| 1 | Supply of 8 mtr.HT HOT DIP Galvanised Octogonal pole with bottom dia 135 mm A/F, top dia 70 mm. A/F, thickness of 4.0 mm HT sheet and base plate of size 225 x225 x 16 mm including 1500 mm. long Decorative SINGLE ARM BRACKET made up of 40NB dia GI pipe including 4 nos. M20 X 700 long \\"J\\" type EN- 8 grade foundation bolts along with template (Material Spec. as per BSEN 10025 grade S355J0).This includes anti theft locking arrangement.(Challan, QAP and test certificate to be submitted) Make: Utkarsh / Transrail / Valmont |
| 2 | Erection of hot dip galvanised Octagonal poles 8 / 10 Mtr including making R.C.C. foundation [as per drawing & design enclosed] including Eachrth work in excavation of foundation pit, making R.C.C. foundation and also including supply of all materials e.g. cable entry pipes, anchoring bolts and nuts, washers, sand, cement, coarse aggregate, reinforcement rods etc. and refilling of pit, duly rammed and finished complete as per direction of and up to satisfaction of E.I.C. This includes 3 mm nEacht cementing. |
| 3 | \\"Supply and delivery of LED street light fitting with pressure dia cast alluminium housing with IP-66 and IK not less than 08, conforming SMD 90 watt, lumen output (delivered lumen) >110 lumen / watt with BIS mark filled silicon potted driver, in built tilting arrangement upto 15 degree, supply voltage 140V 270V, driver compatible with open voltage, short circuit, open circuit, sustain 440V for 15 min, 1 KV for 1 min, surge protection 10 KV, LM 79 & LM 80 report from NABL Lab, Make of LED lumileds, OSRAM, CREE. All LED must be high power LED (not less than 3 Watt individually) with ceramic package & hEacht pod minimum view angle of LED shall not be less than 120. (Make : Jaquar/WIPRO/KLite |
| 4 | Fixing of LED light fitting with 180-200 watt, 120V - 270V LED on the top of the pole and necy. Accy. as per direction of EIC. |
| 5 | Supply and delivery 1.1 KV grade XLPE insulated stranded Alumunium conductor galvanised steel armoured cable of the following sizes Make: Havells / Polycab / KEI I ) 4 core X 16 sq. mm. |
| 6 | II) 3.5 core X 50 sq mm |
| 7 | Eachrthing with 1 no.of G.I. Eachrth spike [20 mm dia X 1.5 mtr long] driven into the ground up to 2mtr, drawing Eachrth line with separate 4 SWG G.I. wires providing 15mm dia G.I. pipe protection 1 mtr. from Eachrth spike Feeder Box/Junction Box,/ poles and fixing to the same by suitable nuts & bolts all complete as per direction of EIC. (31 nos. for Pole) |
| 8 | a) Laying of 1.1 KV grade XLPE insulated stranded Alumunium conductor galvanised steel armoured cable of the following sizes in the under ground trench having 460mm wide X 760 mm. average depth with 8 nos. of brick protection per meter on the top of the cable including excavation of Eachrth in cutting trenches filling space between the brick and cable and also the trench with shifted soil, leveling up and restoring surface duly rammed.I) 4 core X 16 sq mm |
| 9 | II) 3.5 core X 50 sq mm |
| 10 | b) Laying of 1.1 KV grade XLPE insulated stranded alumunium conductor through microtunneling / pole / pipe / pillar boxes of the following sizes cables I) 4 core X 16 sq mm |
| 11 | Finishing the end of following XLPE cables by crimping method including supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials. I) 4 core X 16 sq mm |
| 12 | Finishing the end of following XLPE cables by crimping method including supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials. I) 3.5 core X 50 sq mm |
| 13 | Supply & erection of Pillar Box made 3mm sheet as per the dimension (1050X900X400)mm double lEachf inner and outdoor with hinge lolocking arrangement operated through lan key, including painting the same with one coat red oxide primer and two coat of superior quality of power coating paint and supply & fixing there in following items.a) 125 Amp 4P MCCB with sprEachder - 01 no.b) 100 Amp 4P MCB - 02 nos.c) 63 Amp 4P MCB - 02 nos.d) Analog GIC Timer - 01 no.e) 63Amp Contractor Units(ML4)-1 pc.f) Al. Bus bar size (0.8 Mtr.) - 3 X 50mm X 5mm + 1 x25mm x 5mm - 1 setg) Interconnection of above mentioned accessories with suitable size of HRFRLS PVC insulated stranded copper wire along with sockets, lugs, gasket & glands -01 set. \\" |
| 14 | Installation the feeder pillar box only on cement brick foundation including plastering and nEacht cementing as per specification and direction of E.I.C. For large size feeder pillar box\\" |
| 15 | Eachrthing with 50 mm dia G.I. pipe 3.64 mm thick x 3.04 mm mts long and 1 x 4 Swg G.I. (Hotdip) wire (4 mtr long) 13 mm dia x 80 mm long G.I. bolts, double nuts, double washers including S & F 15 mm dia G.I. pipe protection (1 meter long) to be filled with bitumen partly under the ground level and partly above ground level driven to and average depth of 3.65 mtr below the ground level & restoring surface duly rammed as below for feeder pillar box. (By TATA I- medium GI pipe ) |
| 16 | Supplying and fixing compression gland complete with brass gland , brass ring & rubber ring for dust & moisture -proof entry or XLPE armoured cables.i) 4 core x 16 sq.mm. |
| 17 | Supplying and fixing compression gland complete with brass gland , brass ring & rubber ring for dust & moisture -proof entry or XLPE armoured cables.i) 3.5 core x 50 sq.mm. Connecting the equipments body to earth busbar incl. S & F 50 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor with GI saddle as required and connection to equipments with incl. drilling holes, bolts, nuts,washers etc Please Enable Macros to View BoQ information |