| 1 | M & L disconnecting and taking out old unserviceable damaged / burn out cable of any size & make and supplying, laying, jointing and testing LT under ground cable, heavy duty cable of size 10 Sqmm 4 Core, 1100 Volts, XLPE insulated and PVC sheathed, armoured, multi-stranded aluminium conductor cable conforming to IS , laid in trenches / ducts or fixed to poles / walls or laid under roads / paths / drains / culverts duly protected in galvanised steel pipe of suitable sizes all bare conductor of cable including cable gland and lugs etc at both ends incl disconnecting and taking out unserviceable damaged cable complete all as specified and directed by Engr - in -Charge. Note : Exc, earth work, cable sand cushioning & cable protection shall be measured separately under relevant items of this schedule. |
| 2 | All as per item No 1 here -in- before but 16 Sq mm, 4 Core |
| 3 | All as per item No 1 here -in- before but 25 Sq mm, 4 Core |
| 4 | All as per item No 1 here -in- before but 50 Sq mm, 3.5 Core |
| 5 | All as per item No 1 here -in- before but 95 Sqmm 3.5 Core |
| 6 | All as per item No 1 here -in- before but 120 Sqmm 3.5 Core |
| 7 | Excavation in trenches in hard/dense soil not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth and getting out excavated soil/sand/unseviceable LT Cable for laying of cable complete all as specified and directed. |
| 8 | Excavation in trenches in hard / dense soil n exc 1.5 metre wide but exc 1.5m but n.exc 3.0m deep and getting out including forming bottom surface for laying UG cable, foundation for poles etc complete all as specified and directed. |
| 9 | Returning filling in including spreading levelling watering and well ramming in layers not exceeding 25 cm in hard /loose soil complete all as specified and directed. |
| 10 | Removing excavated material not exceeding 50mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 11 | Supply and laying in trenches fixed to poles wall laid in floor GI steel tubing 80mm bore (dia) light grade including fitting bolt, nut & washers etc or wooden rubber bushing at the ends incl disconnection and taking down existing tubing complete all as specified and directed. |
| 12 | All as per item No.06 above but 40mm bore (dia) pipe light grade |
| 13 | Supply , Installed testing and commissioning steel Tubular swan neck poles 8 mtr long ( 1.5 mtr below ground level and 6.5 mte above the ground level) shall be swaged type high strength, galvanized, painted lighting / utility pole constructed by joining steel pipes of decreasing diameters, Finials and base plate shall be of cast iron typically used for street lighting or highway, it features a tapered multi section design with 8 mtr options often designed for high wind load and longevity. Protection Against Corrosion The poles shall be coated with two coats of silver paint throughout internally, and externally up to the planting depth complete with CI base plate and finial taper plug, bolts, nuts & screws complete all as specified and directed. |
| 14 | M&L for PCC 1:3:6 type C-1 using 20mm graded aggregate as in coping including necessary form work complete all as specified & directed. |
| 15 | M & L for PCC 1:2:4 type B-1 using 20mm graded aggregate for coping to pole foundation including necessary form work with fair finished surface complete all as specified and directed. |
| 16 | M & L for PCC 1 : 4 : 8 type D-2 using 40 mm graded stone aggregate for pole foundation, filling and mass concrete complete all as specified and directed. |
| 17 | M & L for earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6mm thick buried directly in ground [earth pit not less than 2.25 metre deep below normal ground level] with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanized iron earth strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No. 3 of MES SSR Part I all as specified and testing on completion including provision of earth lead protected by 50 mm dia light grade GI pipe & watering pipe shall be 20 mm bore medium grade GI pipe including all excavation and earth work, PCC pit with RCC cover, char coal, salt, funnel etc complete all as specified and directed.. Note:- Rate quoted by tenderers shall be deemed to include for following provisions-[i]. Excavation & earth work in any type of soil including removing of surplus material upto 50 m. [ii].PCC 1:3:6 type C-1 using 20mm graded stone aggregate in pit & 40mm thick precast RCC 1:2:4 type B-1 cover 50x50cm with 8mm TMT bars @ 10 cm C/C both ways with handles.[iii]. Main earthing lead from earth electrode to test point upto 7.5 mtr.[iv]. Funnel with watering pipe [GI pipe] 20mm bore medium grade and charcoal & salt around earth plate in alternate layers of 15 cm [v]. GI protection pipe of size 50 mm bore light grade upto 7.5 m. |
