without N&B |
| 40 | Shackle Insulator 75X90 mm with N&B |
| 41 | Stay Clamp with N&B PCC Pole 8.5Mtr.Long (MS flat 50X6mm) |
| 42 | Stay Clamp with N&B ST Pole SP-10 (MS flat 50X6mm) |
| 43 | Stay Clamp with N&B ST Pole SP-21 (MS flat 50X6mm) |
| 44 | Stay Clamp with N&B ST Pole SP-23 (MS flat 50X6mm) |
| 45 | Stay Clamp with N&B ST Pole SP-33 (MS flat 50X6mm) |
| 46 | Stay Clamp with N&B ST Pole SP-55 (MS flat 50X6mm) |
| 47 | Stay Insulator 90X65 mm |
| 48 | Stud Clamp with N&B PCC Pole to PCC Pole 8.5Mtr Long |
| 49 | Stud Clamp with N&B ST Pole SP-33 to SP-23 |
| 50 | Suspension Clamp with Eye Hook ABCable SP-10 ST Pole |
| 51 | Suspension Clamp with Eye Hook ABCable ST Pole SP-21 |
| 52 | Suspension Clamp with Eye Hook ABCable ST Pole SP-23 |
| 53 | Suspension Clamp with Eye Hook ABCable ST Pole SP-33 |
| 54 | Suspension clamp with Eye Hook AB Cable PCC pole |
| 55 | Top Bracing Clamp with N&B ST pole (Ms flat 50x6mm) |
| 56 | Bottom Bracing Clamp with N&B ST pole (Ms flat 50x6mm) Total - Part [A] 0.0 Part [B] (Labour Portion) |
| 57 | Cartage of ST pole and PCC Poles from store centre to construction site with loading, unloading at both points and oroper stacking. SP-10 No. 1.0 0.0 SP-21 No. 1.0 0.0 SP-23 No. 1.0 0.0 SP-33 No. 1.0 0.0 SP-55 No. 1.0 0.0 PCC Poles No. 1.0 0.0 |
| 58 | Cartage of other material (other than poles) by vehicle fro Store Center to nearest construction site Store including loading and unloading at both ends. Rs.Per Qtl. Qtl. 1.0 0.0 |
| 59 | Cartage of the following capacity transformers from store center to construction site with loading and unloading at both points 25/16 KVA No. 1.0 0.0 63 KVA No. 1.0 0.0 100 KVA No. 1.0 0.0 11 KV VCB(l/c,0/g) bus cupler,Pannels/PRMC No. 1.0 0.0 |
| 60 | Head load cartage of following Poles from road to site Upto 0 to 1 Km. SP-10 No. 1.0 0.0 SP-23 No. 1.0 0.0 SP-21 No. 1.0 0.0 SP-33 No. 1.0 0.0 SP-55 No. 1.0 0.0 PCC Poles No. 1.0 0.0 |
| 61 | Head load cartage of Small material. Rates are per Km/Quintal including loading and Unloading. Upto 0 to 1 Km. Qtl. 1.0 0.0 |
| 62 | Head load cartage/ mannual shifting / lifting with crane/hydra of the following transformers along with loading/Unloading at both points Upto 0 to 1 Km. 16 KVA No. 1.0 0.0 25 KVA No. 1.0 0.0 63 KVA No. 1.0 0.0 100 KVA No. 1.0 0.0 |
| 63 | Excavation of earth for pole pit of size 0.9x0.6x1/6 of full length of pole for erection of pole in all type of soil including proper dressing of sides and ramming of bottom including getting out the excavated soil and disposal of surplus excavated soil as directed complete work |
| 64 | Erection of following Single support pole in proper level and alignment alongwith fixing of all accessories, like top channel & clamps as per RESPO construction Manual. SP-10 No. 1.0 0.0 SP-21 Nos 1.0 0.0 SP-23 Nos 1.0 0.0 SP-33 Nos 1.0 0.0 SP-55 Nos 1.0 0.0 PCC Poles Nos 1.0 0.0 |
| 65 | Erection of following Double support pole in proper level and alignment along with fixing of all accessories, like top channel, X-bracing & clamps as per RESPO construction Manual. SP-23 Nos 1.0 0.0 SP-33 Nos 1.0 0.0 SP-55 Nos 1.0 0.0 PCC Pole Nos 1.0 0.0 |
| 66 | Grouting of pole in size 0.45x0.45x1/9 of the support in CC ratio 1:4:8 (1 cement : 4 graded stone 20mm nominal size : 8 coarse sand ) block including cost of Cement,sand and stone ballast back filling of soil and boulders in pit and ramming and proper alignment, leveling as per RESPO construction Manual. |
