| 1 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 2 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 3 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm |
| 4 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 X 2.5 sq. mm |
| 5 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings). |
| 7 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 8 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required (a)4 Module (125mmX75mm) |
| 9 | (b ) 6 Module (200mmX75mm) |
| 10 | (c) 8 Module (125mmX125mm) |
| 11 | (d)12 Module (200mmX150mm) |
| 12 | Supply & Fixing following modular switch/socket on the existing modular plate & switch box i/c connections but excluding modular plate etc.as reqd. (a)5/6 Amp.Switch |
| 13 | (b)15/16 Amp.Switch |
| 14 | (c)3 pin 5/6 Amp.Socket Outlet |
| 15 | (d)6 pin 15/16 Amp.Socket Outlet |
| 16 | Supply & Fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as reqd. |
| 17 | Supplying and fixing PVC batten/ angle holder including connections etc. as required. |
| 18 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator. 8 way, Double door |
| 19 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator.12 way, Double door |
| 20 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 21 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 22 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps |
| 23 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) . |
| 24 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required |
| 25 | Providing and fixing 6 SWG dia G.I wire on surface or in recess for loop earthing as required. |
| 26 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Upto 35 sq. mm |
| 27 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 28 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 29 | Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep |
| 30 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. Group C |
| 31 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.Group C |
| 32 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. 32 mm |
| 33 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*4 sqmm |
| 34 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*25 sqmm |
| 35 | Supply of 250 mm (10 inch) sweep 1250 rpm exhaust fan Fresh Air Type complete with shutter blades etc. as required. |
| 36 | P/F Hot press sheet moulded compound (SMC) fire retardant (Temp. resistance up to 200 C), IP 55 weather proof pole box of inner dimension 200x160x98mm (NS) complete with suitable arrangement for fixing of 2 nos of 6 to 32 amp single pole MCB & 63 Amp. Double pole isolator (MCB/Isolator excluded) with neutral link duly shorting on DIN Channel with2 Nos of MS clamps with SS back plate of suitable size with danger monogram property printed on the cover etc as reqd. as reqd. |
| 37 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥105 <120 lm/Watt). Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection,EMI-EMC as per CISPR -15, lenses for beamangle 30 deg-120deg as per the application and theproject requirement., suitable tilt able fitting, life time(LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumenmaintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K /4000°K / 5700°K /6500°K (As per ANSI Bin) ,SDCM(Standard Deviation Color Matching) <5,Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/cexternal connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductorsingle core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). .100 watt |
| 38 | LED Batten light (System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P.F.≥0.95, IP20, CRI >80, Flicker free (flicker shouldbe below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) .18-22 Watt |
| 39 | Repair/Rewinding of existing 1HP mono block pump set including replacement of parts like gun metal bush/ bearing condenser, impeller etc to make the pump functional as required. |
| 40 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.200Amp, 16 KA, TPMCCB |
| 41 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.100Amp, 16 KA, TPMCCB |
| 42 | supply and fixing of 4.5 KG DCP with CO2 gas cartridge fire extinguisher (conforming to IS:2171 with cylinder fully charged) |
| 43 | Providing and fixing ABC (Aluminium Phosphate) power type fire extinguisher of 6kgs capacity complete in all respect with isi mark i/c fixing arrangement etc asrequired. |
| 44 | Rewinding of AC ceiling fan of all sizes and make including oiling, greasing as required New Model (Light Weight). |
| 45 | Replacement of ball bearing of size 117/120 NBC equivalent SKF make as required. |
| 46 | Replacement of fan condenser 2.5 mF as required. |
| 47 | Supply, installation, testing and commissioning of cubical type control panel board for Single phase & Three phase submersible pumping set of following rating complete with contactor, relay, MCB, condenser, voltmeter, ammeter, and indication lamp etc including connections etc. as reqd.(a) 1.5 HP (Three Phase) |
| 48 | Supply of following size of PVC insulated & PVC sheathed copper conductor 3 core submersible cable conforming to IS . 694/210 etc. as rqd. 3×2.5 sqmm with voltage grade 1100 volts. |
| 49 | Lifting the existing submersible pump set with its all accessories from well and Lowering the same along with all accessories for the depth upto 50 meter complete as reqd. |
| 50 | Rewinding of single / three phase A.C.motors of vertical type multi stage submersible pump set of following ratings:-(a) Single phase 1/1.5 HP |
| 51 | Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth,metal enclosed plug top along with 20 amps "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. asrequired |