| 18 | M&L for earthing complete with galvanised earth plate electrode 600mm x 600mmx 6mm thick buried directly in ground vertically (earth pit of depth not less than 2.25m below ground level ) with top edge of the earth plate not less than 1.5m below normal ground level, connecting with 4.00 mm dia galvanized steel wire earth lead by means of bolts, nuts, checks nut and washers made out of galvanized iron and earth wire protected by galvanized steel pipe 15mm dia (light grade) including provn of concrete pit in PCC 1:2:4 type B-1 (using 20 mm graded mechanically crushed stone aggregate), 40mm thick RCC cover slab 1:2:4 tpye B-1 reinforced with XPM ( weight not less than 4kg/sqm ) and frame made of angle iron of section 40x40x6mm with lugs, 02 Nos handle of 6mm dia mild steel bar made to shape, 20mm dia GI pipe (Med grade) for watering perforated at bottom 1.75m long placed on top edge of earth plate, charcoal and salt filling in alternate layer, test point made out of phopsphorus/ Bronze with fixing arrangement , funnel wire mesh and earth work in soft/loose soil, returning filling, removal of surplus soil all as shown in electrical plate No.3 of SSR Part-I and connection to earth test point including testing on completion complete all as specified and directed.Note : Item of earthing include cost of 7.5m long GI earth wire 4mm dia, earth work in any type soil, returning filling and removal, GI protection pipe, GI watering pipe, funnel, wire wesh, RCC cover, etc . |
| 19 | S&F in replacement LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed. |
| 20 | S&F in replacement LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed. |
| 21 | S&F in replacement LED flood light fitting 210 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 66 protection complete all as specified and directed. |
| 22 | S & F GI bracket for security lights made out of medium grade GI Pipe 40mm dia, 1.5 mtr long bend to shape as directed, fixed on walls with two Nos MS clamp/saddles as required at site including nuts, bolts and washers complete all as specified and directed. |
| 23 | S & F in replacement MCCB 4 Pole, 400 Amps, 36 KA, 415 V , with ICS=100% ICU, adjustable thermal-0.8-1IN, adjustable magnetic-5 to 10IN, With Option for in Built or Add on Module for ELM complete all as specified and directed. |
| 24 | All as per item No.18 here in above but MCCB 4 Pole, 350 Amps, 36 KA, 415 V |
| 25 | All as per item No.18 here in above but, MCCB 4 Pole 250 Amps, 36 KA, 415 V. |
| 26 | All as per item No.18 here in above but MCCB 4 Pole, 200 Amps, 25 KA, 415 V |
| 27 | All as per item No.18 here in above but MCCB 4 Pole, 160 Amps, 25 KA, 415 V |
| 28 | All as per item No.18 here in above but MCCB 4 Pole, 125 Amps, 25 KA, 415 V |
| 29 | All as per item No.18 here in above but MCCB 4 Pole, 100 Amps, 25 KA, 415 V |
| 30 | All as per item No.18 here in above but MCCB 4 Pole, 63 Amps, 16 KA, 415 V |
| 31 | S&F in replacement LT junction box for street light, sheet moulding compound (SMC) type with hinged type door and locking arrangement, off white colour, of size 300 x 200 x 105mm (internal) comprising of suitable size Aluminium busbar 3 rows with terminals,1 No bakelite base neutral link and 01 No earthing terminal bolt and nut and connecting up cables with aluminium terminal lugs complete all as specified and directed. |
| 32 | M & L for painting to steel pole any type after scrapping and rubbing down with sand paper preparation of old or new surface of poles including pole fittings such as cross arms of any description, anti-climbing devices, nut, bolts etc.and applying two coats of aluminum paint including numbering of poles as per existing complete all as directed and making 5 Nos of alternative strips of black, yellow paint of 30 Cm wide complete all as directed. |
| 33 | M & L for drawing of 3 core 1.5 Sqmm copper conductor cable in existing pole incl making holes for cable entry and exist near to light fitting and junction box complete all as specified and directed. |
| 34 | Supply and laying of DWC Outer dia of 90 mm and inner dia 76 mm (double Wall corrugated) HDPE polyethiline pipe ISI marked including couplers, bends, cap etc. with smooth internal and profiled external surface for non pressure under ground cablecomplete all as specified and directed. |
| 35 | All as per item No.29 here -in- before but Outer dia of pipe 120 mm and inner dia 103.5 mm |
