| 1 | S/E of Terminal Gantry of R.S. Joist-175x85 mm 19.5 Kg/Mtr. 6.1 Mtr. above the ground and 1:3:6 cement concrete foundation mounted on a stone pad of 300x300x75 mm complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. |
| 2 | S/E of erection of 33 KV line Isolator suitable 1250 Amp. with structure & foundation complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. |
| 3 | S/E of erection of 33 KV Bus Isolator suitable 1250 Amp. with structure & foundation complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. |
| 4 | Supply, Errection, testing & Commissioning of 33 KV VCB,1250A 750 MVA Motorized auto spring charge system complete with Mounting structure,Outdoor CT-400/200/100/1A, 0.2 Class with structure and foundation , 33 KV Outdoor PT 33KV/11V with structure and foundation work complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. |
| 5 | S/E of Bus Bar gantry structure of 105 Lbs/Rail Pole 6.5 Meter long 5.2 Meter above in ground level including cost of material, foundation etc. complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. (All drawing preparation & approval shall be done by Contractors at its own cost from DVVNL/Electrical saftey of U.P |
| 6 | S/E of 33 KV lighting arrestors set with structure made of MS channel 125x65 mm 3.1 Kg./M top of MS angle 50x50x6 mm, 4.5 Kg/M Lighting Arrestor (one set of lighting arrestor shall be installed on gantry) complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. |
| 7 | Supply, Errection, testing & Commissioning of outdoor type with copper wound 33/11KV , 10 MVA Transformer with off load tap changer as per DVVNL with following provisions.(a) Cable termination box with disconnecting facility for 33 KV XLPE cable outdoor arrangement with 33 KV bushings at 33 KV side. (b) Cable termination box with disconnecting facility with 11 KV bushings for 11 KV XLPE cable at 11 KV side. (c) Off load tap changer +5% to -15% @ 2.5% (d) Bi directional roller (e) Conservator with drain valve & sump value. (f) Earthing terminals (Two) (g) Double diaphram explosion vent (h) Radiator with top & bottom shut of valve (i) First filling of oil including makeup fill (j) Silica gel breather with oil seal (k) Rating and Diagram plate (l) Air release plug (m) Buchholz relay with shut off valves on both sides.(n) Winding temperature Indicator (WTI) (o) Oil Temperature indicator (OTI) (p) Magnetic oil level gauge (q) Pressure relief device (r) Marshalling Box (s) Tap position indicator (t) Marking plate for OLTC (u) Terminal marking plate (v) Drain valve with plug & locking arrangement (w) Filter valve (x) Oil sampling Valves (03 nos) as per latest technical specification of DVVNL approved by Engineer in charge. |
| 8 | Supply & fixing 33 KV Pin Insulator with pin on main terminal gantry including cost of material, men and T&P. |
| 9 | S/F of 33 KV insulator string having 4 nos of 11 KV B&S type strain disc insulators 120 KN E&M strength & 33 KV tension fitting complete in all respects as per latest technical specification of DVVNL approved by Engineer in charge. |
| 10 | S/F of P.G. Clamp suitable for panther conductor for jumpring complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. |
| 11 | Construction of 33 KV transformer plinth suitable for 33/11KV transformer (1x10 MVA) as per drawing with 90 lbs rail Pcs.(44.64 kg/m), all material, labour and T&P as per latest technical specification of DVVNL approved by Engineer in charge. |
| 12 | S/B of 40 mm dia x 4.5 mtr. long G.I. pipe vertically for earthing having 12 mm dia. Holes spaced 75 mm apart drilled upto 2 mtr. from the bottom complete with earthing lead of no.6 to 8 SWG GI wire in G.I.pipe upto appron upto switch board 30 cm square box with hinged cover masonary enclosure. Funnel of top, alternate layers of charcoal and salt at least 150 mm thick alround etc. as per direction E/I complete in all respect as per drawing. |
| 13 | S/F of 50x6 mm GI strip from earth electrode directly complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. |
| 14 | S/F of 33 KV Post insulator set or 2x22 KV of approved quality complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. |
