| 1 | Excavation in trenches in soft/loose soil not exceeding 1.5 mtr wide and not exeeding 1.5 m deep, getting out the excavated earth bottom surface to required gradient complete all as specified and directed. |
| 2 | Material and labour Removal of excavated material such as soils n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point. |
| 3 | Returning filling in, and including spreading and leveling in layers not exceeding 25 cm thick complete all as specified & directed. |
| 4 | Supply and spreading riddled earth for cushioning of the UG cable in trenches all as specified and as directed |
| 5 | Material and labour well burnt old size sub Class ‘B’ bricks, laid flat, in trenches for cable protection complete all as specified and as directed. |
| 6 | Supply , testing and commissioning in repair of XLPE insulated, armoured, heavy duty, 1100 Volts grade aluminium conductor cable Cross sectional area 16 Sqmm, 4 core in trenches or fixed to wall / passing through pipe / pole and testing vompete all as specified and directed Note : (i) Excavation & earth work, Brick protection and sand cushining shall be measured and paid for separately. |
| 7 | All as per serial item No. 6.00 here in before but cross sectional area of cable 3.5 core x 25 sqmm |
| 8 | All as per serial item No. 6.00 here in before but cross sectional area of cable 3.5 core x 35 sqmm |
| 9 | Material and labour for LT straight through joint kit 1100 volt out door type, of size upto 16 to 35 Sqmm 3.5 core complete all as specified and directed |
| 10 | Supply, esting and commisioning in repair of steel tubular swaged pole type 410 SP-31(9 mtr long) complete with CI base plate including 3 coat of bituminious paint for the embeded potion and two coats of aluminium over a coat of red oxide complete all as specified and directed |
| 11 | Supply ,testing and commisioning in repair of steel tubular swaged pole type 410 SP-64 (12 mtr long) complete with CI base plate including 3 coat of bituminious paint for the embeded potion and two coats of aluminium over a coat of red oxide complete all as specified and directed |
| 12 | Material and labour for cutting/trimming off the tree branches n. exc 30cm girth protruding/ touching both sides of the street light pole 3 mtr away on both sides of the over head conductor lines of any type on any height and clearing all the unserviceable material all as specified and directed |
| 13 | Supplying, Installation, Testing & Commissioning of Street light LED fixture, 50 watt powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI>70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the roadand the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) all as specified and directed |
| 14 | All as per serial item No. 13.00 here in before but 70 watt LED fitting. |
| 15 | All as per serial item No. 13.00 here in before but 100 watt LED fitting. |
| 16 | Supply and Fix as in repairs single Aviation lamp fitting complete LED type with housing cast aluminium base with red diffuse lens all as specified and as directed. |
| 17 | Supplying, Installation, Testing & Commissioning of Flood Light fitting 80 watt powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). complete all as specified and directed. |
| 18 | All as per serial item No. 17.00 here in before but 120 watt LED fitting. |
| 19 | All as per serial item No. 17.00 here in before but 150 watt LED fitting. Please Enable Macros to View BoQ information |
| 20 | All as per serial item No. 17.00 here in before but 150 watt LED fitting. Please Enable Macros to View BoQ information |