| 36 | Cutting existing road / hardstanding of any type by using crow bar chisel upto a depth of 30 cm for laying GI pipe including making good the surface by returning filling watering ramming in layers 150 mm thick PCC 1:2:4 over 200 mm thick hard core of broken bricks / stones over returning filling watering ramming in layers not exceeding 25 cm thick complete all as specified and directed. |
| 37 | M & L for LT straight through joint for under ground cable incl jointing kits for the following sizes :- |
| 38 | Cable upto 50 sqmm 3.5/4 core |
| 39 | Cable 70 to 120 sqmm 3.5/4 core |
| 40 | Cable 150 to 185 sqmm 3.5/4 core |
| 41 | Cable 240 to 300 sqmm 3.5/4 core |
| 42 | M & L for Aluminium Lugs of size 16-35 sqmm complete all as per specified and directed. |
| 43 | M & L for Aluminium Lugs of size 50-95 sqmm complete all as per specified and directed. |
| 44 | M & L for Aluminium Lugs of size 120-240 sqmm complete all as per specified and directed. |
| 45 | M & L for Aluminium Lugs of size 240-400 sqmm complete all as per specified and directed. |
| 46 | Supply, installation, commisioning and testing of automatic street light control system of 25A suitable for automatic switching of Street lights of 240V, 50Hz, Controller shall have following function -(a) Controller shall be automatically switch on the street lights as programmed time setting and astro function. (b) Controller shall be automatically switch off the street lights as programmed time setting and astro function. Following Components shall be fitted in a enclosure, wired and programmed for complete function. 1 No. 25A, 4pole MCB in thermal magnetic release for overload and shortcircuit protection. 1 Nos 3 position (auto - off- manual) 25A, 4pole modlar type contactors. Phase indication Lamps R+Y+B 230/400V, Astonomical time switch of Switching Capacity 16A, ohmic 250V AC, at PF-1, having minimum running reserve 5 years/43800 hours and clock precision 0.1sec./day, having facility of location programing by city name or geographical coordinates , off set time + /- 120 minute relative to sunrise/sunset. |
| 47 | Taking down existing connection from LT Panel/Bus Bar Chamber/Feeder Pillar/ Electric Poles/ Building carefully (any capacity and any type) carrying out repair work at site including replacement of unserviceable/ defective screw/nut & bolts/ Washers/Lugs/ Spreaders/Hinges of doors/ Repair to Locks & handles/ Indication Lamps/meters/Cable glands/Bus Bar (Copper/Aluminium) etc, refixing the fittings in its original position, testing and commissioning, including removal of bushes, creapers and trimming of branches around the LT Panel/Bus Bar Chamber/Feeder Piller/ Electric Poles including takingout and fixing at site complete all as specified and directed . Note: (i) If any major repair is required, attending complaints and replacement of any nature in LT Power network at any point and time, the items shall be replaced with respective item of sch 'A' is deemed to be inclusive (ii) Tools, ladder, vehicle required to carry out the work shall be provided by the contractor. (iii) Contractor will ensure the safety of the workers employed at his own risk. (iv) Contractor shall provided Skilled ITI Electrician and Produce the Certificate before the commencement of work. (v) Contractor should ensure to rendering completion of all attended complaints to respective JEs/Engr-in Charge as day to day basis . (vi) Necessary photagraph to be taken while execution of said items. |
| 48 | Supply, Installation, commissioning & testing of factory made ,any CPRI approved ,LT switched gear panel board,IP-54(outdoor type) ,415 volts,50 Hz,AC supply,three phase and neutral (4 wire) ,suitable Amps aluminium busbars 4 pole ,duly insulted with heat shrinkable sleeve as per colour code supported on epoxy insulatators,having independent compartment for insulated busbar ,incoming feeder & each outgoing feeder ie cubical type ,made out of 3.15 mm thick CRCA sheet,rigid mild steel angle iron frame of 50mmx50mmx6mm with 900mm long extended legs grouting in PCC 1:3:6 type C2 block of size 300mmx200mmx300mm ,duly epoxy powder coated internally & externally with approved shade ,rubber gasket,hinged front & back openable doors with proper locking arrangements for dust and vermin proof ,complete including suitable size cable alley,lugs,cable glands,common earth bar of GI strip 32x6mm at bottom and making connections with MCCB with cable chamber for individual feeders for incomming and outgoing connections, one set of LED indicator lamp RYB with switch and fuse and the panel board shall