| 15 | Supply, Fixing, installation, testing & Commissioning of 11 KV Incoming VCB Panel with 1250 Amp., 350 MVA, 600/300/5 Amp. CT ratio, PT & associated material and 04 nos 11 KV Outgoing VCB Panel of 800 AMP., 350 MVA, 400/200/5 Amp. as per latest approved vender list of DVVNL and as per latest technical specification of DVVNL/Approved by Engineer in charge.The bus bar and connectors should be made from copper with proper cross section area, tinned and insulated properly with HT insulation compound/sleeves.(Incoming VCB Panel 1250A,350 MVA, CTR-600/300/5A along with PT - 01 nos+Outgoing VCB Panel A,350 MVA, CTR-400/200/5A - 04 nos or (All Specification as per DVVNL or subject to revised by E/I) |
| 16 | Supply, Fixing, installation, testing & Commissioning of 11 KV Outgoing VCB Panel of 800 AMP., 350 MVA, 400/200/5 Amp. as per latest technical specification of DVVNL/Approved by Engineer in charge.The bus bar and connectors should be made from copper with proper cross section area, tinned and insulated properly with HT insulation compound/sleeves. (All Specification as per DVVNL or subject to revised by E/I) |
| 17 | S/L of 300 sq. mm, 3 core 11 KV XLPE cable ( cross linked polyethylene)insulated PVC bedded Galvanised flat steel strip armoured cableconfirming to I.S.7098 (Part-II with latest amendments) 11 KV grade in depth of 750 mm below ground level over a cushion of 100 mm thick find river sand alround andprotected with well burnt bricks onsides and on top put across The armouring of cable shall be properly connected with earth conductor by clamps as per latest technical specification of DVVNL approved by Engineer in charge. (Glostar, Grandlay, Havells, Polycab,KEI make) |
| 18 | Supply & fixing of 11 KV indoor type heat shrinkable Jointing kit suitable for 3x300 sq.mm XLPE Cable after carefully removing the insulation of the cable duly plumbing and taping of cable providing, fixing and crimpling of proper size good quality lugs and complete work including cost of material such as insulating tapes, cotton tape, plumbing material and lugs etc.S/F of complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. |
| 19 | Supply & fixing of 11 KV Outdoor type heat shrinkable Jointing kit suitable for 3x300 sq.mm XLPE Cable after carefully removing the insulation of the cable duly plumbing and taping of cable providing, fixing and crimpling of proper size good quality lugs and complete work including cost of material such as insulating tapes, cotton tape, plumbing material and lugs etc.S/F of complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. |
| 20 | S/L of 185 sq. mm, 3 core 11 KV XLPE cable ( cross linked polyethylene)insulated PVC bedded Galvanised flat steel strip armoured cableconfirming to I.S.7098 (Part-II with latest amendments) 11 KV grade in depth of 750 mm below ground level over a cushion of 100 mm thick find river sand alround andprotected with well burnt bricks onsides and on top put across The armouring of cable shall be properly connected with earth conductor by clamps as per latest technical specification of DVVNL approved by Engineer in charge. (Glostar, Grandlay, Havells, Polycab ,KEI make) |
| 21 | Supply & fixing of 11 KV indoor type heat shrinkable Jointing kit suitable for 3x185 sq.mm XLPE Cable after carefully removing the insulation of the cable duly plumbing and taping of cable providing, fixing and crimpling of proper size good quality lugs and complete work including cost of material such as insulating tapes, cotton tape, plumbing material and lugs etc.S/F of complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. (indoor side for spare cable) |
| 22 | Supply & fixing of 11 KV Outdoor type heat shrinkable Jointing kit suitable for 3x185 sq.mm XLPE Cable after carefully removing the insulation of the cable duly plumbing and taping of cable providing, fixing and crimpling of proper size good quality lugs and complete work including cost of material such as insulating tapes, cotton tape, plumbing material and lugs etc.S/F of complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. |