| 67 | Muffing of poles size 0.45 cm x 0.60 cm radious with cc 1:3:6 (1 cement : 3 coarse sand : 6 graded stone 10mm nominal size) block size 45cm height from ground level including cost of cement, stone and sand etc. |
| 68 | Fabrication of M.S. Channel Angle iron after cutting in required sizes with drilling of holes upto good finish for top channel, bracing and special type bracket etc. as per RESSPO sehedule and local approved drawing. |
| 69 | Fixing of D-type bracket in LT line |
| 70 | Fixing of triangular type bracket in 11 KV line |
| 71 | Excavation of earth for stay pit of size 0.06x0.06x1/2 mtr. in all type of soil including proper dressing of sides and ramming of bottom including getting out the excavated soil and disposal of surplus excavated soil as directed complete work |
| 72 | Fixing , tightening and nozzaling of Stay with pole and stay rod on required tension as per drawing / RESPO manual. LT stay Nos 1.0 0.0 11 KV line Nos 1.0 0.0 |
| 73 | Grouting of Stay in size 0.6x0.6x0.3 in CC ratio 1:4:8 (1 cement : 4 graded stone 20mm nominal size : 8 coarse sand ) block including cost of Cement,sand and stone ballast back filling of soil and boulders in pit and ramming and proper alignment, leveling as per RESPO Manual. |
| 74 | Earthing of support with M.S. Earth rod of 2.5 meter long by hammaring of M.S. Rod to proper depth and connecting the earth electrode with the helpof G.I. wire as per construction manual. |
| 75 | Laying, Spreading, Stringing and sagging of 11 KV / 33 KV line in 3 phase (3 Phase 4 wire) of the following wire as phase wire with G.I. earth wire complete including fixing of all accessories in 3 Nos. conductor in parallel with binding and jumpering as per profile and sagging chart. ACSR Rabbit CktKm. 1.0 0.0 ACSR Weasel CktKm. 1.0 0.0 ACSR DOG CktKm. 1.0 0.0 |
| 76 | Laying. Spreading, Stringing and sagging of L.T. Lines of the following wire as phase wire vith G.I. earth wire complete with binding and jumpering as per RESPO Specn. ACSR Weasel Conductor 1 phase 2 wire length CktKm. 1.0 0.0 3 phase 4 wire length CktKm. 1.0 0.0 ACSR Rabbit Conductor 1 phase 2 wire length CktKm. 1.0 0.0 3 phase 4 wire length CktKm. 1.0 0.0 |
| 77 | Chemical Earthing: Earthing of distribution transformer including digging of pit of size 2.5 Mtr depth and make hole of size 150 mm. Placing of earthing electrode (to be supplied by contractor as per drawing No. A) as drawing B, connecting the same with G.I. Strip (to be supplied by contractor ) of size 35x6 mm as per drawing C for a minimum lenght 6 m. treatment of soil with highly condctive substance as per IS 30343 complete in all respect, result of earthing resistance to be recroded in M.B. before and after installation of earthing. The earth resistance after earthing should be less than 1 Ohm. |
| 78 | Guarding of Line over (Telephone / Road / L.T. line crossing as per drawing with 6/8 SWG G.I. wire including fixing of guarding channel/ angle as per RESPO manual. L.T./11KV /33KV LT./11KV Line. Per Span 1.0 0.0 |
| 79 | Laying and erection of L.T. PVC Cable including crimping of lugs of size 1x70,120, 150 Sq.mm. (Including all cost of material) |
| 80 | Mounting & Fixing of TPMO on double pole structures including making of connections complete work |
| 81 | Mounting & Fixing of Fuse sets on double pole structures including making of connections complete work |
| 82 | Mounting and Fixing of Lightning arrestor set (3 Nos.) on double pole structure including making all connections by G.l. strip size 35x6 mm to earth point complete work excluding cost of G.t.Strip) |