| 52 | Online UPS - Input supply: Single Phase, Output Supply : Single Phase Supplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) ON LINE Uninterrupted Power Supply (UPS) system suitable for Single Phase input, Single Phase output AC Supply. The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. The UPS systems shall be Microprocessor based Digital Control, using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter with PWM (Pulse Width Modulation) Technology. The quality of design, manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >95% at 100% non-linear loads. Current total harmonic distortion (ITHD)/ total demand distortion (TDD) on the input grid shall be < 5% at 100 %load. (The required LC filters shall be included in UPS cost), extreme power factor kit to be include to limit the input pf to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ) however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC single phase 160-270V 50 Hz and delivering output AC supplytrue sine wave single phase 220/230/240 Volt, 50 Hz +/- 0.2Hz, Overloadcapacity of 120% for 10 mins and 150% for 1 minute.Operating temperature 0 to 40 deg C, Relative humidity 0-95% noncondensing, noise level less than 60db at 1 meter distance, Protection forUnder voltage, over voltage, abnormal output voltage, battery over charging,output over current, short circuit, battery deep discharge , 10 KV surge.Display for watt/VA,Amp and Voltage power parameters etc. UPS shallcomply with low voltage electromagnetic compatibility (EMC) achieved asper EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and FrequencyIndependent (VFI) type UPS (as per standard IEC 62040-1, 2 & 3) . The UPSshould be with IGBT Based Inverter Technology, CommunicationRS232/RS485/SNMP port open protocol for BMS integration as perapproved by Engineering in charge. Required battery racks, DC breaker ofsuitable rating and interconnecting copper conductor cable of suitable sizeand connectors and all required accoseries are inclusive in the cost. TheUPS should have QR code which should contain drawing, test report OEMmanual, Geo- Tag of manufacturing location etc 3KVA |
| 53 | SITC of 4MP varifocal lens Bullet IP Camera with following specifications:-Image Sensor: 1/3 4MP CMOSMinimum Illumination: 0.05 lux color, 0 lux with IR or better **Shutter Speed:1/3 – 1/100,000 sFrame Rate: 20 fps or better **Lens: 3.6 to 10mm Varifocal lensVideo Compression: H.265 or better **S/N Ratio: >45dBResolution: (2650x1440) or better **Protocol: should comply to IPv4/v6, TCP/IP, HTTP, HTTPS, FTP, PPPoE,DDNS, IEEE802.1XIR Range: Minimum:30mOperating Temperature: -20 to 55 deg CentWeatherproof Standard: IP66 or better **Safety standard: UL |
| 54 | SITC of 4MP varifocal lens Dome IP Camera with following specifications:-Image Sensor: 1/3 4MP CMOSMinimum Illumination: 0.05 lux color, 0 lux with IR or better **Shutter Speed:1/3 – 1/100,000 sFrame Rate: 20 fps or better **Lens: 3.6 to 10mm Varifocal lensVideo Compression: H.265 or better **S/N Ratio: >45dBResolution: (2650x1440) or better **Protocol: should comply to IPv4/v6, TCP/IP, HTTP, HTTPS, FTP, PPPoE,DDNS, IEEE802.1XIR Range: Minimum 30mOperating Temperature: -20 to 50 deg CentWeatherproof Standard:IP66 or better **Safety standard: UL |
| 55 | SITC of 16 channel NVR with the following specifications:Camera resolution:upto8MPInterface: 1 HDMI, 1VGA minimumCompression :H.265or better**Network Throughput :160Mbps or better**USB Port: 2 USB port (USB2.0)minimumHard disk interface: 1 SATA port suitable for 6TB eachProtocol: IPv4/v6, TCP/IP, HTTP, HTTPS, FTP, PPPoE,DDNSOperating temp: -10 to 55 deg CentSafety standard: UL |
| 56 | SITC of 6 TB surveillance HDD |
| 57 | SITC of 8 port Giga PoE switch, 8(PoE 10/100) + 2(10/100) port long distance switch |
| 58 | SITC of following rack capacity with glass front door, steel rear door, power supply, MCB, cable manager, drawer shelves and wiring channels to accommodate CCTV systems equipment and complete with accessories as reqd.17 U |
| 59 | SITC of full HD LED Monitor,42 INCHES complying with the following specifications:Resolution : Full HD : 1920 x 1080 or betterBacklight : LEDBrightness : 300 NITS min.Contrast : 1200 : 1 or betterPower supply : 230v + / - 10%, 50 Hz at site with connections and along with all accessories etc. complete as required. |
| 60 | Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 23AWG Twisted 275 DELHI SCHEDULE OF RATES (E&M)-2025Pair Cable in existing conduit/ on surface, Category 6 Unshielded Twisted Pair, 4 pair should be complied as per UL/ETL verification program for compliance with ANSI/TIA-568.2-D standard. Outer diameter should be in the range of 6.1mm nominal with Operating Temperature Range : -5° to +60°C, Bending Radius : < 4 X Cable Diameter at –5°C ± 1°C and Pulling Force: 11.5Kg etc. complete as required. . 1 run of cable |
| 61 | 2 run of cable |
| 62 | SITC IP65 box (without PoE switches)of dimention 310mmX160mmX140 mm on pole or wall with suitable arrangement for support/installation of 8 port Giga PoE switch and 1 nos. 15/16 amp modular switch socket set |
| 63 | supply and fixing of 4.5 KG DCP with CO2 gas cartridge fire extinguisher (conforming to IS:2171 with cylinder fully charged) |
| 64 | Providing and fixing ABC (Aluminium Phosphate) power type fire extinguisher of 6kgs capacity complete in all respect with isi mark i/c fixing arrangement etc as required. |
| 65 | Supplying AND Installation of Reverse Osmosis (RO) water purifier of capacity 50 ltr/hr complete as required. |
| 66 | Supplying and fixing of full stainless steel body self-contained drinking water cooler with cooling capacity 150ltr per hr, storage capacity 150ltr and suitable for 230V supply as required. |
| 67 | Supply , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). Inverter Type - Cooling only ,1.5 TR with 5 Star BEE Rating |
| 68 | S/I/T/C of stand for split AC |
| 69 | S/I/T/C of copper pipe for split AC |
| 70 | S/I/T/C of drain pipe |
| 71 | S/I/T/C of 4 KVA Voltage Stabilizer having input voltage 150V-270V and output voltage 195-245V |
| 72 | S/I/T/C of 3 Core, 4 Sqmm. Electrical wire for Air Conditioner |
| 73 | SITC of metal clad, powder coated, compartmentalized cubical panel board as per CPWD electrical specifications including insulated aluminum bus bars, supports, interconnection, erection of switchgears with depth 30 cm to 60 cm and making provisions for termination of incoming/ outgoing cables/ bus ducting and making foundation etc as required. (Suitable for 400 Amp TP & N) Please Enable Macros to View BoQ information |