| 23 | S/L of 70 sq. mm, 3 core 11 KV XLPE cable ( cross linked polyethylene)insulated PVC bedded Galvanised flat steel strip armoured cableconfirming to I.S.7098 (Part-II with latest amendments) 11 KV grade ata depth of 900 mm below groundlevel over a cushion of 100 mmthick find river sand alround andprotected with well burnt bricks onsides and on top put across Thearmouring of cable shall be properly connected with earth conductor by clamps etc. complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. (Glostar, Grandlay, Havells, Polycab, KEI make) |
| 24 | S/F of Jointing kit 70 sq. mm indoor type 11 KV heat shrinkable type complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. |
| 25 | S/F of Jointing kit 70 sq. mm outdoor type 11 KV heat shrinkable type complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. |
| 26 | Supply and laying of 70 sq. mm 3.5 core aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 27 | S/F of brass nickel plated compression gland 70mm x 3.5 core. |
| 28 | Supply & fixing of lugs suitable for 70 sq. mm |
| 29 | Supply and burying of 600mm x 600mm x 6mm G.I. plate vertically for earthing with its top at least 3 metres below ground level complete with 20mm dia G.I. pipe and funnel for watering and one earthing lead of one no. 8 to 10 SWG GI wire in 15mm dia G.I. pipe up to switch board (from appron to switch board the cost of G.I. pipe and G.I. wire will be extra) 30cm square C.I. frame with hinged cover masonry housing alternate layers of charcoal/coke and salt at least 150mm thick alround etc. as per directions of Engineer-in-charge complete in all respects as per drawing (This will apply for earthing of poles also). |
| 30 | S/filling of 20 mm stone grit in yard of size 26x36 Mtr. 75 mm thick complete in all respects as per direction of E/I. |
| 31 | S/F of 100 mm dia GI Pipe \\"B\\" class for protection of cable on pole complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. |
| 32 | Earthing of sub station by supply,fabricating and laying of earth mat in the switch yard of the sub-station for all Electrical Equipments and structure(indoor & outdoor) by laying of M.S. rod of 32 mm in 750 mm deep trenches and earth electrode 3 Mtr. long MS round bar 32 mm dia 0.5 Mtr. below ground level and cutting,straightening, bending laying of MS flat of size 50x6mm(below and above ground) as per detail specification of DVVNL complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge.(All drawing preparation & approval shall be done by Contractors at its own cost from DVVNL/Electrical saftey of U.P |
| 33 | Painting of terminal gentry, lighting arrestor, Busbar gentry, line isolator & Bus isolator structures, post insulator, fencing, Poles and other structure complete in all respects as per latest technical specification of DVVNL approved by Engineer in charge. |
| 34 | Supply, installation, testing & Commissioning of float cum boost battery charger 24V/40 Amp, 230V+-10% 1 phase 50 Hz along with 24Volt battery set on acid resistant stand and DC Distribution system as per latest technical specification of DVVNL approved by Engineer in charge. |
| 35 | S/E of Straight MS Channel 50x100 mm 2.5 Mtr. long with clamp complete in all respect. |
| 36 | Supply and laying of 1800mm x 900mm x 12mm thick chequered rubbbber matting of tested quality. |
| 37 | S/F of 11 KV TPMO with polymer insulator complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. As per uppcl stock issue 24-25 |
| 38 | S/F of outdoor type 11 KV fuse set with insulator complete in all respect as per as per latest technical specification of DVVNL approved by Engineer in charge. As per uppcl stock issue 24-25 |
| 39 | S/L of Control Cable for metering complete as per technical specification/GTP approved by Engineer in charge. (2.5 sq. mm, 2 core copper) as per latest technical specification of DVVNL approved by Engineer in charge. (Grandlay, Havells,Polycab, Gloster, KEI) make . |
| 40 | S/L of Control Cable for metering complete as per technical specification/GTP approved by Engineer in charge. (2.5 sq. mm, 4 core copper) as per latest technical specification of DVVNL approved by Engineer in charge.(Grandlay, Havells, polycab, Gloster, KEI make.) |