be provided with proper ventillation including suitable size of cable alley copper bus bar suitable for carrying of Aluminium suitable bus bar suitable Amps rating , 3 Nos for phases and one No for neutra with suitable connections from MCCB out going to main bus bar shall be carried out with TPN copper bus bars of suitable rating and connections from main bus bar to out going MCCB's (intake point) will be carried out with TPN copper bus bar as per MCCB rating duly insulated all MCCB with ICS=100% ICU, adjustable thermal-0.8-1IN, adjustable magnetic-5 to 10IN, With Option for in Built or Add on Module for ELM with spreader link and colour coded heat shrinkable sleeve and shall be rigidly mounted on suitable size of bridge insulator including necessary PCC foundation of minimum 0.35 m height positioned and fixed with suitable nut, bolts, washers etc to the MC pedestal all as specified and directed comprising of the following :-Incomer :- MCCB 250 Amps 4P, 36 KA - 01 Nos.Meter set : Digital voltmeter,Ammeter + CT : 400/5,RYB Indicating Lamp LED type 240 V ,MCB SP 6A, KWH Meter : CT/PT operated Trivector Energy with TOD Meter,3 Phase 4 wire for measuring of LT Instanteneous & Intigrating Parameters with bright LCD Display Outgoing :-MCCB 63 Amps 4P, 36 KA - 06 Nos.Astronomical timer switch 25 A with contactor - 01 Nos |
| 49 | S & F Aluminium strip 25 x 3 mm fixed with Epoxy heavy duty type insulator and earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing , aluminium strip with saddles / insulators at 50cm distance, roof conductors and down conductors above ground complete all as specified and as directed. |
| 50 | S & F GI strip 32 x 6 mm fixed with Epoxy heavy duty type insulator and earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing , aluminium strip with sadles/ insulators at 50cm distance, for roof conductors and down conductors above ground complete all as specified and as directed. |
| 51 | S&F in replacement air termination single pointed aluminium rod 12mm dia and 300mm long complete all as specified and directed. |
| 52 | S & F test point terminal block made of gun metal or phosphhorus bronze size 75x75x25mm, drilled and screwed including 3 Nos, 8mm dia 25mm long hexagonal head brass screws including suitable sheet metal powder coated enclosure complete all as specified and as directed. |
| 53 | S&F galvanised iron tubing, medium grade, 40 mm bore, for lighting protection rod fixing on roof with plain cement concrete 1:2:4 type B-1 using 20 mm graded stone aggregate, complete all as specified and as directed.Note:- PCC shall be measured and paid seperately under respective item. |
| 54 | M & L for PCC 1:2:4 type B-1 (using 20 mm graded stone aggregate) in foundation of pipe supports/platform etc. including necessary form work complete all as specified and as directed. |
| 55 | S & F Rolled mild steel Joist, channel, angle, or tee sections, fixed independently, without connecting plates, etc. (cut to ordinary lenghts i.e. within 20mm of the length indicated) GDE Fe 410-0 W (Gde E-250) quality B complete all as specified and as directed. |
| 56 | S & F junction fitting for Aluminium/copper strip at junction of strip complete all as specified and directed. |
| 57 | S & F baby insulators for Aluminium/copper strip at 50cm distance, roof conductor and down conductor above ground complete all as specified and directed. |
| 58 | S & F Lighting arrester studds for Aluminium/copper strips complete all as specified and directed. |
| 59 | Taking down carefully existing aluminum/copper surface/concealed point wiring (light, fan, socket or power point) complete of any description including fitting such as switches, ceiling roses, lamp holder, regulators, sockets, wooden boards, laminated sheets from sunken boxes, boards, shades light fitting etc and making good the disturbed surfaces in CM 1:3 of walls, floors, ceiling etc including painting if required to match up with existing surfaces complete all as specified and directed. Please Enable Macros to View BoQ information |
| 60 | Taking down carefully existing aluminum/copper surface/concealed point wiring (light, fan, socket or power point) complete of any description including fitting such as switches, ceiling roses, lamp holder, regulators, sockets, wooden boards, laminated sheets from sunken boxes, boards, shades light fitting etc and making good the disturbed surfaces in CM 1:3 of walls, floors, ceiling etc including painting if required to match up with existing surfaces complete all as specified and directed. Please Enable Macros to View BoQ information |