| 1 | OPD, PTD - Supply and Installation |
| 2 | Hydrocarbon Detection system: Supply of Flameproof cum weather proof(IP 66 or better) min SIL 2 certified Hydrocarbon vapour detectors along with test filter,calibration kit, accessories and structural supports, canopy/sunshade etc as per specification and tender document. |
| 3 | Point type Infrared detector (Indicative location: Ethanol Dyke- 2 nos, Pump House Manifold- 2 nos, Exchange Pit- 1no) |
| 4 | Open path type Infrared detector (0-90m) along with alignment telescope, configuration & testing kit etc (Tentative location: Ethanol Dyke- 1no.) |
| 5 | Supply of weather proof and Explosion proof Hooter cum beacons/ flash light along with accessories and structural supports as per specification. ( Tentative location : Ethanol Dyke- 3 nos, Pump House Manifold- 2 nos, Exchange Pit- 1no) |
| 6 | Installation, integration, Calibration, Testing, and Commissioning Flameproof cum weather proof (IP 66 or better) min SIL 2 certified Hydrocarbon gas detectors along with calibration kit, accessories and structural supports etc as per specification and tender document. |
| 7 | Point type Infrared detector (Indicative location: Ethanol Dyke- 2 nos, Pump House Manifold- 2 nos, Exchange Pit- 1no) |
| 8 | Open path type Infrared detector (0-90m) along with alignment telescope, configuration & testing kit etc (Tentative location: Ethanol Dyke- 2no.) |
| 9 | Installation, testing and commissioning of weather proof and Explosion proof Hooter cum beacons/ flash light along with accessoriesand structural supports as per specification. ( Tentative location : Ethanol Dyke- 3 nos, Pump House Manifold- 2 nos, Exchange Pit- 1no) |
| 10 | Cabling Works for OPD, PTD, HVLR |
| 11 | Cabling, JB, Earthing:Note: Supply of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc |
| 12 | Supply of FRLS Armoured Copper Signal cable as per tender specifications. |
| 13 | 6P x 1.5 sqmm |
| 14 | 8P x 1.5 sqmm |
| 15 | 8T x 1.5 sqmm |
| 16 | Supply of FS Armoured Copper Signal cable as per tender specifications. |
| 17 | 1T x 1.5 sqmm |
| 18 | Supply of FRLS Armoured Copper Control cable as per tender specifications. |
| 19 | 2C x 1.5 sqmm |
| 20 | 12C x 1.5 sqmm |
| 21 | 16C x 1.5 sqmm |
| 22 | Cabling, JB, Earthing:Note: Laying, glanding, ferruling, termination of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners, OFC accessories (like12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc |
| 23 | Laying, glanding, ferruling, termination of FRLS Armoured Copper Signal cable as per tender specifications. |
| 24 | 6P x 1.5 sqmm |
| 25 | 8P x 1.5 sqmm |
| 26 | 8T x 1.5 sqmm |
| 27 | Laying, glanding, ferruling, termination of FS Armoured Copper Signal cable as per tender specifications. |
| 28 | 1T x 1.5 sqmm |
| 29 | Laying, glanding, ferruling, termination of FRLS Armoured Copper Control cable as per tender specifications. |
| 30 | 2C x 1.5 sqmm |
| 31 | 12C x 1.5 sqmm |
| 32 | 16C x 1.5 sqmm |
| 33 | Supply of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. |
| 34 | 6 ways JB |
| 35 | 12 ways JB |
| 36 | 18 ways JB |
| 37 | Installation of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. |
| 38 | 6 ways JB |
| 39 | 12 ways JB |
| 40 | 18 ways JB |
| 41 | Supply of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as perspecification and tender document |
| 42 | Laying, glanding, ferruling, termination of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document |
| 43 | Supply of GI strip ( 50mm X 6mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. |
| 44 | Fabrication, cutting, laying and connecting of GI strip ( 50mm X 6mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. |
| 45 | Supply of anodized Aluminium perforated cable trays (2.5mm Thick and 25mm edge height), tray covers (1.5mm Thick and 10 mm edge height) along with structural steel for mounting of the cable tray. Complete as per specifications / tender documents. |
| 46 | 150 mm |
| 47 | 100 mm |
| 48 | Laying of anodized Aluminium perforated cable trays (2.5mm Thick and 25mm edge height), tray covers (1.5mm Thick and 10 mm edge height) along with structural steel for mounting of the cable tray. Complete as per specifications / tender documents. |
| 49 | 150 mm |
| 50 | 100 mm |
| 51 | \\"PIPE ELECTRODE EARTH PITSupply, installation & testing of earth electrode with following sizes: 80 mm dia, 3.8 M long heavy duty perforated GI pipe electrode (Galvanisation is 610 gms/sq. mtr or as per IS-4759/ISO ONLY 1461.) as per IS:3043 providing suitable earth bus for interconnection, providing a mixture of salt & charcoal, making RCC/ Brick earth pit chamber and associated civil works with chequered plate cover as per standard Drwng. etc. all complete as per specification & direction of Site-In-charge.Item also includes Supply and fixing of Earth resistance display board of size 450 X 300 mm with 3mm thick Aluminium Composite Material (ACM)/ Aluminium Composite Panel (ACP) bolted to 25 X 25 X 5 mm (with 2 bolts MS angle section, 60 cm long (minmum 200 mm embedded in ground). The rate shall also include supply and pasting of UV resistant vinyl sticker having details as per Site-in-charge.\\" |
| 52 | CIVIL Works |
| 53 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30 cm in depth, 1.5m in width as well as 10 sqm on plan) including taking out and disposal of excavated earth within or outside site to unobjectionable place and lift upto 1.5m, as directed by Engineer-in-charge. Disposed earth to be levelled and neatly dressed. Extra for levelling & neatly dressing of disposed soil completely to be paid separately as per item no. MPLCN00600 |
| 54 | i) All kinds of Soil |
| 55 | Excavating trenches of required width for pipes, cables etc including excavation for sockets & dressing of sides, ramming of bottoms,depth upto 1.5m including taking out excavated soil & then returning the soil as required, in layers not exceeding 20 cm in depth including consolidating each deposited layer by ramming, watering, etc. and disposing surplus excavated soil as directed, within or outside site at unobjectionable place in all kinds of soil |
| 56 | i) Pipes,cables etc. not exceeding 80mm dia |
| 57 | Clearing grass and removal of the rubbish outside site premises and at an unobjectionable place. |
| 58 | Providing and laying in position cement concrete of specified grade excluding cost of centering & shuttering. All work up to plinth level: |
| 59 | iv) 1:2:4(1 Cement : 2 Coarse Sand :4 Graded stone aggregate of 40mm) |
| 60 | viii) 1:4:8(1 Cement :4 Coarse Sand :8 Graded stone aggregate of 40mm) Please Enable Macros to View BoQ information |