| 83 | Jointing and Fixing of Cable Jointing Kits Indoor /outdoor cable boxes. 11 KV XLPE heat shrinkable No 1.0 0.0 Fixing & Installation of LT Fuse set Nos. 1.0 0.0 |
| 84 | Installation / mounting of new Tranformer on plinth pole structure and fixing of channel / angle etc. and making all connections of Ht and LT side and its complete commissioning. On Double Pole 25/16 KVA No. 1.0 0.0 63 KVA No. 1.0 0.0 100 KVA No. 1.0 0.0 |
| 85 | Route cleareance by cutting of tree branches / proning, lopping and chopping of trees for L.T., 11 &33 KV line. |
| 86 | T-off Connection Complete 11 KV line. |
| 87 | T-off Connection Complete 33 KV line. |
| 88 | Providmg and fixing of Danger Board complete by providing clamps of MS. Flat 50x5 mm and Nuts & Bolts, danger Boards of M.S. Sheet 2 mm Thick 11\\"x7\\" size Including cost of all material) |
| 89 | Disconnection/Reconnection of existing service connection by jumpering as per RESPO Schedule. |
| 90 | Digging of trench of size 0.60x0.15x1.5 mtr. and laying of underground 11 KV XLPE cable with making of brick housing and filling of sand including filling of earth with ramming. & repairing of road including cost of cement sand and stone blast |
| 91 | Making of section pole for existing LT/HT/33KV line complete in all respect. |
| 92 | Installation of 33/11 KV Metering cubical in the Metering room with grouting and making all connection |
| 93 | Fixing of Gl pipe. |
| 94 | Fixing of RCC cable route marker Including cost material |
| 95 | Loading, unloading & carriage of LT PRMC from Store to pit site & Installation on the double pole with the help of Nut Bolt & Clamp and making to pass LT cable from T/F tc PRMC. |
| 96 | Mannual shifting /Pulling from existing site to plinth/ nearby place distance upto 200 mtrs. 11 KV VCB l/C 350 MVA, 600/300/5A, 110 V AC/PRMC Nos. 1.0 0.0 |
| 97 | Laying, Sagging & Binding of AB cable of size 25/120 sqmm these rates are only for cable additional provisions to be made for matching accessories installation, case of any network modification ie. Additional pole etc. and for actual connection disconnection as per site condition. |
| 98 | Release of Single Phase Conncetion: Complete errection of LT PVC Cable 2x4 sqmm/2x6 sqmm and installation of single phase electronic meter 10-60 Amp on pole or outside the premises of applicant |
| 99 | Release of Three Phase Conncetion: Complete errection of LT PVC Cable 4x6 sqmm/4x10 sqmm and installation of single phase electronic meter 10-60 Amp on pole or outside the premises of applicant |
| 100 | Jumpering and connection complete on the D/P conductor to TPMO fuse set & T/F |
| 101 | Making of complete T/F Base on the D/P. |
| 102 | Laying, Stringing, Sagging of 11KV XLPE Cable 3x120sqmm |
| 103 | Laying, Stringing, Sagging of 11KV XLPE Cable 3x35/3x70 sqmm |
| 104 | Dismantling of Transformers 25 KVA No. 1.0 0.0 63 KVA No. 1.0 0.0 100 KVA No 1.0 0.0 |
| 105 | Back cartage of following type of material from site to JE/Center Store 25 KVA No. 1.0 0.0 63 KVA No. 1.0 0.0 100 KVA No 1.0 0.0 11 KV VCB(l/c,0/g) bus cupler,Pannels/PRMC No. 1.0 0.0 |
| 106 | Back Head load cartage of following type of material from site to JE/Center Store 25 KVA No. 1.0 0.0 63 KVA No. 1.0 0.0 100 KVA No 1.0 0.0 11 KV VCB(l/c,0/g) bus cupler,Pannels/PRMC No. 1.0 0.0 Total - Part [B] 0.0 TOTAL [Part-(A) + Part (B)] 0.0 Place Date Superintending Engineer Please Enable Macros to View BoQ information |