| 41 | S/L of Control Cable for metering complete as per technical specification/GTP approved by Engineer in charge. (2.5 sq. mm, 10 core copper) as per latest technical specification of DVVNL approved by Engineer in charge. (Grandlay, Havells,polycab, Gloster,KEI) make. |
| 42 | Supply,installation,testing & commissiong of 3.96 MVAr Capacitor Bank as per latest technical specification of DVVNL approved by Engineer in charge. |
| 43 | Supply and erection double pole structure consisting of steel tubular pole 410-SP-56 11M long. complete with 1/6th of overall length of pole below ground level with 45cm dia cement concrete with 45cm above the ground leval. The foundation of underground will not be less than 20cm thick layers of cement concrete in the ration of 1:3:6 (Cement : coarse sand : over burnt brick ballast/stone ballast), The brick ballast/stone ballast will be used of 1.25cm size with stone pad of 30x30x7.5cm at the base. as per direction of E/I of work/site including all T&P, men and material for proper completion of work . ( The Pole Should be galvanized upto approved level as per technical specification of DVVNL.) |
| 44 | Fabrication and grouting of Neutral support Structure M.S Channel 100x50x6mm in L shape & in proper size andalignment to provide support for the two separate earthing strips for power transformer neutral including supply and fixing of two nos Flexible copper bonds for neutral ear thing. |
| 45 | Fabrication & erection outdoor Copper Bus Bar for 11 KV side (R,Y,B phase) made from 65x6mm copper strip on LV side of Transformer with suitable structure and other associated material to connect 3x300 sq.mm XLPE Cable outdoor jointing kit including cost of all material men and T&P. |
| 46 | Fabrication and erection of cable support structure made of two pieces of M.S channel 100x50mm,3.0 Mtr. long joined to each other by means of 5 nosM.S Flat 50x6mm places of size 150mm long each by welding at equal intervals as per drawing and grouting in a block of size300x300x700mm complete with one coat of ready mixed primer and two coats of alluminum paint. This includes provinding of four nos M.S clamp made of M.S flat holding the cable including nuts and bolts and fixing of XLPE Cable |
| 47 | Delta Earthing of 10 MVA T/F's Neutral & 33 KV LA's by consisting of fabrication of 3/6 nos 3.0 Mtr long electrode of 32mm dia having 150mm lonh conical shape,its placing inside the ground in rectangular/tringle shape and connected all 3/6 nos electrodes with 50x6mm M.S flate/GI flate laid on its edge and then this shape be connected to main earth mat/bushing at two place in opposite direction as per technical specification/direction of E/I including cost of material, men and T&P. (a) Neutral Delta Earthing |
| 48 | Delta Earthing of 33 KV LA's by consisting of fabrication of 6 nos 3.0 Mtr long electrode of 32mm dia having 150mm lonh conical shape,its placing inside the ground in rectangular/tringle shape and connected all 6 nos electrodes with 50x6mm M.S flate/GI flate laid on its edge and then this shape be connected to main earth mat/bushing at two place in opposite direction as per technical specification/direction of E/I including cost of material, men and T&P. (b) Lighting Arester Delta Earthing |
| 49 | Construction of Control cable trench of required size 0.30x 0.45 Mtr. complete in all respect as per latest technical specification of DVVNL approved by Engineer in charge. |
| 50 | Providing M.S. frames work for B.C.C. Trench covers and edging with M.S. Angles including cutting bending and vending of M.S. angle and cutting and welding of M.S. bars for reinforcement and lifting books as per approved design. The rate is including cost of all labour, materials etc proper completion of the work. (sl no 502) |
| 51 | Concreting of 40 mm thick RCC trench covers in mild steel frame work with c.c. 1:1:5:3 in cement. Coarse sand and 2 cm gauge graded hard stone ballast with 3 mm thick loathing coat of near cement finish on top of cover complete with all labor, materials T&P etc. required for proper completion of the work but excluding gust of frames.(sl no 5.19) Please Enable Macros to View BoQ information |